Professional Documents
Culture Documents
Thermo Active Building Systems
Thermo Active Building Systems
Institute of Energy System Technology (INES), Offenburg University of Applied Sciences, Badstrasse 24, 77652 Offenburg, Germany
Industrielle Werke Basel (IWB), Margarethenstrasse 40, 4002 Basel, Switzerland
a r t i c l e
i n f o
Article history:
Received 6 June 2016
Received in revised form 2 August 2016
Accepted 3 August 2016
Available online 3 August 2016
Keywords:
Thermo-activate building system (TABS)
Concrete core activation
Adaptive predictive control
Multiple regression
Thermal comfort
Energy savings
a b s t r a c t
There is a growing trend for the use of thermo-active building systems (TABS) for the heating and cooling
of buildings, because these systems are known to be very economical and efcient. However, their control is complicated due to the large thermal inertia, and their parameterization is time-consuming. With
conventional TABS-control strategies, the required thermal comfort in buildings can often not be maintained, particularly if the internal heat sources are suddenly changed. This paper shows measurement
results and evaluations of the operation of a novel adaptive and predictive calculation method, based on
a multiple linear regression (AMLR) for the control of TABS. The measurement results are compared with
the standard TABS strategy. The results show that the electrical pump energy could be reduced by more
than 86%. Including the weather adjustment, it could be demonstrated that thermal energy savings of
over 41% could be reached. In addition, the thermal comfort could be improved due to the possibility to
specify mean room set-point temperatures. With the AMLR, comfort category I of the comfort norms ISO
7730 and DIN EN 15251 are observed in about 95% of occasions. With the standard TABS strategy, only
about 24% are within category I.
2016 Elsevier B.V. All rights reserved.
1. Introduction
From 1990 to 2010, the global primary energy demand increased
by 50% [1]. The building sector is a major consumer of energy. In
2012, the share of nal energy consumption in the European Union
was at 42.6% in the tertiary sector, at 25.6% in the industry sector,
and at 31.8% in the transportation sector [2]. A large part of the tertiary sector accounts for the energy consumption of buildings. Most
of it is needed for their heating and cooling. Therefore, heating and
cooling concepts for renewable energy sources become increasingly important. For this purpose, low-temperature systems such
as thermo-active building systems (TABS) are particularly suitable.
There are different system congurations and designations for
TABS. A very popular and often-used one is known as concrete
core conditioning and concrete core activation. One of the rst
buildings to be equipped with concrete-core activation was built
in Switzerland in 1990/1991 [3]. According to a 2001 market analysis [4], there were a total of more than 60 buildings with TABS in
Germany at that time. In 2007, 508 new buildings were equipped
with 483,000 m2 of concrete-core-activated areas in Germany.
Corresponding author.
E-mail address: martin.schmelas@hs-offenburg.de (M. Schmelas).
URL: http://www.ines.hs-offenburg.de (M. Schmelas).
http://dx.doi.org/10.1016/j.enbuild.2016.08.013
0378-7788/ 2016 Elsevier B.V. All rights reserved.
368
Nomenclature
Q
V
I glob
T amb
T Rs et
TR
a, b, c
d
e
fHC
H
hdd
m
n
P
p
Qmc
Qua
t
Tamb
Ted
Trm
TRW
TR
TSW
u
W
w
y
z
AMLR
BMBF
COP
DIN
EN
F
GF
hist
INES
ISO
IWB
MPC
MWK
OLS
PID
PLC
pred
SIA
TABS
TCP
TF
UBB
VDI
VIP
energy ow
volume ow
mean daily global irradiation
mean daily ambient temperature
set-point mean daily room temperature
mean daily room temperature
variables of the multiple linear regression
time of actual integrated and mean daily values
errors
heating and cooling curve
hysteresis
heating-degree days
measured values
time of historical values
status signal of the control valve, electrical energy
time of predicted values
daily energy of a slab
daily energy demand of a zone
time of actual values
ambient temperature
mean daily ambient temperature
moving average ambient air temperature
return-water temperature
room temperature
supply-water temperature
control signal
weighting function
set-point
control variables
disturbances
adaptive predictive control of TABS based on a multiple linear regression
German Federal Ministry of Education and Research
coefcient of performance
Deutsches Institut fr Normung
Europische Norm
oor
ground oor
historical
Institute of Energy System Technology
International Organization for Standardization
Industrielle Werke Basel
model-based predictive control
Ministry of Science, Research and Arts of BadenWrttemberg, Germany
ordinary least squares
proportional-integral-derivative
programmable logic controller
prediction
Schweizerischer Ingenieur- und Architektenverein
thermo-active building systems
transmission control protocol
top oor
unknown-but-bounded
Verein Deutscher Ingenieure
vacuum insulation panels
(1)
The variable coefcients a, b, and c are determined by the ordinary least squares (OLS) method. The OLS method is the reason
why the AMLR strategy can adapt to different buildings and usage
proles. In the OLS method, it is possible to involve a weighting function W in the calculation of the variable coefcients. The
dependent variables are weighted by a function. Particularly important values are weighted with 1 and unimportant values with 0. A
linear function is chosen in dependency of the age of the historical
days for the weighting function.
Eq. (1) only use historical values in order to determine the
plane coefcients a, b, and c. With weather forecasts of the next
369
Fig. 1. Functional diagram of the AMLR algorithm for one TABS zone with its inputs and outputs.
370
are opened which have an energy demand, and other zones remain
closed. For the standard strategy, no control valves are usually used.
Therefore, each zone is loaded with energy, even if it does not
require any. The neutral zone describes the energy range within
the control valve remains closed. The deviation between the mean
room temperature and its set-point is that low, that no energy must
be supplied to the zone. On weekends, the mean room set-point
temperature does not have to be met. Therefore, a weekend temperature reduction will be applied in addition to a neutral zone. For
this purpose, Qmc,pred will be reduced to a predened value.
The mean room set-point temperature has been set for the
period shown here at 22 C. The neutral zone was dened with
150 Wh/m2 on workdays and with 300 Wh/m2 on weekends. The
weekend temperature reduction is 300 Wh/m2 . The calculation of
the predicted energy packages as well as the loading of the TABS
starts daily at 6:00 p.m.
3. IWB CityCenter building description
(2)
Fig. 2. Exterior view of the IWB CityCenter with advisory center for clients of IWB
on the ground and 1st oor as well as ofces for employees of IWB on the other
oors.
Fig. 3. Hydraulic diagram of the IWB CityCenter with sensors, actuators, the TABS,
the TABS pump, and the heat pump.
371
Fig. 4. Schematic diagram of the integration of the AMLR into the IWB CityCenter.
HP on = TRW,set H
(3)
HP off = TRW,set + H
(4)
there is only one control valve here. In addition, it can be seen that
this is a two-pipe system, i.e. it can only be either heated or cooled.
Other hydraulic variants for the integration of TABS are shown in
[27]. As part of the integration of the AMLR to the building, the
following sensors and actuators were retrotted:
Room-temperature sensors on each oor (previously, they were
only located on the ground, 2nd and top oors),
Fig. 5. Part of the measured data from 10.12.2014 until 12.12.2014 for the room temperatures for three oors, supply temperature, ambient temperature and the thermal
power of the TABS from the IWB CityCenter with the standard TABS strategy.
372
Fig. 6. Part of the measured data from 10.12.2015 until 12.12.2015 for the room temperatures for every oor, supply and return temperatures, ambient temperature and the
thermal power of the TABS from the IWB CityCenter with the AMLR TABS strategy.
(5)
373
Table 1
Percentage of the distribution of the room temperatures during occupancy in accordance with ISO 7730 and DIN EN 15251 for the standard control strategy of TABS
for December 2014.
Ground oor
2. oor
Top oor
Category I
Category II
Category III
53.64%
2.23%
17.19%
37.64%
51.03%
54.35%
8.72%
44.94%
28.45%
Category IV
0%
1.8%
0%
Fig. 7. Room temperatures plotted against the moving average ambient temperature during occupancy, according to ISO 7730/DIN EN 15251 for Dec 2014 (standard TABS
strategy).
374
Fig. 8. Room temperatures plotted against the moving average ambient temperature during occupancy, according to ISO 7730/DIN EN15251 for Dec 2015 (AMLR TABS
strategy).
results can be found in Table 3. As the ambient temperature deviates at around 0.7 K on average, a heating-degree day adjustment
of TABS energy demand was performed according to VDI 3807 [30].
For this purpose, the heating-degree days hdd are calculated with
Eq. (6):
hdd =
z
(T R T amb ),
(6)
Ground oor
1. oor
2. oor
3. oor
4. oor
5. oor
Top oor
Category I
Category II
Category III
Category IV
98.51%
100%
96.19%
86.93%
99.95%
93.19%
92.48%
1.49%
0%
3.81%
13.07%
0.05%
6.81%
7.52%
0%
0%
0%
0%
0%
0%
0%
0%
0%
0%
0%
0%
0%
0%
Table 3
Energy consumption, mean ambient temperature, heating-degree days and savings for December 2014 (standard TABS strategy) and December 2015 (AMLR TABS
strategy) at the IWB Citycenter.
Dec. 2014
Dec. 2015
Savings/
difference
3067 kWh
102.06 kWh
1695 kWh
13.95 kWh
44.73%
86.33%
7.8 C
8.5 C
0.7 K
304.98 Kd
3067 kWh
286.22 Kd
1807 kWh
18.76 Kd
41.08%
V 1
V 2
3
(7)
375
different buildings, which enormously simplied its commissioning. The elaborate parameterization of heating and cooling curves
is not necessary anymore. The algorithm automatically reacts to
changes in internal loads, which would entail a new parameterization of heating and cooling curves in the standard strategy.
In further steps, measured data are to be collected from other
periods so that a statement about the energy-saving potential of an
entire year can be made. In addition, the AMLR will be implemented
in other buildings. By calculating energy packages, the AMLR also
offers the option of load shifts without violating the thermal comfort within the building. This potential is to be quantied in other
investigations.
Acknowledgments
The AMLR has been developed within the scope of a PhD work.
The work has been supported by the Ministry of Science, Research
and Arts (MWK) of Baden-Wrttemberg, Germany, the German
Federal Ministry of Education and Research (BMBF) and the company IWB in the framework of an industry project.
Appendix
Fig. 9. Measured data from 01.12.2014 until 26.12.2014 for the room temperatures for three oors, supply temperature, ambient temperature and the thermal power of the
TABS from the IWB CityCenter with the standard TABS strategy.
376
Fig. 10. Measured data from 01.12.2015 until 26.12.2015 for the room temperatures for every oor, supply and return temperatures, ambient temperature and the thermal
power of the TABS from the IWB CityCenter with the AMLR TABS strategy.
References
[1] U.S. Department of Energys (DOE), Ofce of Energy Efciency and Renewable
Energy, 2011 Buildings Energy Data Book, 2012.
[2] European Union, Statistical Pocketbook 2014, 2014, http://dx.doi.org/10.
2833/24150, URL http://ec.europa.eu/energy/publications/doc/2014
pocketbook.pdf.
[3] G.P. Henze, C. Felsmann, D.E. Kalz, S. Herkel, Primary energy and comfort
performance of ventilation assisted thermo-active building systems in
continental climates, Energy Build. 40 (2) (2008) 99111, http://dx.doi.org/10.
1016/j.enbuild.2007.01.014, URL http://www.sciencedirect.com/science/
article/pii/S0378778807000333.
[4] S. Lohmller, C. Koob, F. Leisering, Das Marktvolumen fr Flchenkhlung in
Deutschland, HLH. Heizung, Lftung/Klima, Haustechnik (60) (2009) 5860.
[5] J.-H. Lim, J.-H. Song, S.-Y. Song, Development of operational guidelines for
thermally activated building system according to heating and cooling load
characteristics, Appl. Energy 126 (0) (2014) 123135, http://dx.doi.org/10.
1016/j.apenergy.2014.03.087, URL http://www.sciencedirect.com/science/
article/pii/S0306261914003274.
[6] J. Pfafferott, D. Kalz, R. Koenigsdorff, Bauteilaktivierung: Einsatz
Praxiserfahrungen Anforderungen, Fraunhofer IRB Verlag, Stuttgart, 2015.
[7] B.W. Olesen, Radiant oor-heating in theory and practice, ASHRAE J. (44)
(2002) 1926.
[8] B.W. Olesen, F.C. Dossi, Operation and control of activated slab heating and
cooling systems, in: Building for the Future: The 16th CIB World Building
Congress, 2004, URL http://www.irbnet.de/daten/iconda/CIB1743.pdf.
[9] B. Olesen, K. Sommer, B. Dchting, Control of slab heating and cooling
systems studied by dynamic computer simulations, ASHRAE Trans. 108 (2)
(2002) 110.
[10] S.H. Cho, M. Zaheer-uddin, An experimental study of multiple parameter
switching control for radiant oor heating systems, Energy 24 (5) (1999)
[11]
[12]
[13]
[14]
[15]
[16]
[17]
[18]
377