Manual
C53000-G1176-C174-3
Application Instructions
Serial Hub
Ethernet hub for transmission of serial data or protocols
from devices with an RS232/RS485/FO interface via Ethernet
English
7XV5655-0BA00
CONTENTS
GENERAL INFORMATION..................................................................................................................................3
APPLICATION........................................................................................................................................................8
DESCRIPTION OF INTERFACES, DIP SWITCHES AND DISPLAYS........................................................11
MOUNTING AND COMMISSIONING ..............................................................................................................16
PRACTICAL SAFETY INFORMATION ...........................................................................................................19
PREPARING THE OPERATING PC OR SERVICE NOTEBOOK................................................................20
THE CONFIGURATION TOOL .........................................................................................................................27
OPTIMISING DATA TRANSFER ......................................................................................................................38
SELECTING A PASSWORD-PROTECTED SERIAL HUB............................................................................40
PIN ASSIGNMENT ...............................................................................................................................................41
TECHNICAL DATA .............................................................................................................................................44
DIMENSIONS ........................................................................................................................................................49
ORDERING INFORMATION .............................................................................................................................50
2 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
General Information
This manual contains the information that is necessary for proper and safe operation of the
products described. This manual is intended for technically qualified personnel having
received special training in, or having special knowledge of protection, measurement and
control engineering, hereinafter called automation engineering. The knowledge and correct
application of the warnings and instructions contained in this manual are prerequisites to
safe installation and commissioning of this product, as well as to proper and safe operation
and maintenance. Only qualified personnel as defined overleaf have the special knowledge
required for correct interpretation of the general safety information and warnings given in
this manual, and for their application to the task in hand. This manual is included in the
scope of delivery. For reasons of clarity, however, it does not purport to contain every detail
of all versions of the product described, nor can it deal with all possible cases of erection,
operation or maintenance. If further information is desired or if special problems arise that
are not treated adequately in this document, it is possible to obtain additional details from
your local Siemens office or from the addresses stated on the back of this manual.
We should also like to point out that the contents of this product documentation are not part
of any previous or existing agreement or legal relationship, nor are they apt to modify such
an agreement or relationship. All obligations incurred by Siemens result from the purchase
contract, which also contains the complete and solely applicable warranty conditions.
Contractual warranty conditions are neither extended nor restricted by the contents of this
document.
Disclaimer of Liability
Copyright
3 / 53
Registered Trademarks
SIPROTEC, SINAUT, SICAM and DIGSI are registered
trademarks of Siemens AG. Other designations in this
manual might be trademarks whose use by third parties for
their own purposes would infringe the rights of the owner.
C53000-G1176-C174-3
English
7XV5655-0BA00
Statement of Conformity
This product complies with the directive of the Council of the
European Communities on the approximation of the laws of the member states relating to
electromagnetic compatibility (EMC Council Directive 2004/108/EC) and concerning
electrical equipment for use within specified voltage limits (Low Voltage Directive
2006/95/EC).
This conformity has been proved by tests performed according to the Council
Directives in agreement with the generic standards EN 61000-6-2
and EN 61000-6-4 (for EMC Directive) and with the standard EN 60255-6 (for Low Voltage
Directive) by Siemens AG.
The device is designed and manufactured for application in industriel environment. The
product conforms with the international standards of IEC 60255 and the German
regulations of VDE 0435.
4 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
Warning
The 7XV5655-0BA00 is specifically intended for installation in a switchgear
cubicle or distribution box.
After installation, the entire area around the terminals must be covered. Only
then is the device sufficiently protected against impermissible contact with
live parts.
5 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
Warning!
Hazardous voltages are present in this electrical equipment during
operation. Severe personal injury or property damage can result if
the device is not handled properly.
Only qualified personnel should work on or around this equipment.
The personnel must be thoroughly familiar with all warnings and
maintenance procedures of this manual as well as the safety
regulations.
Successful and safe operation of the unit is dependent on proper
transportation, storage, erection and assembly and the observance
of the warnings and instructions of the manual.
In particular, the general installation and safety regulations for work
in power current plants (e.g. ANSI, IEC, EN, DIN, or other national
and international regulations) must be observed.
Failure to observe these precautions can result in death, personal
injury, or serious material damage.
Never look into fibre-optic components or the ends of the fibres.
Qualified Personnel
for the purposes of this manual and the warnings on the product
itself, are persons who are acquainted with the erection,
installation, commissioning and operation of the device and who
possess the appropriate qualifications for their task, such as
6 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
Scope of Supply
Installation Instructions
Storage
SIPROTEC devices and associated assemblies should be stored in a dry and clean place.
The device and its replacement modules must be stored within the temperature range 10
C to +55 C.
The relative humidity must not cause condensation or ice.
To avoid premature ageing of the electrolyte capacitors in the power supply unit, a
temperature range of +10 C to +35 C (+50 F to +95 F) is recommended for storage.
After extended storage, the power supply of the device should be energised, approximately
every two years, for one or two days to regenerate the electrolytic capacitors in the power
supply unit. This should also be done before the device is put into service.
7 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
Application
General scope of application
The Serial Hub is designed for operation in industrial zones and substations.
The Serial Hub enables devices with serial interfaces (RS232, RS485, or FO) to convert
data to the UDP protocol and to transmit and receive it via a TCP/IP network. This allows
devices without dedicated network ports to exchange data via the Ethernet.
Hamburg
Ethernet
Berlin
Ethernet
TCP/IP
Ethernet
10/100 Mbps
Serial hub
Measuring
equipment
Serial hub
Parameterisation, e.g.
with a notebook
Serial hub
Safety equipment
Munich
8 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
Application in Substations
Using a 7XV5655-0BA00 Serial Hub with a fixed IP address, one or more SIPROTEC
protection units can exchange serial data via an Ethernet network.
On the operating PC, a configuration tool is used to link virtual COM port with the IP
address of a Serial Hub. Using DIGSI 4 it is then possible to operate all protection units
connected to the Serial Hub via the virtual COM port.
The protection unit is connected to the Serial Hub via its serial interface. The serial interface
types available are RS232 or RS485 (same connector), and FO (fibre optical). The serial
data are converted to the UDP protocol with error detection and correction as useful data in
the Serial Hub and transmitted via the TCP/IP Ethernet network.
The hub meets the requirement for standard compliant, uninterrupted transmission of serial
DIGSI or IEC 60870-5-103/101 frames via the network by listening into the serial frame
traffic and sending the serial IEC telegrams via the Ethernet packed in blocks. Both fullduplex and half-duplex data transmission (RS485) are possible. The serial control lines are
not supported. The Serial Hub can be configured with password protection.
Configuration of the Serial Hub is performed using the configuration tool included in the
scope of supply.
WAN (Private Network)
up
Router / Switch
2
3
4
5
LAN
Patch-Cable
Substationmodem 1
Substationmodem 2
FO-Cable 6XV8100
INPUT
EthernetHub
7XV5655
EthernetHub
7XV5655
RS485-FO
Converter
7XV5650
Mini-Starcoupler
7XV5450
RS485-Bus-Cable 7XV5103
Config-Tool
SIEMENS
SIPROTEC
SIEMENS
RUN
L1 402,1A
L2 402,1A
L3 402,1A
E
00.0A
Max450.1A
Max450.1A
Max450.1A
SIPROTEC
SIEMENS
ERROR
RUN
L1 402,1A
L2 402,1A
L3 402,1A
E
00.0A
Max450.1A
Max450.1A
Max450.1A
RUN
L1 402,1A
L2 402,1A
L3 402,1A
E
00.0A
Anr. L1
Anr. L1
Anr. L1
Anr. L2
Anr. L2
Anr. L2
Anr. L3
Anr. L3
Anr. L3
Anr. Erde
Anr. Erde
Anr. Erde
Automat
Automat
Automat
SIEMENS
SIPROTEC
SIEMENS
ERROR
ERROR
Max450.1A
Max450.1A
Max450.1A
L2 402,1A
L3 402,1A
Max450.1A
Max450.1A
L2 402,1A
L3 402,1A
RUN
RUN
ERROR
ERROR
Anr. L1
Anr. L2
Anr. L1
Anr. L2
Max450.1A
Max450.1A
7XV5101
DIGSI 4
7XV5103
Station-PC for
Remote control
and Configuration for
the Ethernet-Modems
SIPROTEC 4
with EthernetInterface
Max. 31 SIPROTEC 3
Devices with
RS485-Interface
9 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
Features
Serial baudrate and data format to the terminal devices automatically set by the
application, e.g. DIGSI 4 at 2400 Bd to 57.6 kBd (115.2 kBd) with data formats 8N1,
8N2, 8E1.
Reset to default values (factory settings) with INIT button: 9600 baud, 8N1
DIP switch for RS232/RS485 selection and RS485 bus termination and FO idle state
LED displays for operating voltage and data traffic are located on the front panel.
DIN rail module in the plastic housing with integrated wide-range power supply unit
(24 - 250 V DC and 60 - 230 V AC) permits connection to all common substation
batteries or AC power systems.
10 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
DIP switches for RS232/RS485 switchover and RS485 termination and for setting the
FO idle state
AC/DC power supply and protective conductor (PE) connection via 3-way screw
terminal
Communications Interfaces
The RS232/RS485 or FO interfaces are controlled internally by the same processor
interface. The electrical interface is selected via the DIP switches. You can choose between
RS232 or RS485; the FO interface always works parallel with RS232 or RS485 at the
transmitter end and is ORed with RS232/485 at the receiver end, that is, both streams of
receive data are unlocked and are received and evaluated with equal priority. To rule out
data collisions, the connected protection units are addressed selectively by DIGSI. This is
done via the interface address of the protection units.
RS232 Interface
The terminal device (protection unit) (e.g. a
SIPROTEC 4 unit) or a device from the
SIEMENS accessory program (e.g. a 7XV5300
or 7XV5450 star coupler for operating two or
more SIPROTEC devices) can be connected
directly to the RS232 port. The data is
exchanged between the protection unit and the
Serial Hub via this interface.
To use the RS232 interface, DIP switch S2-1
must be set to RS232 and DIP switches S11+2 to (RS485 termination) OFF. The DIP
switch for the FO idle state (S2-2) must be OFF
(see Fig. 3).
Fig. 3: Connectors and DIP switch positions
RS232
Note: The factory settings for all interfaces are 9600 baud / data format 8N1. The settings
are automatically adapted to the terminal device's interface by the application (e.g. DIGSI)
on connection.
11 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
RS485 Interface
The bus-capable RS485 interface provides a
more noise-immune link than the RS232
interface. The data transfer rate is identical
for both interfaces. The terminal device (e.g.
SIPROTEC 4 device) to be operated or up
to 30 further bus-capable SIPROTEC
devices are connected directly to the RS485
port.
FO Interface
The FO interface has a transmitter and
receiver port with an ST connector. It is a
noise-immune link and is used whenever
especially high interference levels are to be
expected in the operating environment or
when equipotential bonding with the
terminal device has to be avoided. The data
transfer rate is that of the RS232 interface.
The terminal device (e.g. a SIPROTEC 4
unit) or a further device from the Siemens
accessory program (e.g. 7XV5300 or
7XV5450 star coupler for operating two or
more SIPROTEC devices) can be
connected directly to the FO port.
12 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
To use the FO interface, DIP switch S2-2 must be set to match the FO idle state of the
communications partner (ON or OFF). DIP switch S2-1 for RS232/485 selection must be
set to RS232. DIP switches S1-1 and S1-2 must be set to OFF (see Fig. 5).
On SIPROTEC units, the idle state is preset to OFF. This is also the as-delivered state of
the Serial Hub.
The 9-way RS232 interface can be used in parallel. If it is not, please cover it with the
red protective cover supplied !
If the FO interface is not used, it must also be covered with the protective covers supplied.
Auxiliary voltage
The auxiliary voltage Vaux (AC/DC) and the protective earth conductor are connected via
three terminals. The wide-range power supply unit has reverse polarity protection (terminals
L+ and L- could be swapped in AC and DC operation) and can be used in substations with
substation batteries, for example. It features double or reinforced insulation and backs up
the auxiliary voltage for >50ms.
GOK Contact
The isolated GOK contact (device run) is for signalling faulty device states. The device
internally monitors the supply voltage and proper functioning of the device.
The contact is open in the normal operating state and closes on faults and auxiliary voltage
failure. It is connected via two terminals (GOK 1+2).
13 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
INIT button
The INIT button is for resetting the Serial Hub to its factory (default) settings and should
only be operated by technically qualified personnel.
It can be used to set a defined baudrate locally for service work. The default baudrate is
9600 8N1. The Serial Hub also outputs a reset string with the date and version number of
the firmware on its serial interface (RS232 / RS485 / FO).
This reset string can be read by a terminal program (e.g. HyperTerminal in Windows) on a
connected PC. The serial interface of the PC must be set to the default baudrate.
You do not need to use the INIT button if you know the baudrate!
Operating the INIT button does not change any settings relevant to security such as IP
addresses or password!
14 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
Meaning of Displays
The LEDs indicate the state of the device and have the following meaning:
GOK
System
LAN
LAN TxD
ERROR
15 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
General
16 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
Warning
Never look into fibre-optic waveguide elements or the ends of the
fibres.
Please observe the permissible bending radii of the optical fibre waveguide (manufacturer
data).
Bending cables to a smaller radius than the minimum bending radius can destroy the FO
fibres.
1.5 mm2
Nominal conductor cross-section 2.5 mm , rigid conductor or with wire end ferrule
Tightening torque
17 / 53
0.5 Nm
C53000-G1176-C174-3
English
7XV5655-0BA00
Ethernet Connection
The Serial Hub is connected to the network, i.e. a router or switch, using a patch cable via
the RJ45 (10BaseT) connector.
The dielectric strength of the Ethernet cable must be at least 300 V AC.
OR
The Serial Hub is connected directly to the LAN port of the operating PC using a cross-over
patch cable via the RJ45 connector.
The "link LAN" LED indicates correct connection with the Ethernet.
If that is not the case, check the network connection or network cable.
Cat5 cables (or better) must be used.
Commissioning
Check whether the operating data match the values on the rating plate. Do not make any
changes on the device that are not described in this manual.
Plug in the connecting cable for the RS232/RS485 and screw it tight or plug in the FO cable
and secure it. If you are not using the Sub D connector for RS232/RS485, attach the red
cover supplied.
Set the DIP switches for serial mode (RS232 / 485 / FO).
18 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
The device is never placed near a heater or the air outlet of an air-conditioning unit.
The device never comes into direct contact with liquids of any kind. Never use liquids
in the vicinity of the device.
Opening the housing can lead to electric shock and other damage. Never make any
changes to the device that are not described in this manual. Doing so could damage
the device and you would have to pay for the repairs.
The mains supply values are the same those stated on the power supply unit. If in
doubt, contact your supplier.
The maximum power rating of the connected cables is not be exceeded and
conductors have the required minimum cross-section.
The line-side fuse is removed before cleaning the device to ensure complete
disconnection from the power source and precautions are taken that prevent
unintentional reconnection.
19 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
20 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
21 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
A checkmark in
"Show icon in notification area when
connected "
has an icon display the status of the
connection in the notification area.
22 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
After you have started the configuration tool, the connected Serial Hub is found
automatically and can be configured (see Section "Configuration tool").
23 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
Under
"Support"
you can look at the settings assigned to the
connection.
Here, the network addresses are
automatically assigned by a DHCP server in
the network.
After you have started the configuration tool, all Serial Hubs connected in the same network
segment are found automatically and can be configured (see Section "Configuration tool").
24 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
Continue with
OK
Note: The Serial Hub data traffic can only be observed via the serial interface in the
currently set baudrate and data format. If these settings were changed, the connection
settings in HyperTerminal would have to be adjusted.
It is advisable to note down these settings to avoid any problems accessing the
Serial Hub later.
25 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
If the Serial Hub is connected to the PC, it is possible to listen in to the data traffic on the
RS232 interface using HyperTerminal.
This is useful, for example, when troubleshooting or to monitor the function of the Serial
Hub after pressing the INIT button.
26 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
Overview Window
The configuration program finds all devices in its own network segment, even those without
a valid IP address.
Clicking on the column header in the overview, e.g. "IP address", sorts the devices in
ascending or descending order of the items in that column.
IP Address
Current IP address
Subnet Mask
Gateway
MAC
Current Gateway
Worldwide unique MAC address
27 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
Device Type
Device Type
Version
Info
In Use
Ping OK
in local Net
Password
Logged in
CPU-ID
General Settings
A unique IP address must first be assigned to each device.
When the Serial Hub is delivered, no valid IP address has been set yet (default: 10.10.5.1).
If the Serial Hub is integrated into a DHCP network, i.e. the available IP addresses are
assigned automatically, the network administrator on the DHCP server must reserve a
fixed IP address for the Serial Hub.
Right-clicking the device entry in the overview window displays a dialog box in which
further actions can be performed.
28 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
Set IP Address
Set Name
Enter the name of the Serial Hub, e.g. "Substation east" for
a better clarity in the table.
Password
If the password has been forgotten, the device must be sent in.
(For address, see last page of this manual)
29 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
Upload Firmware
Look for the new firmware version and import with "Open"
or by double-clicking.
The firmware update resets the Serial Hub to its factory
settings (default values). Passwords are not reset.
If the message: "Cant upload Firmware. See Logging"
appears during a firmware update, please repeat the
upload until the message: "device is up again" appears.
You will find new firmware and manuals under :
www.siprotec.com / Accessories / 7XV5655
Delete
30 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
31 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
Properties
Double-clicking the device entry in the overview window displays a dialog box in which
further settings can be made.
TCP/IP Settings
"Info" displays the
MAC address,
IP address and the
Device name
32 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
The user must select the required format and enter the values for "Fixed frame length" and
"Header length".
The value in the "Fixed frame length" edit box is in the range 2 to 255 bytes.
The value in the "Header length" edit box is in the range 2 to 14 bytes. The value only
refers to "User data" from the header.
Note: For the protocols IEC60870-5-103, VDEW or for the protocol used by DIGSI, the
format FT 1.2 (Header length = 0 byte and Fixed Frame length = 2 byte) is required.
33 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
NOTE : The settings for baudrate, data bits, parity and stop bits are made by the application
(e.g. DIGSI). This establishes a link to the Serial Hub via the driver for the virtual COM
port and transfers the serial interface settings for communication to the terminal device.
34 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
Port assignment
This setting lists the virtual COM ports of the Serial Hubs.
35 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
INet Info
This window provides up-to-date network information.
Trace Route
Ping
The "Start" button transmits a ping to the Serial Hub to ascertain the throughput time of the
telegrams in the network.
Throughput time + 10ms = ideal "Total Timeout" here <10ms + 10ms = 20ms
36 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
About
This window provides information about the program version and the date of creation of this
configuration tool.
If the PC has Internet
access, you can double-click
the image for direct access
to our
Download Area.
All up-to-date documents,
drivers and updates for our
products are available there.
You can also access the download area using an Internet browser at:
www.siprotec.com
37 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
Character timeout
No transmission.
Gap is too small.
Transmission Transmission
to PC
to PC
Transmission
to PC
Transmission because
"Total Timeout" has
expired
Transmission because
the gap between the
characters is larger
than "Char Timeout"
Transmission because
the gap between the
characters is larger
than "Char Timeout"
38 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
2 = Format FT 2
1 = Format FT 1.2
3 = Format FT 3
39 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
Entering a Password
To enter a password, call 'Change Password' from the configuration tool and enter the
password under 'New Password' and then under 'Retype New Password' before pressing
"Enter". The password has up to 8 digits.
To be able to access a password-protected Serial Hub later from the computer from which
the application will be started, the password must be entered on this computer.
40 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
Pin Assignment
The cables for RS232 and RS485 are connected to the same port and selected using
the DIP switches.
RS232 Interface
SERIAL PORT
9-pin SubD connector
Pin
Direction
Definition
Screen
INPUT
OUTPUT
not connected
not connected
not connected
Do not assign !
not connected
RS485 Interface
SERIAL PORT
9-pin SubD connector
Pin
Definition
Screen
Do not assign !
INPUT/
OUTPUT
RS485 Data-A
not connected
not connected
not connected
8
9
41 / 53
Direction
INPUT/
OUTPUT
RS485 Data-B
not connected
C53000-G1176-C174-3
English
7XV5655-0BA00
Ethernet Interface
Ethernet connector
RJ 45
Pin
Name
Definition
TX+
Transmit Data+
TX-
Transmit Data-
RX+
Receive Data+
n/c
not connected
n/c
not connected
RX-
Receive Data-
n/c
not connected
n/c
not connected
L-
L+
Pin
Name
Definition
L+
Vaux+
L-
Vaux-
Earth
Protective Earth
DR Contact
2-way terminal block
DR
42 / 53
Pin
Name
Definition
DR
Isol. DR
DR-NC
Isol. DR-NC
C53000-G1176-C174-3
English
7XV5655-0BA00
Connecting Cable
RS232 connection options:
1) PC/laptop to the protection unit
2) Serial Hub to SIPROTEC 4 or
7XV5300, 7XV5450, 7XV5550, 7XV5652
7XV5100-4/BB
Notebook / PC
9-way female
Notebook / PC
9-way male
Length=3m
RxD
TxD
GND
Housing
Housing
7
8
7XV5103-0AAxx
From serial model
SUB-D connector
9-way male
3
8
xx= length
Further devices
or bus termination
SUB-D connector
9-way female
3 8 Housing
A
B
SIPROTEC
SUB-D connector
9-way male
L=1/3/5/10 m
Housing
L=0.2 m
A
B
3
8
Housing
43 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
Technical Data
Auxiliary voltage
24 V 250 V DC +/-20 %
60 V 230 V AC +/-20 % , 45-65 Hz,
Power input
2.5 W DC
14 VA AC
Line-side fuse
Relays, 1 NC isolated
2-way screw terminal,
1A
250V AC and DC
20 W / 20 VA
3-way terminal
1.5 mm2
Tightening torque
Stripping length:
0.5 Nm
up to 8 mm
FO connection
Connection method
Wavelength
Fibre Type
Baud rate
Protocol
Laser class
Transmit power in dBm , peak (type),
NA = 0.275
Max. optical power for high level
Min. optical power for low level
Optical power budget
NA = 0.275
Range
Ethernet interface
Connection
TCP/IP
44 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
Connection type
Pin assignment
See Pin Assignment
Cable length RS232
Max. 10 m / 3280 feet
Baud rate
2400 to 115200 baud, Rxd, Txd
Parity : None, Even, Odd, Mark, Space
DIP switches
LED displays
Firmware
Driver
Data : 7 or 8 bits
Stop : 1 or 2 bits
RS232 : full-duplex , RS485 : half-duplex
RS232/485 switchover
Idle state FO ON/OFF
RS485 termination
DR (GN): Alarm (Vaux power o.k. and reset o.k.)
COM-TxD (GN) : Transmit - RS232 or RS485 or
FO
COM-TxD (YE) : Receive - RS232 or RS485 or
FO
System (GN) : Connection to the PC via RS232
detected
LAN-TxD (GN) : Transmit Ethernet
LAN-TxD (YE) : Receive - Ethernet
LAN (GN) : Connection to the Ethernet network
Error (RD) : hub error on RS232/Reset
Updatable
Setup & configuration tool
for WINDOWS NT4 / 2000 / XP
Note :
To operate this Serial Hub, Windows XP Home
Edition is sufficient but for DIGSI, XP
Professional is required.
Mechanical design
Housing
Dimensions
Weight:
Plastic
See Dimension Drawings
Approx. 180 g
Safety
Acc. to DIN EN61010 Part 1
Overvoltage category
Pollution degree
Fire resistance class (acc. to UL94)
III
2
V0
45 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
Standards:
Insulation tests
Standards:
Voltage test (100% test) all circuits except
auxiliary voltage and communication
interfaces
Voltage test (100% test) on auxiliary voltage
Voltage test (100% test) only locked
communication interfaces
Surge withstand capability test (type
test) all circuits except communication
interfaces, class III
Warning
- pulse-modulated
Fast transients / bursts
IEC 60255-22-4 and IEC61000-4-4
Class IV
High energy surge voltages (SURGE)
EN61000-4-5 insulation class 3
- Auxiliary voltages
46 / 53
C53000-G1176-C174-3
English
- Relay output
Conducted RF, amplitude-modulated
IEC61000-4-6, Class III
7XV5655-0BA00
common mode; 2 KV; 42 ; 0.5 F
differential mode : 1 KV; 42 ; 0.5 F
10 V; 150 KHz 80 MHz; 80 % AM, 1 KHz
0.5 mT; 50 Hz
Class IV: 30 A/m continuous; 300 A/m for 3s; 50Hz
2.5 KV (peak); 1 MHz; = 15 s; 400 surges per s;
test duration 2s; Ri = 200
4 kV; 5/50 ns; 5 kHz; burst length = 15 ms;
Repeat rate 300 ms; pos./neg. polarity;
test duration 1 min.; Ri = 50
2.5 kV (peak value), polarity alternating 100 kHz,
1 MHz, Ri = 200
47 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
Climatic tests
0 C to 55 C
-5 C to +70 C
Humidity
Maximum relative humidity
80 % at temperatures up to 31 C,
decreasing linearly down to 50 % at 40 C
Installation altitude
Maximum height above sea level
2,000 m
All devices shall be installed so that they are not exposed to direct sunlight, nor subject to great
fluctuations in temperature that may cause condensation.
48 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
Dimensions
49 / 53
C53000-G1176-C174-3
English
7XV5655-0BA00
Ordering Information
Name
Order No.
Serial Hub
7 X V 5 6 5 5
0 B A 0 0
10BaseT connection
10/100 Mbits, RJ45 connector
Serial RS232/485 interface
9-way Sub D connector
Gender changer (male-male)
FO interface, ST connection
DIN rail mounted device for 35mm rail
Aux. voltage 24-250 VDC / 60-230 VAC
50 / 53
C53000-G1176-C174-3
nderungen vorbehalten
Subject to change without prior notice
SIEMENS AKTIENGESELLSCHAFT
Siemens AG
Siemens AG
PTD EA P
Rckwarenabteilung
Humboldtstrasse 59
Wernerwerkdamm 5
D-90459 Nrnberg
D-13629 Berlin
: ptd.support@siemens.com
www.SIPROTEC.de
If you have any notes or questions on
this product please contact :
Siemens AG
Siemens AG
PTD EA P ACC2
Returned Goods Customer Service
Humboldtstrasse 59
Wernerwerkdamm 5
D-90459 Nrnberg
D-13629 Berlin
: ptd.support@siemens.com
Further information regarding our products is to be found in our download area in the
Internet:
www.SIPROTEC.com
SIEMENS AKTIENGESELLSCHAFT