Alfanar Low Voltage Control Cables Catalog
Alfanar Low Voltage Control Cables Catalog
To IEC Standard
CONSTRUCTION
Conductor
Insulation
Outer sheath :
APPLICATION
For use indoors in cable trenches or ducts; and outdoors - for connecting signaling and control
units in industries, railways, trafc signals, power stations, industrial plants and switchgears if
mechanical protection is not required, or in applications where the cable is not exposed to
mechanical damage.
TECHNICAL DATA
- Nominal voltage Uo/U = 0.6/1 kV
- Power frequency test voltage 3.5 kV for 5 minutes
- Max. admissible temperature of conductor at normal operation 70 C
- Max. admissible temperature of conductor at short circuit 160 C for 5 seconds
DC at 20 C
AC at 70 C
No. X mm
/ km
/ km
5 X 1.5
7 X 1.5
10 X 1.5
12 X 1.5
14 X 1.5
16 X 1.5
19 X 1.5
24 X 1.5
30 X 1.5
37 X 1.5
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
37
DIMENSIONS
AND WEIGHTS
ELECTRICAL DATA
Number &
Nominal
cross
sectional
area
Current Rating
Laid in
ground
A
Laid in
ducts
A
1.5 mm2
18.0
16.0
14.0
13.0
12.0
11.0
10.0
9.0
8.0
7.5
15.5
14.0
12.5
11.5
10.5
10.0
9.0
8.0
7.5
6.5
Approx.
overall
diameter
Approx.
overall
weight
mm
Kg / km
13.5
12.5
11.5
10.5
9.5
9.0
8.0
7.5
6.5
6.0
11.8
12.7
15.7
16.2
17.0
17.8
18.7
21.7
23.8
24.7
200
250
340
385
435
490
560
700
850
1000
Laid in
free air
AES Code
C108PA10500CBK12IMR
C108PA10700CBK21IMR
C108PA11000CBK21IMR
C108PA11200CBK21IMR
C108PA11400CBK21IMR
C108PA11600CBK21IMR
C108PA11900CBK21IMR
C108PA12400CBK21IMF
C108PA13000CBK21IMF
C108PA13700CBK21IMF
DC at 20 C
AC at 70 C
No. X mm
/ km
/ km
5 X 2.5
7 X 2.5
10 X 2.5
12 X 2.5
14 X 2.5
16 X 2.5
19 X 2.5
24 X 2.5
30 X 2.5
37 X 2.5
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
5 X 4.0
7 X 4.0
10 X 4.0
12 X 4.0
14 X 4.0
16 X 4.0
19 X 4.0
24 X 4.0
30 X 4.0
37 X 4.0
DIMENSIONS
AND WEIGHTS
ELECTRICAL DATA
Number &
Nominal
cross
sectional
area
2
0.6 / 1 kV
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
Current Rating
Laid in
ground
A
24.0
22.0
20.0
18.0
16.0
15.0
14.0
13.0
11.5
10.0
31.0
28.0
25.0
23.0
20.5
19.5
18.0
16.0
14.5
13.0
Laid in
ducts
A
2.5 mm
20.5
18.5
16.5
15.5
14.0
13.0
12.0
11.0
10.0
9.0
4.0 mm2
25.5
23.0
21.0
19.5
17.0
16.0
15.0
13.5
12.0
11.0
Approx.
overall
diameter
Approx.
overall
weight
mm
Kg / km
18.0
16.0
14.5
13.5
12.0
11.0
10.5
9.5
8.5
7.5
12.9
13.8
17.2
17.7
18.6
19.6
20.6
24.0
25.4
27.4
260
330
450
540
600
670
780
1030
1160
1410
C110PA10500CBK12IMR
24.0
21.5
19.5
18.0
16.0
15.0
14.0
12.5
11.0
10.0
15.3
16.5
20.8
21.5
22.6
23.8
25.1
29.6
31.6
34.1
430
480
670
780
890
1000
1170
1460
1830
2320
C112PA10500CBK12IMR
Laid in
free air
AES Code
C110PA10700CBK21IMR
C110PA11000CBK21IMR
C110PA11200CBK21IMR
C110PA11400CBK21IMR
C110PA11600CBK21IMR
C110PA11900CBK21IMR
C110PA12400CBK21IMF
C110PA13000CBK21IMF
C110PA13700CBK21IMF
C112PA10700CBK21IMR
C112PA11000CBK21IMR
C112PA11200CBK21IMR
C112PA11400CBK21IMR
C112PA11600CBK21IMR
C112PA11900CBK21IMR
C112PA12400CBK21IMF
C112PA13000CBK21IMF
C112PA13700CBK21IMF
CONSTRUCTION
Conductor
Insulation
Outer sheath :
APPLICATION
For use indoors in cable trenches or ducts; and outdoors - for connecting signaling and control
units in industries, railways, trafc signals, power stations, industrial plants and switchgears if
mechanical protection is not required, or in applications where the cable is not exposed to
mechanical damage.
TECHNICAL DATA
- Nominal voltage Uo/U = 0.6/1 kV
- Power frequency test voltage 3.5 kV for 5 minutes
- Max. admissible temperature of conductor at normal operation 70 C
- Max. admissible temperature of conductor at short circuit 160 C for 5 seconds
DC at 20 C
AC at 70 C
No. X mm
/ km
/ km
5 X 1.5
7 X 1.5
10 X 1.5
12 X 1.5
14 X 1.5
16 X 1.5
19 X 1.5
24 X 1.5
30 X 1.5
37 X 1.5
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
39
DIMENSIONS
AND WEIGHTS
ELECTRICAL DATA
Number &
Nominal
cross
sectional
area
Current Rating
Laid in
ground
A
Laid in
ducts
A
1.5 mm2
18.0
16.0
14.0
13.0
12.0
11.0
10.0
9.0
8.0
7.5
15.5
14.0
12.5
11.5
10.5
10.0
9.0
8.0
7.5
6.5
Approx.
overall
diameter
Approx.
overall
weight
mm
Kg / km
13.5
12.5
11.5
10.5
9.5
9.0
8.0
7.5
6.5
6.0
12.3
13.3
16.5
17.0
17.8
18.7
19.7
22.9
24.2
26.1
215
265
360
410
465
530
600
740
890
1070
Laid in
free air
AES Code
C208PA10500CBK12IMR
C208PA10700CBK21IMR
C208PA11000CBK21IMR
C208PA11200CBK21IMR
C208PA11400CBK21IMR
C208PA11600CBK21IMR
C208PA11900CBK21IMR
C208PA12400CBK21IMF
C208PA13000CBK21IMF
C208PA13700CBK21IMF
DC at 20 C
AC at 70 C
No. X mm
/ km
/ km
5 X 2.5
7 X 2.5
10 X 2.5
12 X 2.5
14 X 2.5
16 X 2.5
19 X 2.5
24 X 2.5
30 X 2.5
37 X 2.5
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
5 X 4.0
7 X 4.0
10 X 4.0
12 X 4.0
14 X 4.0
16 X 4.0
19 X 4.0
24 X 4.0
30 X 4.0
37 X 4.0
DIMENSIONS
AND WEIGHTS
ELECTRICAL DATA
Number &
Nominal
cross
sectional
area
2
0.6 / 1 kV
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
Current Rating
Laid in
ground
A
Laid in
ducts
2.5 mm
24.0
22.0
20.0
18.0
16.0
15.0
14.0
13.0
11.5
10.0
20.5
18.5
16.5
15.5
14.0
13.0
12.0
11.0
10.0
9.0
4.0 mm2
31.0
28.0
25.0
23.0
20.5
19.5
18.0
16.0
14.5
13.0
25.5
23.0
21.0
19.5
17.0
16.0
15.0
13.5
12.0
11.0
Approx.
overall
diameter
Approx.
overall
weight
mm
Kg / km
18.0
16.0
14.5
13.5
12.0
11.0
10.5
9.5
8.5
7.5
13.4
14.5
18.1
18.7
19.6
20.6
21.7
25.3
26.8
28.9
275
350
480
555
630
710
820
1020
1235
1495
C210PA10500CBK12IMR
24.0
21.5
19.5
18.0
16.0
15.0
14.0
12.5
11.0
10.0
16.1
17.4
22.0
22.7
23.9
25.2
26.6
31.4
33.5
36.2
410
520
720
840
950
1070
1260
1580
1965
2510
C212PA10500CBK12IMR
Laid in
free air
AES Code
C210PA10700CBK21IMR
C210PA11000CBK21IMR
C210PA11200CBK21IMR
C210PA11400CBK21IMR
C210PA11600CBK21IMR
C210PA11900CBK21IMR
C210PA12400CBK21IMF
C210PA13000CBK21IMF
C210PA13700CBK21IMF
C212PA10700CBK21IMR
C212PA11000CBK21IMR
C212PA11200CBK21IMR
C212PA11400CBK21IMR
C212PA11600CBK21IMR
C212PA11900CBK21IMR
C212PA12400CBK21IMF
C212PA13000CBK21IMF
C212PA13700CBK21IMF
CONSTRUCTION
Conductor
Insulation
Bedding
Shielding
Outer sheath :
APPLICATION
For use indoors in cable trenches or ducts; and outdoors - for connecting signaling and control
units in industries, railways, trafc signals, power stations, industrial plants and switchgears if
mechanical protection is not required, or in applications where the cable is not exposed to
mechanical damage.
TECHNICAL DATA
- Nominal voltage Uo/U = 0.6/1 kV
- Power frequency test voltage 3.5 kV for 5 minutes
- Max. admissible temperature of conductor at normal operation 70 C
- Max. admissible temperature of conductor at short circuit 160 C for 5 seconds
41
DIMENSIONS
AND WEIGHTS
ELECTRICAL DATA
Number &
Nominal
cross
sectional
area
DC at 20 C
AC at 70 C
No. X mm2
/ km
/ km
5 X 1.5
7 X 1.5
10 X 1.5
12 X 1.5
14 X 1.5
16 X 1.5
19 X 1.5
24 X 1.5
30 X 1.5
37 X 1.5
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
Current Rating
Laid in
ground
A
18.0
16.0
14.0
13.0
12.0
11.0
10.0
9.0
8.0
7.5
Laid in
ducts
A
1.5 mm2
15.5
14.0
12.5
11.5
10.5
10.0
9.0
8.0
7.5
6.5
Approx.
overall
diameter
Approx.
overall
weight
mm
Kg / km
13.5
12.5
11.5
10.5
9.5
9.0
8.0
7.5
6.5
6.0
14.2
15.1
18.1
18.6
19.4
20.2
21.1
25.3
27.5
29.4
305
350
465
520
575
635
715
930
1115
1205
Laid in
free air
AES Code
C108PA105N0CBK12IMR
C108PA107N0CBK21IMR
C108PA110N0CBK21IMR
C108PA112N0CBK21IMR
C108PA114N0CBK21IMR
C108PA116N0CBK21IMR
C108PA119N0CBK21IMR
C108PA124N0CBK21IMF
C108PA130N0CBK21IMF
C108PA137N0CBK21IMF
DC at 20 C
AC at 70 C
No. X mm
/ km
/ km
5 X 2.5
7 X 2.5
10 X 2.5
12 X 2.5
14 X 2.5
16 X 2.5
19 X 2.5
24 X 2.5
30 X 2.5
37 X 2.5
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
5 X 4.0
7 X 4.0
10 X 4.0
12 X 4.0
14 X 4.0
16 X 4.0
19 X 4.0
24 X 4.0
30 X 4.0
37 X 4.0
DIMENSIONS
AND WEIGHTS
ELECTRICAL DATA
Number &
Nominal
cross
sectional
area
2
0.6 / 1 kV
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
Current Rating
Laid in
ground
A
24.0
22.0
20.0
18.0
16.0
15.0
14.0
13.0
11.5
10.0
31.0
28.0
25.0
23.0
20.5
19.5
18.0
16.0
14.5
13.0
Laid in
ducts
A
2.5 mm
20.5
18.5
16.5
15.5
14.0
13.0
12.0
11.0
10.0
9.0
4.0 mm2
25.5
23.0
21.0
19.5
17.0
16.0
15.0
13.5
12.0
11.0
Approx.
overall
diameter
Approx.
overall
weight
mm
Kg / km
18.0
16.0
14.5
13.5
12.0
11.0
10.5
9.5
8.5
7.5
15.1
16.2
19.6
20.1
21.0
22.0
23.0
26.4
27.8
30.0
380
450
560
650
750
830
970
1260
1380
1670
C110PA105N0CBK12IMR
24.0
21.5
19.5
18.0
16.0
15.0
14.0
12.5
11.0
10.0
18.5
19.9
23.2
23.9
25.0
26.2
27.5
32.0
34.0
36.7
540
670
800
920
1080
1230
1430
1780
2210
2790
C112PA105N0CBK12IMR
Laid in
free air
AES Code
C110PA107N0CBK21IMR
C110PA110N0CBK21IMR
C110PA112N0CBK21IMR
C110PA114N0CBK21IMR
C110PA116N0CBK21IMR
C110PA119N0CBK21IMR
C110PA124N0CBK21IMF
C110PA130N0CBK21IMF
C110PA137N0CBK21IMF
C112PA107N0CBK21IMR
C112PA110N0CBK21IMR
C112PA112N0CBK21IMR
C112PA114N0CBK21IMR
C112PA116N0CBK21IMR
C112PA119N0CBK21IMR
C112PA124N0CBK21IMF
C112PA130N0CBK21IMF
C112PA137N0CBK21IMF
CONSTRUCTION
Conductor
Insulation
Bedding
Shielding
Outer sheath :
APPLICATION
For use indoors in cable trenches or ducts; and outdoors - for connecting signaling and control
units in industries, railways, trafc signals, power stations, industrial plants and switchgears if
mechanical protection is not required, or in applications where the cable is not exposed to
mechanical damage.
TECHNICAL DATA
- Nominal voltage Uo/U = 0.6/1 kV
- Power frequency test voltage 3.5 kV for 5 minutes
- Max. admissible temperature of conductor at normal operation 70 C
- Max. admissible temperature of conductor at short circuit 160 C for 5 seconds
43
DIMENSIONS
AND WEIGHTS
ELECTRICAL DATA
Number &
Nominal
cross
sectional
area
DC at 20 C
AC at 70 C
No. X mm2
/ km
/ km
5 X 1.5
7 X 1.5
10 X 1.5
12 X 1.5
14 X 1.5
16 X 1.5
19 X 1.5
24 X 1.5
30 X 1.5
37 X 1.5
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
Current Rating
Laid in
ground
A
18.0
16.0
14.0
13.0
12.0
11.0
10.0
9.0
8.0
7.5
Laid in
ducts
A
1.5 mm2
15.5
14.0
12.5
11.5
10.5
10.0
9.0
8.0
7.5
6.5
Approx.
overall
diameter
Approx.
overall
weight
mm
Kg / km
13.5
12.5
11.5
10.5
9.5
9.0
8.0
7.5
6.5
6.0
15.7
16.5
18.9
19.4
20.2
21.1
22.1
25.3
27.5
28.5
340
370
495
550
610
670
760
930
1115
1290
Laid in
free air
AES Code
C208PA105N0CBK12IMR
C208PA107N0CBK21IMR
C208PA110N0CBK21IMR
C208PA112N0CBK21IMR
C208PA114N0CBK21IMR
C208PA116N0CBK21IMR
C208PA119N0CBK21IMR
C208PA124N0CBK21IMF
C208PA130N0CBK21IMF
C208PA137N0CBK21IMF
DC at 20 C
AC at 70 C
No. X mm
/ km
/ km
5 X 2.5
7 X 2.5
10 X 2.5
12 X 2.5
14 X 2.5
16 X 2.5
19 X 2.5
24 X 2.5
30 X 2.5
37 X 2.5
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
5 X 4.0
7 X 4.0
10 X 4.0
12 X 4.0
14 X 4.0
16 X 4.0
19 X 4.0
24 X 4.0
30 X 4.0
37 X 4.0
DIMENSIONS
AND WEIGHTS
ELECTRICAL DATA
Number &
Nominal
cross
sectional
area
2
0.6 / 1 kV
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
Current Rating
Laid in
ground
A
24.0
22.0
20.0
18.0
16.0
15.0
14.0
13.0
11.5
10.0
31.0
28.0
25.0
23.0
20.5
19.5
18.0
16.0
14.5
13.0
Laid in
ducts
A
2.5 mm
20.5
18.5
16.5
15.5
14.0
13.0
12.0
11.0
10.0
9.0
4.0 mm2
25.5
23.0
21.0
19.5
17.0
16.0
15.0
13.5
12.0
11.0
Approx.
overall
diameter
Approx.
overall
weight
mm
Kg / km
18.0
16.0
14.5
13.5
12.0
11.0
10.5
9.5
8.5
7.5
15.8
16.9
20.5
21.1
22.0
23.0
24.1
27.7
26.8
31.5
390
470
630
710
800
875
1000
1225
1240
1750
C210PA105N0CBK12IMR
24.0
21.5
19.5
18.0
16.0
15.0
14.0
12.5
11.0
10.0
18.5
19.9
24.4
25.2
26.3
27.6
29.0
33.8
35.9
38.8
540
670
850
980
1160
1310
1520
1900
2350
2970
C212PA105N0CBK12IMR
Laid in
free air
AES Code
C210PA107N0CBK21IMR
C210PA110N0CBK21IMR
C210PA112N0CBK21IMR
C210PA114N0CBK21IMR
C210PA116N0CBK21IMR
C210PA119N0CBK21IMR
C210PA124N0CBK21IMF
C210PA130N0CBK21IMF
C210PA137N0CBK21IMF
C212PA107N0CBK21IMR
C212PA110N0CBK21IMR
C212PA112N0CBK21IMR
C212PA114N0CBK21IMR
C212PA116N0CBK21IMR
C212PA119N0CBK21IMR
C212PA124N0CBK21IMF
C212PA130N0CBK21IMF
C212PA137N0CBK21IMF
CONSTRUCTION
Conductor
Insulation
Bedding
Armouring
Outer sheath :
APPLICATION
For outdoor installations, for connecting signaling and control units in industries, railways,
trafc signals, power stations, industrial plants and switchgears if mechanical protection is
required, or in applications where mechanical damages are expected to occur.
TECHNICAL DATA
- Nominal voltage Uo/U = 0.6/1 kV
- Power frequency test voltage 3.5 kV for 5 minutes
- Max. admissible temperature of conductor at normal operation 70 C
- Max. admissible temperature of conductor at short circuit 160 C for 5 seconds
45
DIMENSIONS
AND WEIGHTS
ELECTRICAL DATA
Number &
Nominal
cross
sectional
area
DC at 20 C
AC at 70 C
No. X mm2
/ km
/ km
5 X 1.5
7 X 1.5
10 X 1.5
12 X 1.5
14 X 1.5
16 X 1.5
19 X 1.5
24 X 1.5
30 X 1.5
37 X 1.5
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
Current Rating
Laid in
ground
A
18.0
16.0
14.0
13.0
12.0
11.0
10.0
9.0
8.0
7.5
Laid in
ducts
A
1.5 mm2
15.5
14.0
12.5
11.5
10.5
10.0
9.0
8.0
7.5
6.5
Approx.
overall
diameter
Approx.
overall
weight
mm
Kg / km
13.5
12.5
11.5
10.5
9.5
9.0
8.0
7.5
6.5
6.0
15.0
15.5
18.5
19.0
20.6
21.0
21.5
24.5
25.8
27.5
355
410
540
590
670
720
800
970
1170
1315
Laid in
free air
AES Code
C108PA1050GCBK12IMR
C108PA1070GCBK21IMR
C108PA1100GCBK21IMR
C108PA1120GCBK21IMR
C108PA1140GCBK21IMR
C108PA1160GCBK21IMR
C108PA1190GCBK21IMR
C108PA1240GCBK21IMF
C108PA1300GCBK21IMF
C108PA1370GCBK21IMF
DC at 20 C
AC at 70 C
No. X mm
/ km
/ km
5 X 2.5
7 X 2.5
10 X 2.5
12 X 2.5
14 X 2.5
16 X 2.5
19 X 2.5
24 X 2.5
30 X 2.5
37 X 2.5
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
5 X 4.0
7 X 4.0
10 X 4.0
12 X 4.0
14 X 4.0
16 X 4.0
19 X 4.0
24 X 4.0
30 X 4.0
37 X 4.0
DIMENSIONS
AND WEIGHTS
ELECTRICAL DATA
Number &
Nominal
cross
sectional
area
2
0.6 / 1 kV
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
Current Rating
Laid in
ground
A
24.0
22.0
20.0
18.0
16.0
15.0
14.0
13.0
11.5
10.0
31.0
28.0
25.0
23.0
20.5
19.5
18.0
16.0
14.5
13.0
Laid in
ducts
A
2.5 mm
20.5
18.5
16.5
15.5
14.0
13.0
12.0
11.0
10.0
9.0
4.0 mm2
25.5
23.0
21.0
19.5
17.0
16.0
15.0
13.5
12.0
11.0
Approx.
overall
diameter
Approx.
overall
weight
mm
Kg / km
18.0
16.0
14.5
13.5
12.0
11.0
10.5
9.5
8.5
7.5
15.5
16.6
20.0
20.5
21.4
22.4
23.4
27.0
28.2
30.5
340
495
650
760
820
920
1030
1260
1520
1830
C110PA1050GCBK12IMR
24.0
21.5
19.5
18.0
16.0
15.0
14.0
12.5
11.0
10.0
18.9
20.3
23.6
24.1
25.4
26.6
28.1
32.6
34.4
37.3
610
710
890
1140
1180
1300
1500
1890
2480
3030
C112PA1050GCBK12IMR
Laid in
free air
AES Code
C110PA1070GCBK21IMR
C110PA1100GCBK21IMR
C110PA1120GCBK21IMR
C110PA1140GCBK21IMR
C110PA1160GCBK21IMR
C110PA1190GCBK21IMR
C110PA1240GCBK21IMF
C110PA1300GCBK21IMF
C110PA1370GCBK21IMF
C112PA1070GCBK21IMR
C112PA1100GCBK21IMR
C112PA1120GCBK21IMR
C112PA1140GCBK21IMR
C112PA1160GCBK21IMR
C112PA1190GCBK21IMR
C112PA1240GCBK21IMF
C112PA1300GCBK21IMF
C112PA1370GCBK21IMF
CONSTRUCTION
Conductor
Insulation
Bedding
Armouring
Outer sheath :
APPLICATION
For outdoor installations, for connecting signaling and control units in industries, railways,
trafc signals, power stations, industrial plants and switchgears if mechanical protection is
required, or in applications where mechanical damages are expected to occur.
TECHNICAL DATA
- Nominal voltage Uo/U = 0.6/1 kV
- Power frequency test voltage 3.5 kV for 5 minutes
- Max. admissible temperature of conductor at normal operation 70 C
- Max. admissible temperature of conductor at short circuit 160 C for 5 seconds
DC at 20 C
AC at 70 C
No. X mm
/ km
/ km
5 X 1.5
7 X 1.5
10 X 1.5
12 X 1.5
14 X 1.5
16 X 1.5
19 X 1.5
24 X 1.5
30 X 1.5
37 X 1.5
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
47
DIMENSIONS
AND WEIGHTS
ELECTRICAL DATA
Number &
Nominal
cross
sectional
area
Current Rating
Laid in
ground
A
18.0
16.0
14.0
13.0
12.0
11.0
10.0
9.0
8.0
7.5
Laid in
ducts
A
1.5 mm
15.5
14.0
12.5
11.5
10.5
10.0
9.0
8.0
7.5
6.5
Approx.
overall
diameter
Approx.
overall
weight
mm
Kg / km
13.5
12.5
11.5
10.5
9.5
9.0
8.0
7.5
6.5
6.0
15.3
17.0
19.3
19.8
21.0
21.9
22.5
25.7
27.3
28.9
350
430
570
625
690
800
850
1030
1185
1400
Laid in
free air
AES Code
C208PA1050GCBK12IMR
C208PA1070GCBK21IMR
C208PA1100GCBK21IMR
C208PA1120GCBK21IMR
C208PA1140GCBK21IMR
C208PA1160GCBK21IMR
C208PA1190GCBK21IMR
C208PA1240GCBK21IMF
C208PA1300GCBK21IMF
C208PA1370GCBK21IMF
DC at 20 C
AC at 70 C
No. X mm
/ km
/ km
5 X 2.5
7 X 2.5
10 X 2.5
12 X 2.5
14 X 2.5
16 X 2.5
19 X 2.5
24 X 2.5
30 X 2.5
37 X 2.5
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
5 X 4.0
7 X 4.0
10 X 4.0
12 X 4.0
14 X 4.0
16 X 4.0
19 X 4.0
24 X 4.0
30 X 4.0
37 X 4.0
DIMENSIONS
AND WEIGHTS
ELECTRICAL DATA
Number &
Nominal
cross
sectional
area
2
0.6 / 1 kV
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
Current Rating
Laid in
ground
A
24.0
22.0
20.0
18.0
16.0
15.0
14.0
13.0
11.5
10.0
31.0
28.0
25.0
23.0
20.5
19.5
18.0
16.0
14.5
13.0
Laid in
ducts
A
2.5 mm
20.5
18.5
16.5
15.5
14.0
13.0
12.0
11.0
10.0
9.0
4.0 mm2
25.5
23.0
21.0
19.5
17.0
16.0
15.0
13.5
12.0
11.0
Approx.
overall
diameter
Approx.
overall
weight
mm
Kg / km
18.0
16.0
14.5
13.5
12.0
11.0
10.5
9.5
8.5
7.5
16.2
17.3
20.9
21.5
22.4
23.4
24.5
28.1
30.3
31.9
440
530
710
790
880
970
1090
1340
1630
1875
C210PA1050GCBK12IMR
24.0
21.5
19.5
18.0
16.0
15.0
14.0
12.5
11.0
10.0
19.1
20.4
24.9
25.6
26.7
28.0
29.4
34.4
36.5
39.4
660
740
960
1120
1270
1390
1610
2030
2660
3250
C212PA1050GCBK12IMR
Laid in
free air
AES Code
C210PA1070GCBK21IMR
C210PA1100GCBK21IMR
C210PA1120GCBK21IMR
C210PA1140GCBK21IMR
C210PA1160GCBK21IMR
C210PA1190GCBK21IMR
C210PA1240GCBK21IMF
C210PA1300GCBK21IMF
C210PA1370GCBK21IMF
C212PA1070GCBK21IMR
C212PA1100GCBK21IMR
C212PA1120GCBK21IMR
C212PA1140GCBK21IMR
C212PA1160GCBK21IMR
C212PA1190GCBK21IMR
C212PA1240GCBK21IMF
C212PA1300GCBK21IMF
C212PA1370GCBK21IMF
CONSTRUCTION
Conductor
Insulation
Bedding
Armouring
Outer sheath :
APPLICATION
For outdoor installations, for connecting signaling and control units in industries, railways,
trafc signals, power stations, industrial plants and switchgears if mechanical protection is
required, or in applications where mechanical damages are expected to occur.
TECHNICAL DATA
- Nominal voltage Uo/U = 0.6/1 kV
- Power frequency test voltage 3.5 kV for 5 minutes
- Max. admissible temperature of conductor at normal operation 70 C
- Max. admissible temperature of conductor at short circuit 160 C for 5 seconds
DC at 20 C
AC at 70 C
No. X mm
/ km
/ km
5 X 1.5
7 X 1.5
10 X 1.5
12 X 1.5
14 X 1.5
16 X 1.5
19 X 1.5
24 X 1.5
30 X 1.5
37 X 1.5
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
49
DIMENSIONS
AND WEIGHTS
ELECTRICAL DATA
Number &
Nominal
cross
sectional
area
Current Rating
Laid in
ground
A
18.0
16.0
14.0
13.0
12.0
11.0
10.0
9.0
8.0
7.5
Laid in
ducts
A
1.5 mm
15.5
14.0
12.5
11.5
10.5
10.0
9.0
8.0
7.5
6.5
Approx.
overall
diameter
Approx.
overall
weight
mm
Kg / km
13.5
12.5
11.5
10.5
9.5
9.0
8.0
7.5
6.5
6.0
16.0
17.2
20.2
22.5
23.3
24.2
25.2
28.0
30.1
33.0
470
530
740
1050
1110
1220
1320
1530
1800
2180
Laid in
free air
AES Code
C108PA1050WCBK12IMR
C108PA1070WCBK21IMR
C108PA1100WCBK21IMR
C108PA1120WCBK21IMR
C108PA1140WCBK21IMR
C108PA1160WCBK21IMR
C108PA1190WCBK21IMR
C108PA1240WCBK21IMF
C108PA1300WCBK21IMF
C108PA1370WCBK21IMF
DC at 20 C
AC at 70 C
No. X mm
/ km
/ km
5 X 2.5
7 X 2.5
10 X 2.5
12 X 2.5
14 X 2.5
16 X 2.5
19 X 2.5
24 X 2.5
30 X 2.5
37 X 2.5
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
5 X 4.0
7 X 4.0
10 X 4.0
12 X 4.0
14 X 4.0
16 X 4.0
19 X 4.0
24 X 4.0
30 X 4.0
37 X 4.0
DIMENSIONS
AND WEIGHTS
ELECTRICAL DATA
Number &
Nominal
cross
sectional
area
2
0.6 / 1 kV
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
Current Rating
Laid in
ground
A
24.0
22.0
20.0
18.0
16.0
15.0
14.0
13.0
11.5
10.0
31.0
28.0
25.0
23.0
20.5
19.5
18.0
16.0
14.5
13.0
Laid in
ducts
A
2.5 mm
20.5
18.5
16.5
15.5
14.0
13.0
12.0
11.0
10.0
9.0
4.0 mm2
25.5
23.0
21.0
19.5
17.0
16.0
15.0
13.5
12.0
11.0
Approx.
overall
diameter
Approx.
overall
weight
mm
Kg / km
18.0
16.0
14.5
13.5
12.0
11.0
10.5
9.5
8.5
7.5
17.2
18.4
22.9
24.2
25.1
26.1
27.4
30.5
33.7
36.6
570
640
1125
1240
1350
1470
1620
1970
2380
2790
C110PA1050WCBK12IMR
24.0
21.5
19.5
18.0
16.0
15.0
14.0
12.5
11.0
10.0
20.2
22.7
26.3
28.2
29.2
30.8
32.1
37.5
40.4
43.3
750
1150
1460
1650
1790
1980
2150
3010
3430
4020
C112PA1050WCBK12IMR
Laid in
free air
AES Code
C110PA1070WCBK21IMR
C110PA1100WCBK21IMR
C110PA1120WCBK21IMR
C110PA1140WCBK21IMR
C110PA1160WCBK21IMR
C110PA1190WCBK21IMR
C110PA1240WCBK21IMF
C110PA1300WCBK21IMF
C110PA1370WCBK21IMF
C112PA1070WCBK21IMR
C112PA1100WCBK21IMR
C112PA1120WCBK21IMR
C112PA1140WCBK21IMR
C112PA1160WCBK21IMR
C112PA1190WCBK21IMR
C112PA1240WCBK21IMF
C112PA1300WCBK21IMF
C112PA1370WCBK21IMF
CONSTRUCTION
Conductor
Insulation
Bedding
Armouring
Outer sheath :
APPLICATION
For outdoor installations, for connecting signaling and control units in industries, railways,
trafc signals, power stations, industrial plants and switchgears if mechanical protection is
required, or in applications where mechanical damages are expected to occur.
TECHNICAL DATA
- Nominal voltage Uo/U = 0.6/1 kV
- Power frequency test voltage 3.5 kV for 5 minutes
- Max. admissible temperature of conductor at normal operation 70 C
- Max. admissible temperature of conductor at short circuit 160 C for 5 seconds
51
DIMENSIONS
AND WEIGHTS
ELECTRICAL DATA
Number &
Nominal
cross
sectional
area
DC at 20 C
AC at 70 C
No. X mm2
/ km
/ km
5 X 1.5
7 X 1.5
10 X 1.5
12 X 1.5
14 X 1.5
16 X 1.5
19 X 1.5
24 X 1.5
30 X 1.5
37 X 1.5
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
12.1000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
14.6000
Current Rating
Laid in
ground
A
18.0
16.0
14.0
13.0
12.0
11.0
10.0
9.0
8.0
7.5
Laid in
ducts
A
1.5 mm2
15.5
14.0
12.5
11.5
10.5
10.0
9.0
8.0
7.5
6.5
Approx.
overall
diameter
Approx.
overall
weight
mm
Kg / km
13.5
12.5
11.5
10.5
9.5
9.0
8.0
7.5
6.5
6.0
16.6
18.0
21.0
23.3
24.2
25.0
26.0
28.9
31.0
34.0
500
550
770
1080
1140
1260
1370
1620
1850
2250
Laid in
free air
AES Code
C208PA1050WCBK12IMR
C208PA1070WCBK21IMR
C208PA1100WCBK21IMR
C208PA1120WCBK21IMR
C208PA1140WCBK21IMR
C208PA1160WCBK21IMR
C208PA1190WCBK21IMR
C208PA1240WCBK21IMF
C208PA1300WCBK21IMF
C208PA1370WCBK21IMF
DC at 20 C
AC at 70 C
No. X mm
/ km
/ km
5 X 2.5
7 X 2.5
10 X 2.5
12 X 2.5
14 X 2.5
16 X 2.5
19 X 2.5
24 X 2.5
30 X 2.5
37 X 2.5
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
7.4100
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
8.8700
5 X 4.0
7 X 4.0
10 X 4.0
12 X 4.0
14 X 4.0
16 X 4.0
19 X 4.0
24 X 4.0
30 X 4.0
37 X 4.0
DIMENSIONS
AND WEIGHTS
ELECTRICAL DATA
Number &
Nominal
cross
sectional
area
2
0.6 / 1 kV
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
4.6100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
5.5100
Current Rating
Laid in
ground
A
24.0
22.0
20.0
18.0
16.0
15.0
14.0
13.0
11.5
10.0
31.0
28.0
25.0
23.0
20.5
19.5
18.0
16.0
14.5
13.0
Laid in
ducts
A
2.5 mm
20.5
18.5
16.5
15.5
14.0
13.0
12.0
11.0
10.0
9.0
4.0 mm2
25.5
23.0
21.0
19.5
17.0
16.0
15.0
13.5
12.0
11.0
Approx.
overall
diameter
Approx.
overall
weight
mm
Kg / km
18.0
16.0
14.5
13.5
12.0
11.0
10.5
9.5
8.5
7.5
17.8
19.2
23.8
25.0
26.0
27.0
28.3
31.4
34.5
37.4
600
660
960
1280
1390
1510
1670
2030
2450
2870
C210PA1050WCBK12IMR
24.0
21.5
19.5
18.0
16.0
15.0
14.0
12.5
11.0
10.0
20.8
23.5
27.2
29.0
30.0
31.6
33.0
38.4
41.3
44.5
780
1190
1510
1700
1850
2040
2260
3070
3560
4120
C212PA1050WCBK12IMR
Laid in
free air
AES Code
C210PA1070WCBK21IMR
C210PA1100WCBK21IMR
C210PA1120WCBK21IMR
C210PA1140WCBK21IMR
C210PA1160WCBK21IMR
C210PA1190WCBK21IMR
C210PA1240WCBK21IMF
C210PA1300WCBK21IMF
C210PA1370WCBK21IMF
C212PA1070WCBK21IMR
C212PA1100WCBK21IMR
C212PA1120WCBK21IMR
C212PA1140WCBK21IMR
C212PA1160WCBK21IMR
C212PA1190WCBK21IMR
C212PA1240WCBK21IMF
C212PA1300WCBK21IMF
C212PA1370WCBK21IMF
Control Cables
To BS Standard
CONSTRUCTION
Conductor
Insulation
Bedding
Armouring
Outer sheath :
APPLICATION
For outdoor installations, for connecting signaling and control units in industries, railways,
trafc signals, power stations, industrial plants and switchgears if mechanical protection is
required, or in applications where mechanical damages are expected to occur.
TECHNICAL DATA
- Nominal voltage Uo/U = 600 / 1000 V
- Power frequency test voltage 3.5 kV for 5 minutes
- Max. admissible temperature of conductor at normal operation 70 C
- Max. admissible temperature of conductor at short circuit 160 C for 5 seconds
65
DIMENSIONS
AND WEIGHTS
ELECTRICAL DATA
Number &
Nominal
cross
sectional
area
DC at 20 C
AC at 70 C
No. X mm2
/ km
/ km
7 X 1.5
12 X 1.5
19 X 1.5
27 X 1.5
37 X 1.5
12.1000
12.1000
12.1000
12.1000
12.1000
14.6000
14.6000
14.6000
14.6000
14.6000
Current Rating
Laid in
ground
A
16.0
13.0
10.0
8.0
7.5
Laid in
ducts
A
1.5 mm2
14.0
11.5
9.0
7.5
6.5
Approx.
overall
diameter
Approx.
overall
weight
mm
Kg / km
12.5
10.5
8.0
6.5
6.0
15.6
19.7
22.6
27.1
30.0
490
790
1040
1515
1860
Laid in
free air
AES Code
C208PA1070WCBK21BMR
C208PA1120WCBK21BMR
C208PA1190WCBK21BMR
C208PA1270WCBK21BMF
C208PA1370WCBK21BMF
DC at 20 C
AC at 70 C
No. X mm
/ km
/ km
7 X 2.5
12 X 2.5
7.4100
7.4100
8.8700
8.8700
19 X 2.5
27 X 2.5
37 X 2.5
DIMENSIONS
AND WEIGHTS
ELECTRICAL DATA
Number &
Nominal
cross
sectional
area
2
600 / 1000 V
7.4100
7.4100
7.4100
8.8700
8.8700
8.8700
Current Rating
Laid in
ground
A
22.0
18.0
14.0
11.5
10.0
Laid in
ducts
A
2.5 mm
18.5
15.5
12.0
10.0
9.0
Approx.
overall
diameter
Approx.
overall
weight
mm
Kg / km
16.0
13.5
18.3
22.4
725
1025
Laid in
free air
10.5
8.5
7.5
26.9
31.0
34.4
1575
2020
2495
AES Code
C210PA1070WCBK21BMR
C210PA1120WCBK21BMR
C210PA1190WCBK21BMR
C210PA1270WCBK21BMF
C210PA1370WCBK21BMF
4.0 mm
7 X 4.0
12 X 4.0
19 X 4.0
27 X 4.0
37 X 4.0
4.6100
4.6100
4.6100
4.6100
4.6100
5.5100
5.5100
5.5100
5.5100
5.5100
28.0
23.0
18.0
14.5
13.0
23.0
19.5
15.0
12.0
11.0
21.5
18.0
14.0
11.0
10.0
20.9
27.1
31.1
37.1
41.1
940
1570
2115
3110
3840
C212PA1070WCBK21BMR
C212PA1120WCBK21BMR
C212PA1190WCBK21BMR
C212PA1270WCBK21BMF
C212PA1370WCBK21BMF
Cables For
Special Applications
Application
For outdoor installations in damp and wet locations in chemical
and petrol plants in which mechanical protection is required or in
applications where mechanical damages are expected to occur.
Main properties
Radially watertight
Corrosion resistant
Where necessary, it is available with the longitudinal
watertight protection
Suitable for use in hostile environment or underground
Especially suitable for submarine installation
Resistant to aggressive chemical substances
Offer good protection against rodents
Application
Low smoke halogen free power cables with enhanced characteristics
in case of re are used for applications where harm to human life
and damage to property must be prevented in the event of re,
e.g. in industrial installations, commercial establishments,
hotels, airports, underground stations, railway stations, hospitals,
banks, schools, etc.
Main properties
Reduced smoke and toxic gases emission in the event of re
Reduced acid gases emission in the event of re
Excellent ame retardant properties
67
Other possibilities:
Delivery lengths other than standard lengths
Products as per other national and international norms/standards
Technical Data
Recommendations
Installation of Cables
A. Minimum installation radius
None of the low voltage power or control cables should be bent
during installation to a radius smaller than the following:
Tm = 0.036
Tm = 0.027
69
X
X
n
n
X
X
Cm (Copper)
Cm (Aluminum)
Where
Tm : Maximum pulling tension in N
n : The number of conductors
Cm : Circular mil area of each conductor
The maximum limitation for this calculation is 22240 N for single conductor (1/C) cables, and 44480 N for multi-core
cables. This limitation is due to unequal distribution of tension forces when pulling multiple conductors.
When the calculated pulling tension is close to (or within 10% of) the maximum pulling tension, the use of a tension
gauge during the pulling is recommended.
D.2 Cable grip over lead sheath
With cable grip over lead sheath, with commercial lead, the maximum pulling tension on the lead sheath should not
exceed 10.33 N/mm2.
D.3 Cable grip over non-leaded cable
With cable grip over non-leaded cable, the maximum pulling tension should not exceed 4400 N.
E. Sidewall pressure
One of the limitations to be considered for the installation of electrical cables is sidewall pressure. The sidewall
pressure is the force exerted on the insulation and sheath of the cable at a bend point when the cable is under
tension, and is normally the limiting factor in an installation where cable bends are involved. The sidewall
pressure in general is expressed as the tension out of a bend expressed in newtons divided by the inside radius of the
bend expressed in meters.
P=
To
r
Where
P : Sidewall pressure in N/m
To : Tension leaving the bend in N
r : Inside radius of conduit in m
The normal maximum sidewall pressure per meter of radius is as given below. However, in order to minimize cable
damage due to excessive sidewall pressure, the installer should check the proper recommendations for each
type of cables to be installed.
Cable type
7300
Armoured cables
4400
7300
Formulas
71
Material Properties
Metals Used For Cables
Table 1
ELECTRICAL PROPERTIES
Metal
Relative Conductivity
Copper 100
Electrical Resistivity at
20 C .m ( 10-8 )
Temperature Coefcient
of Resistance per C
100
97
95 97
61
8
1.7241
1.7770
1.741 1.814
2.8264
21.40
0.00393
0.00393
0.00393
0.00403
0.00400
Copper (Annealed)
Copper (Hard drawn)
Tinned Copper
Aluminum
Lead
PHYSICAL PROPERTIES
Property
Unit
Copper
Kg/m3
C x 10-6
C
W/Cm.C
Density at 20 C
Coeff. of thermal expansion
Melting point
Thermal conductivity
Aluminum
8890.0
17.0
1083.0
3.8
2703.0
23.0
659.0
2.4
Lead
11340.0
29.0
327.0
0.34
PVC
Nominal
Emergency
Short Circuit
90
130
250
Mechanical
Strength
12.5
200
12.5
150
4.2
200
Good
2.5
0.93
Good
Poor
8.0
1.5
Poor
10
10
10
Excellent
3.0
1.4
Poor
Easy
Good
Easy
Good
Easy
Poor
.cm
12
70
95
140 * or 160 **
EPR
Rated Temp.
73
XLPE
90
130
250
12
10
Derating Factors
Table 3
temperature
C
25
30
35
40
45
50
55
70 C
1.13
1.07
1.00
0.93
0.85
0.76
0.65
90 C
1.09
1.04
1.00
0.95
0.90
0.85
0.80
Table 4
temperature
C
25
30
35
40
45
50
55
70 C
1.22
1.15
1.08
1.00
0.95
0.82
0.71
1.14
1.10
1.05
1.00
0.95
0.89
0.84
90 C
Table 5
95 up to 240 mm2
1.00
0.60
0.99
0.98
0.97
0.80
0.97
0.96
0.94
1.00
0.95
0.93
0.92
1.25
0.94
0.92
0.89
1.50
0.93
0.90
0.87
1.75
0.92
0.89
0.86
2.00
0.91
0.88
0.85
Derating Factors
Table 6
0.8
0.9
1.0
1.2
1.5
2.0
2.5
1.17
1.12
1.07
1.00
0.91
0.80
0.73
Table 7
70
85
95
105
1.000
1.195
1.309
1.414
Table 8
Number
Spacing
Spacing
Spacing
of
Trefoil formation
circuits
75
Touching
Flat formation
Spacing = 0.15 Mt.
Trefoil
Flat
Trefoil
Flat
Trefoil
Flat
0.77
0.80
0.82
0.85
0.88
0.91
0.66
0.69
0.73
0.76
0.80
0.83
0.60
0.63
0.68
0.71
0.74
0.77
0.56
0.59
0.64
0.67
0.72
0.75
0.53
0.57
0.61
0.64
0.70
0.73
Table 9
Number of circuits
1
0.92
0.89
0.88
0.92
0.89
0.88
0.87
0.84
0.83
Number of troughs
0.84
0.82
0.81
0.82
0.80
0.79
Number of circuits
1
1.00
0.97
0.96
0.97
0.94
0.93
0.96
0.93
0.92
0.94
0.91
0.90
Rating factor
0.94
0.91
0.89
Number of circuits
1
0.89
0.86
0.84
Derating Factors
Table 10
Number of circuits
1
0.95
0.90
0.88
Number of troughs
0.95
0.90
0.88
0.90
0.85
0.83
0.88
0.83
0.81
0.86
0.81
0.79
Number of circuits
1
1.00
0.98
0.96
1.00
0.95
0.93
1.00
0.94
0.92
1.00
0.93
0.90
77
Number of circuits
1
1.00
1.00
1.00
Table 11
Number of circuits
1
0.95
0.90
0.88
0.85
0.84
Number of circuits
1
0.95
0.90
0.88
0.85
0.84
Number of troughs
2
0.90
0.85
0.83
0.81
0.80
0.88
0.83
0.81
0.79
0.78
0.86
0.81
0.79
0.77
0.76
Number of circuits
1
Number of racks
1.00
0.98
0.96
0.93
0.92
1.00
0.95
0.93
0.90
0.89
1.00
0.94
0.92
0.89
0.88
1.00
0.93
0.90
0.87
0.86
Rating factor
1.00
0.93
0.90
0.87
0.86
Rating factor
1.00
1.00
1.00
1.00
1.00
Derating Factors
Table 12
Rating factor
0.90
0.84
0.80
0.75
0.73
Number of circuits
1
0.95
0.84
0.80
0.75
0.73
0.95
0.80
0.76
0.71
0.69
0.95
0.78
0.74
0.70
0.68
0.95
0.76
0.72
0.68
0.66
Number of troughs
Number of circuits
1
0.95
0.84
0.80
0.75
0.73
0.95
0.80
0.76
0.71
0.69
0.95
0.78
0.74
0.70
0.68
0.95
0.76
0.72
0.68
0.66
Number of racks
79
Number of circuits
Rating factor
0.95
0.78
0.73
0.68
0.66
Cable component
Insulation
PVC Insulation
Sheathing
2
2
XLPE Insulation
250
PVC Sheath
200
LDPE Sheath
150
HDPE Sheath
180
Lead Sheath
170
200
Table 14
mm
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
0.55
0.91
1.45
2.18
3.6
5.8
9.1
12.7
18.2
25.5
34.5
43.6
54.5
67.3
87.3
109.1
130.0
162.5
204.8
260.1
325.1
0.2
0.39
0.64
1.03
1.54
2.6
4.1
6.4
9.0
12.9
18.0
24.4
30.9
38.6
47.6
61.7
77.1
91.9
114.9
144.8
183.9
229.9
0.3
0.31
0.52
0.84
1.26
2.1
3.4
5.2
7.3
10.5
14.7
19.9
25.2
31.5
38.8
50.4
63.0
75.1
93.8
118.2
150.1
187.7
0.4
0.27
0.45
0.73
1.09
1.8
2.9
4.5
6.4
9.1
12.7
17.3
21.8
27.3
33.6
43.6
54.5
65.0
81.3
102.4
130.0
162.5
0.5
0.24
0.41
0.65
0.98
1.6
2.6
4.1
5.7
8.1
11.4
15.5
19.5
24.4
30.1
39.0
48.8
58.2
72.7
91.6
116.3
145.4
1.0
0.17
0.29
0.46
0.69
1.2
1.8
2.9
4.0
5.8
8.1
10.9
13.8
17.3
21.3
27.6
34.5
41.1
51.4
64.8
82.2
102.8
2.0
0.12
0.20
0.33
0.49
0.8
1.3
2.0
2.8
4.1
5.7
7.7
9.8
12.2
15.0
19.5
24.4
29.1
36.3
45.8
58.2
72.7
3.0
0.10
0.17
0.27
0.40
0.7
1.1
1.7
2.3
3.3
4.6
6.3
8.0
10.0
12.3
15.9
19.9
23.7
29.7
37.4
47.5
59.4
4.0
0.09
0.14
0.23
0.35
0.6
0.9
1.4
2.0
2.9
4.0
5.5
6.9
8.6
10.6
13.8
17.3
20.6
25.7
32.4
41.1
51.4
5.0
0.08
0.13
0.21
0.31
0.5
0.8
1.3
1.8
2.6
3.6
4.9
6.2
7.7
9.5
12.3
15.4
18.4
23.0
29.0
36.8
46.0
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
3.8
6.0
8.4
12.0
16.8
22.8
28.8
36.0
44.5
57.7
72.1
86.0
107.5
135.5
172.0
215.0
0.2
2.7
4.2
5.9
8.5
11.9
16.1
20.4
25.5
31.4
40.8
51.0
60.8
76.0
95.8
121.6
152.1
0.3
2.2
3.5
4.9
6.9
9.7
13.2
16.7
20.8
25.7
33.3
41.6
49.7
62.1
78.2
99.3
124.2
0.4
1.9
3.0
4.2
6.0
8.4
11.4
14.4
18.0
22.2
28.8
36.0
43.0
53.8
67.7
86.0
107.5
0.5
1.7
2.7
3.8
5.4
7.5
10.2
12.9
16.1
19.9
25.8
32.2
38.5
48.1
60.6
76.9
96.2
1.0
1.2
1.9
2.7
3.8
5.3
7.2
9.1
11.4
14.1
18.2
22.8
27.2
34.0
42.8
54.4
68.0
2.0
0.9
1.3
1.9
2.7
3.8
5.1
6.4
8.1
9.9
12.9
16.1
19.2
24.0
30.3
38.5
48.1
3.0
0.7
1.1
1.5
2.2
3.1
4.2
5.3
6.6
8.1
10.5
13.2
15.7
19.6
24.7
31.4
39.3
4.0
0.6
1.0
1.3
1.9
2.7
3.6
4.6
5.7
7.0
9.1
11.4
13.6
17.0
21.4
27.2
34.0
5.0
0.5
0.8
1.2
1.7
2.4
3.2
4.1
5.1
6.3
8.2
10.2
12.2
15.2
19.2
24.3
30.4
Table 16
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
81
4.7
7.4
10.4
14.8
20.7
28.1
35.6
44.4
54.8
71.1
88.9
118.5
148.2
186.7
237.0
296.3
0.2
3.4
5.2
7.3
10.5
14.7
19.9
25.1
31.4
38.8
50.3
62.9
83.8
104.8
132.0
167.6
209.5
0.3
2.7
4.3
6.0
8.6
12.0
16.3
20.5
25.7
31.6
41.1
51.3
68.4
85.5
107.8
136.9
171.1
0.4
2.4
3.7
5.2
7.4
10.4
14.1
17.8
22.2
27.4
35.6
44.4
59.3
74.1
93.3
118.5
148.2
0.5
2.1
3.3
4.6
6.6
9.3
12.6
15.9
19.9
24.5
31.8
39.8
53.0
66.3
83.5
106.0
132.5
1.0
1.5
2.3
3.3
4.7
6.6
8.9
11.2
14.1
17.3
22.5
28.1
37.5
46.9
59.0
75.0
93.7
2.0
1.1
1.7
2.3
3.3
4.6
6.3
8.0
9.9
12.3
15.9
19.9
26.5
33.1
41.7
53.0
66.3
3.0
0.9
1.4
1.9
2.7
3.8
5.1
6.5
8.1
10.0
13.0
16.2
21.6
27.0
34.1
43.3
54.1
4.0
0.75
1.2
1.6
2.3
3.3
4.5
5.6
7.0
8.7
11.2
14.1
18.7
23.4
29.5
37.5
46.9
5.0
0.67
1.0
1.5
2.1
2.9
4.0
5.0
6.3
7.8
10.1
12.6
16.8
21.0
26.4
33.5
41.9
Table 17
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
0.7
1.1
1.8
2.7
4.5
7.2
11.3
15.8
22.6
31.7
43.0
54.3
67.8
83.7
108.5
135.7
180.9
226.1
284.9
361.8
452.2
0.2
0.5
0.8
1.3
1.9
3.2
5.1
8.0
11.2
16.0
22.4
30.4
38.4
48.0
59.2
76.7
95.9
127.9
159.9
201.4
255.8
319.8
0.3
0.4
0.7
1.0
1.6
2.6
4.2
6.5
9.1
13.1
18.3
24.8
31.3
39.2
48.3
62.7
78.3
104.4
130.5
164.5
208.9
261.1
0.4
0.3
0.6
0.9
1.4
2.3
3.6
5.7
7.9
11.3
15.8
21.5
27.1
33.9
41.8
54.3
67.8
90.4
113.1
142.4
180.9
226.1
0.5
0.3
0.5
0.8
1.2
2.0
3.2
5.1
7.1
10.1
14.2
19.2
24.3
30.3
37.4
48.5
60.7
80.9
101.1
127.4
161.8
202.2
1.0
0.21
0.36
0.57
0.86
1.4
2.3
3.6
5.0
7.2
10.0
13.6
17.2
21.5
26.5
34.3
42.9
57.2
71.5
90.1
114.4
143.0
2.0
0.15
0.25
0.40
0.61
1.0
1.6
2.5
3.5
5.1
7.1
9.6
12.1
15.2
18.7
24.3
30.3
40.4
50.6
63.7
80.9
101.1
3.0
0.12
0.21
0.33
0.50
0.8
1.3
2.1
2.9
4.1
5.8
7.8
9.9
12.4
15.3
19.8
24.8
33.0
41.3
52.0
66.0
82.6
4.0
0.11
0.18
0.29
0.43
0.7
1.1
1.8
2.5
3.6
5.0
6.8
8.6
10.7
13.2
17.2
21.5
28.6
35.8
45.0
57.2
71.5
5.0
0.10
0.16
0.26
0.38
0.6
1.0
1.6
2.2
3.2
4.5
6.1
7.7
9.6
11.8
15.3
19.2
25.6
32.0
40.3
51.2
64.0
Voltage Drop
Table 18
C.S.A
mm 2
16
25
35
50
70
95
120
150
185
240
300
400
500
630
Copper Conductors
Voltage drop ( mV / Amp / Meter )
XLPE Insulated & PVC Sheathed
Trefoil
22.8
14.1
8.8
5.9
3.6
2.3
1.5
1.1
0.83
0.60
0.46
0.38
0.33
0.28
0.24
0.21
0.18
0.16
0.15
Aluminum Conductors
Voltage drop ( mV / Amp / Meter )
83
Flat
22.9
14.1
8.8
5.9
3.6
2.3
1.5
1.1
0.84
0.61
0.47
0.39
0.34
0.29
0.25
0.22
0.19
0.17
0.16
Trefoil
3.7
2.4
1.7
1.3
0.93
0.70
0.57
0.48
0.40
0.33
0.28
0.24
0.21
0.18
Table 19
C.S.A
2
mm
16
25
35
50
70
95
120
150
185
240
300
400
500
Copper Conductors
Voltage drop ( mV / Amp / Meter )
XLPE Insulated & PVC Sheathed
22.8
14.0
8.7
5.9
3.5
2.2
1.5
1.1
0.81
0.58
0.44
0.37
0.31
0.27
0.23
0.2
0.18
0.15
Aluminum Conductors
Voltage drop ( mV / Amp / Meter )
XLPE Insulated & PVC Sheathed
3.7
2.4
1.7
1.3
0.92
0.68
0.56
0.47
0.39
0.32
0.27
0.23
0.20
Coding Key
1
Copper
A:
Aluminum
2. Type of conductor
1:
2:
3:
4:
5:
6:
Solid
Stranded - Circular round
Stranded - Circular compacted
Stranded - Sector shaped
Flexible
Extra-flexible
85
1.5 mm2
2.5 mm2
4 mm2
6 mm2
10 mm2
16 mm2
25 mm2
35 mm2
50 mm2
70 mm2
3 x 10 + 6 mm2
3 x 16 + 10 mm2
3 x 25 + 16 mm2
3 x 35 + 16 mm2
3 x 50 + 25 mm2
3 x 70 + 35 mm2
3 x 95 + 50 mm2
3 x 120 + 70 mm2
3 x 150 + 70 mm2
3 x 185 + 95 mm2
3 x 240 + 120 mm2
3 x 300 + 150 mm2
3 x 400 + 185 mm2
95 mm2
10
11
12
13
14
15
16
17
18
19
46 :
120 mm2
X:
47 :
48 :
49 :
50 :
51 :
52 :
53 :
54 :
55 :
150 mm2
185 mm2
240 mm2
300 mm2
400 mm2
500 mm2
630 mm2
800 mm2
1000 mm2
R:
XLPE Insulation
PVC Insulation rated 70 C
PVC Insulation rated 85 C
6. Rated voltage
A:
0.6 / 1 kV
7. Cable construction
1:
2:
Cores
Pairs
1 Core
02 :
03 :
04 :
05 :
2 Cores
3 Cores
4 Cores
5 Cores
37 :
37 Cores
10. Shielding
N:
C:
Copper tape
Copper wires
0:
Without shielding
11. Armouring
0:
L:
N:
A:
B:
G:
W:
Without armouring
Pure lead sheathed
Lead alloy sheathed
Aluminum wire armoured
Aluminum tape armoured
Galvanized steel tape armoured
Galvanized steel wire armoured
T:
S:
D:
Black
RD :
GY :
GR :
YG :
GL :
Red
Grey
Green
Yellow / Green
Green / Yellow
1C - Red
01 :
04 :
08 :
12 :
21 :
2C - Red, Black
3C - Red, Yellow, Blue
4C - Red, Yellow, Blue, Black
5C - Red, Yellow, Blue, Black, G/Y
6C & Above - Black + No.
IEC Standard
BS Standard
Customer request
Wooden drum
Steel drum
250 Meter
500 Meter
1000 Meter
0.05 MVA at an operating voltage of 380V have to be transmitted by 4 cores cable with copper conductor, XLPE
insulated and PVC sheathed direct buried in the ground under the following laying conditions :
Burial depth
Soil thermal resistivity
Ambient ground temp.
Cable route length
:
:
:
:
0.5
1.2
35
50
m
K.m/W
C
m
Sx10 6
3 xU
0.05 x10 6
3 x380
= 76 A
Where
I : Load current in A
S : KVA rating
U : Line voltage in volts
According to the relevant current carrying capacity values for the used cable type, it has been found that the current
carrying capacity value for 4 X 16 mm2 cable under the required installation conditions is 97A, which is greater than the
required load current (76A). So, cable 4 X 16 mm2 can be used to carry the required load current.
Calculating cross-section according to voltage drop
The tabulated voltage drop values in this catalogue are based on a load power factor of 85% lagging and given for
a current one ampere for a one meter run. For any cable length, the values should be multiplied by the cable route length
in meters and by the load current in amperes.
The applicable formula to calculate the approximate voltage drop/ampere/meter is the following :
V ap =
V p x1000
IxL
mV/Amp/Meter
Where
Vap
I
L
Vp
:
:
:
:
By substituting current, cable route length, and maximum permissible voltage drop.
Vap =
9.5 x1000
= 2.5 mV/Amp/Meter
76 x50
To determine a suitable size of conductor, select a cable from the voltage drop tables, such that the selected voltage drop
value from the tables is less than the calculated value of 2.5 mv/amp/m. Also ensure that it will carry the desired
current. In this example, the nearest voltage drop value is 2.2 mv/amp/m, which is corresponding to size 16 mm2.
In situations where the load power factor is other than 85% lagging, the voltage drop equations shown in the
formula section should be used to calculate the voltage drop.
Weight-Imperial
v
v
Weight-Metric
Length-Metric
Miscellaneous-Imperial
Area-Imperial
Miscellaneous-Metric
Area-Metric
centimeters
Volume-Imperial
4.54609
Temperature
Lenght-Imperial
87
Volume-U.S.
Volume-Metric
Certicates
Product Range
manufactures a wide range of low, medium and high voltage electrical products under 50 categories.
Listed below is
s comprehensive product classication:
Load Center
METAL ENCLOSURES
Service Box Enclosures
Modular Enclosures
Extendable Cubicles
Telephone Box
Busbar Chamber w/o Main
METAL ACCESSORIES
Switch Boxes
Junction Boxes
89
Overhead conductors
Power Cables
Telephone Cables
LIGHTING
Halogen
Florescent
Energy Saving
COMMUNICATION SYSTEMS
Audio Intercom
Contact us
markets and sells over 800 electrical construction products in the Saudi Arabian markets and exports them to
several countries in the Middle East, Europe, Asia and Africa.
Through our several operational domains and a widespread network of distributors, we ensure uninterrupted supply of
products. We also provide solutions to our clients including end-users, project owners, engineering contractors
and consultants.
s highly-qualied engineers, sales & marketing teams not only cater to its customers requirements efciently,
they also manage prompt after-sales services and extend full technical support and consultancy services to them.