Our Ref: Dated HiYole yramid Control Systems (P) Ltd. 14/6, Mathura Road, Faridabad-121 003, India Depa: JCONTACT Honeywell Phones : (0129) 2275307, 2278607, 2275044 Fax: (0129) 2276448 E-mail : pyramidcontrolsystem@yahoo.com, js_dua@yahoo.com, gurnitsdua@yahoo.com website : www.pyramidcontrolsystems.com esa (ouea in ELECTRIFICATION® INSTRUMENTATION® AUTOMATION® SAFETY & SECURITY ——PCPL/HEA3-2627-C/R03/2014 (29.01.14 WITNESS INSPECTION TEST CERTIFICATE 7__[Customer IMIS Escorts Limited 2 _ [Project 22 KW Heater Control Panel. 3__|ltem Details 22 KW Heater Control Panel. 4 [Drawing No. HEA3-2627-C/RO3 a [Description [As above [Quantity 3 No. : [0.K. as per approved drawing No HEAS- 8. [Physical checks eee een a [Component mounting & fiting [Satisfactory b_ [Painting finish (O.K. ¢_ [Paint scratch test caried out __|Found OK. 6 _ [Electrical test: a__|Insulation test Passed HV test on 1.5 KV for 1 minute. [Above 50 mega ohms @ 1000 VDC and b Meagar test lround satisfactory. [Continuity test OK. - Following test Carried out and found [Functional test rotctenene fa. Operation of main Incomer FSU,Contactors, control fuses,auxilary lcontrot relays, TIC by simulation method lb Operation of indication lamps and Measuring Instruments. 7__ [Enclosure Size at Electrical Engineer (PYRAMID CONTROL SYSTEMS (P) LTD.) ep 600 (W) X 300(D) Electrical Engineer ( M/S Escorts Limited) Regd. Office : 1710, B-1, Vasant Kunj, New Delhi-110 070 [wixal]