WITNESS INSPECTION TEST CERTIFICATE
7__[Customer IMIS Escorts Limited
2 _ [Project 22 KW Heater Control Panel.
3__|ltem Details 22 KW Heater Control Panel.
4 [Drawing No. HEA3-2627-C/RO3
a [Description [As above
[Quantity 3 No.
: [0.K. as per approved drawing No HEAS-
8. [Physical checks eee een
a [Component mounting & fiting [Satisfactory
b_ [Painting finish (O.K.
¢_ [Paint scratch test caried out __|Found OK.
6 _ [Electrical test:
a__|Insulation test Passed HV test on 1.5 KV for 1 minute.
[Above 50 mega ohms @ 1000 VDC and
b Meagar test lround satisfactory.
[Continuity test OK.
- Following test Carried out and found
[Functional test rotctenene
fa. Operation of main Incomer
FSU,Contactors, control fuses,auxilary
lcontrot relays, TIC by simulation method
lb Operation of indication lamps and
Measuring Instruments.
7__ [Enclosure Size
at
Electrical Engineer
(PYRAMID CONTROL SYSTEMS (P) LTD.)
ep 600 (W) X 300(D)
Electrical Engineer
( M/S Escorts Limited)