SIEMENS

MLFB code :
serial no.:
software :
order no. :

7VE6110-5EB02-0AA0/BB
BF0404074137
V04.00.08
802473/83

date of test:
test equip. :
tested by
:
page no.
:

03.05.2004 08:45:09
OMICRON UPS-12 / V04.01
757
1 / 3

Auxiliary voltage / Hilfsspannung


| setpoint
|
|
|

|meas. value| unit | deviation| phase | remarks / communication

220.000 |
31.000 |
7.000 |

219.940 | V
27.294 | mA
5.972 | W

| -0.03 % |
| -3.71 mA |
| -1.03 W |

| aux. voltage
| dc current
| power consumption

| stat.|
| PASS |
| PASS |
| PASS |

Test result: PASS

MLFB-Compare / MLFB-Vergleich
DEV-MLFBNr=7VE61105EB020AA0---------------Bootsystem=01.04.01
Test result: PASS

DEV-BFNr=BF0404074137

DEV-Soft=04.00.08

Hardware test
Max. Relay count= 11
LED test: OK
Display test: OK
Battery test: OK
Device clock: Date=3.5.2004
Test result: PASS

Time=8:47:33

HWT keyboard test / Folien-Tastatur


Test result: PASS

HWT binary inputs / Binr-Eingnge


Max. Bin-Input count= 6
Test result: PASS

HWT relay outputs / Relais-Ausgnge


Test result: PASS

HWT communication ports / Schnittstellen


Location A: DCF77-Interface : OK
Location C: Modem-Interface = RS485 : OK
Test result: PASS

Channel phase angle / Phasenwinkel


| setpoint

|meas. value| unit | deviation| phase | remarks / communication

| stat.|

|
|
|
|
|
|
|

|
|
|
|
|
|
|

|
|
|
|
|
|
|

0.000
0.000
240.000
240.000
240.000
0.000
240.000

-0.003
0.008
239.991
239.987
240.002
-0.001
239.971

Test result: PASS

|
|
|
|
|
|
|

|
|
|
|
|
|
|

-0.00
0.01
-0.01
-0.01
0.00
-0.00
-0.03

|
|
|
|
|
|
|

L123E
L123E
L123E
L123E
L123E
L123E
L123E

|
|
|
|
|
|
|

50Hz:
50Hz:
50Hz:
50Hz:
50Hz:
50Hz:
50Hz:

Ub-Ua
Uc-Ua
Ud-Ua
Ue-Ua
Uf-Ua
Ug-Ua
Uh-Ua

PASS
PASS
PASS
PASS
PASS
PASS
PASS

|
|
|
|
|
|
|

SIEMENS
MLFB code :
serial no.:
software :
order no. :

7VE6110-5EB02-0AA0/BB
BF0404074137
V04.00.08
802473/83

date of test:
test equip. :
tested by
:
page no.
:

03.05.2004 08:45:09
OMICRON UPS-12 / V04.01
757
2 / 3

Channel correction factor / Abgleichfaktor


| setpoint

|meas. value| unit | deviation| phase | remarks / communication

| stat.|

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|

1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000

1004.325
997.715
997.294
996.353
1001.479
996.698
1004.497
1001.038
1000.904
995.266
994.814
993.947
998.107
994.217
1001.098
997.695
999.970
996.658
995.778
994.662
996.145
995.322
1000.127
995.874

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|

0.43
-0.23
-0.27
-0.36
0.15
-0.33
0.45
0.10
0.09
-0.47
-0.52
-0.61
-0.19
-0.58
0.11
-0.23
-0.00
-0.33
-0.42
-0.53
-0.39
-0.47
0.01
-0.41

%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|

Ua
|
1.220|
1.190|
1.196|
-0.088|
1.158|
-0.001|
-0.088|
Ua
|
1.478|
1.443|
1.456|
-0.071|
1.407|
0.011|
-0.063|
Ua
|
0.452|
0.392|
0.381|
-0.126|
0.394|
0.002|
-0.128|

50Hz Kl. Q 1-Q 2


50Hz Kl. Q 3-Q 4
50Hz Kl. Q 5-Q 6
50Hz Kl. Q 7-Q 8
50Hz Kl. Q 9-Q10
50Hz Kl. Q11-Q12
50Hz Intern
50Hz Intern
60Hz Kl. Q 1-Q 2
60Hz Kl. Q 3-Q 4
60Hz Kl. Q 5-Q 6
60Hz Kl. Q 7-Q 8
60Hz Kl. Q 9-Q10
60Hz Kl. Q11-Q12
60Hz Intern
60Hz Intern
16.67Hz Kl. Q 1-Q 2
16.67Hz Kl. Q 3-Q 4
16.67Hz Kl. Q 5-Q 6
16.67Hz Kl. Q 7-Q 8
16.67Hz Kl. Q 9-Q10
16.67Hz Kl. Q11-Q12
16.67Hz Intern
16.67Hz Intern

PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|

Test result: PASS

Voltage analog inputs / Spannung analoge Eingnge


| setpoint

|meas. value| unit | deviation| phase | remarks / communication

| stat.|

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|

100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000

99.998
100.006
100.005
99.992
99.994
99.986
100.004
99.990
100.007
100.013
100.016
99.998
100.004
99.999
100.009
99.988
99.991
100.009
100.013
100.002
100.004
99.990
100.008
99.986

Test result: PASS

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|

V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|

-0.00
0.01
0.00
-0.01
-0.01
-0.01
0.00
-0.01
0.01
0.01
0.02
-0.00
0.00
-0.00
0.01
-0.01
-0.01
0.01
0.01
0.00
0.00
-0.01
0.01
-0.01

%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|

Ua
Ub
Uc
Ud
Ue
Uf
Ug
Uh
Ua
Ub
Uc
Ud
Ue
Uf
Ug
Uh
Ua
Ub
Uc
Ud
Ue
Uf
Ug
Uh

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|

16Hz:
16Hz:
16Hz:
16Hz:
16Hz:
16Hz:
16Hz:
16Hz:
50Hz:
50Hz:
50Hz:
50Hz:
50Hz:
50Hz:
50Hz:
50Hz:
60Hz:
60Hz:
60Hz:
60Hz:
60Hz:
60Hz:
60Hz:
60Hz:

Q 1-Q 2
Q 3-Q 4
Q 5-Q 6
Q 7-Q 8
Q 9-Q10
Q11-Q12
Intern
Intern
Q 1-Q 2
Q 3-Q 4
Q 5-Q 6
Q 7-Q 8
Q 9-Q10
Q11-Q12
Intern
Intern
Q 1-Q 2
Q 3-Q 4
Q 5-Q 6
Q 7-Q 8
Q 9-Q10
Q11-Q12
Intern
Intern

PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|

SIEMENS
MLFB code :
serial no.:
software :
order no. :

7VE6110-5EB02-0AA0/BB
BF0404074137
V04.00.08
802473/83

date of test:
test equip. :
tested by
:
page no.
:

03.05.2004 08:45:09
OMICRON UPS-12 / V04.01
757
3 / 3

Operating buffer / Betriebsmeldungen


Test result: PASS

Test parameter / Grund-Parameterierung


161: SYNC Function group 1= 1phase Synchro check
6101: Synchronizing Function= ON
Test result: PASS

Operational measuring values / Betriebsmewerte


3Ph-System: Fart=F-20

Ik=0.000A Uk=100.000V Pk=0.0

Freq=50.00Hz

| setpoint

|meas. value| unit | deviation| phase | remarks / communication

| stat.|

|
|
|
|
|
|
|
|
|
|
|
|

|
|
|
|
|
|
|
|
|
|
|
|

|
|
|
|
|
|
|
|
|
|
|
|

100.000
100.000
100.000
100.000
100.000
100.000
50.000
50.000
50.000
50.000
50.000
50.000

100.000
100.000
100.000
100.000
100.000
100.000
50.000
50.000
50.000
50.000
50.000
50.000

3Ph-System: Fart=F-20

|
|
|
|
|
|
|
|
|
|
|
|

V
V
V
V
V
V
Hz
Hz
Hz
Hz
Hz
Hz

|
|
|
|
|
|
|
|
|
|
|
|

0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00

%
%
%
%
%
%
%
%
%
%
%
%

|
|
|
|
|
|
|
|
|
|
|
|

|
|
|
|
|
|
|
|
|
|
|
|

Ik=0.000A Uk=100.000V Pk=0.0

Voltage Ua
Voltage Ub
Voltage Uc
Voltage Ud
Voltage Ue
Voltage Uf
Frequency fa
Frequency fb
Frequency fc
Frequency fd
Frequency fe
Frequency ff

PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS

|
|
|
|
|
|
|
|
|
|
|
|

Freq=50.00Hz

| setpoint

|meas. value| unit | deviation| phase | remarks / communication

| stat.|

|
|
|
|
|
|
|

|
|
|
|
|
|
|

|
|
|
|
|
|
|

100.000
50.000
100.000
50.000
0.000
0.000
0.000

99.900
50.000
99.900
50.000
0.000
0.000
0.000

|
|
|
|
|
|
|

V
Hz
V
Hz
V
Hz

| -0.10 %
| 0.00 %
| -0.10 %
| 0.00 %
| 0.00 V
| 0.00 Hz
| 0.00

|
|
|
|
|
|
|

|
|
|
|
|
|
|

U1
f1
U2
f2
dU
df
dalpha

PASS
PASS
PASS
PASS
PASS
PASS
PASS

|
|
|
|
|
|
|

Test result: PASS

Synchronization 98V and 102V


| setpoint

|meas. value| unit | deviation| phase | remarks / communication

|
|
|
|

|
|
|
|

1.000
98.000
1.000
102.000

1.000
97.907
1.000
101.975

|
|
|
|

dig
V
dig
V

| 0.00 %
| -0.09 %
| 0.00 %
| -0.02 %

|
|
|
|

OFF
-

|
|
|
|

| stat.|

Sync Start R3
|
Synchronization dU=-2V Stop-R1|
Sync Start R3
|
Synchronization dU=+2V Stop-R1|

Test result: PASS

Original start / Uranlauf


6101: Synchronizing Function= OFF
161: SYNC Function group 1= Disabled
Buffer Initial-Start: PASS
MLFB-Nr= 7VE61105EB020AA0----------------

Software= V04.00.08 : Test result: PASS

PASS
PASS