Input Data

No. of Pumps
Capacity of each
pump (m3/hr)
1

1
30

System

Volumetric flow

Initial Velocity
Internal diameter of pipe
calculated
Internal diameter of pipe
selected
Final Velocity

Service Water
SUCTIO
Units
N
m^3/hr
30

DISCHA
RGE
30

TO JNT TO JNT
14
10
10
20

m/sec.

1.2

2.4

2.4

2.4

0.09

0.07

0.04

0.05

0.1107

0.086

0.0464

0.0735

m/sec.

0.87

1.43

1.64

1.31

Thickness

mm

5.40

4.80

4.00

4.50

Outer Diameter

mm

114.10

88.80

48.40

76.00

Hazen - Williams coefficient

80

50

65

4
5

10

NB

Formula used
Hazen-Williams formula given below
F = 6.815 x (V/C)1.852 x
(1/d)1.167 x L
F = Total friction loss in pipe
Where
in MWC
V = Flow velocity in M/Sec.
d = Internal pipe diameter
in meters
C = Hazen- Williams
coefficient = 120

120
100

L = Length of the Pipe in


Meters