DHW Systems Water Heaters Catalog Nov14
DHW Systems Water Heaters Catalog Nov14
DHW Systems Water Heaters Catalog Nov14
60C
water temperature
ensures thermal
disinfection
during hot water
production
www.district-heating.danfoss.com
Index
3
Termix Novi
Akva Vita II
10
Akva Lux II GW
12
ThermoDual
14
16
ThermoDual
26
Akva Therm II LV
28
Termix One-B
30
32
34
ThermoClean
42
ThermoDual CM
46
ThermoDual FLS
50
ThermoClean
Construction
All pipes are made of stainless steel.
The connections are made by nuts and
gaskets. The Termix One Solar is delivered
with an attractive steel grey cover in mo
dern design, emphasising the high level
of quality and comfort which characterises
this product.
BT
supply
DHW
BT
return
DCW
BT
supply
DHW
Cirk.
BT
return
DCW
Technical parameters:
Nominal pressure:
DH supply temperature:
DCW static pressure:
Brazing material (HEX):
With circulation:
Without cover:
With cover:
20 kg
(incl. packing)
PN 16
Tmax = 120 C
pmin = 0,5 bar
Copper
24 Delivered
loose with unit
35 Ball valve
/ non-return valve
39 Connection closed
45 Flow switch
48 Air vent, manual
63 Sieve
Connections:
1 Domestic cold water (DCW)
2 Domestic hot water (DHW)
3 Buffer tank (BT) supply
4 Buffer tank (BT) return
5 Circulation
Connections sizes:
All connections:
Grey-lacquered
steel sheet
39 Connection closed
45 Flow switch
48 Air vent, manual
63 Sieve
G (int. thread)
Wall
Dimensions (mm):
Without cover:
H 760 B 312 T 155
With cover:
H 760 B 315 T 165
Without cover, with circulation:
H 935 B 410 T 150
DHW
Capacity
kW
29.3
38.2
37.8
52.3
60
66
80
90
Supply
flow
Primary
C
60
60
70
70
60
60
70
70
Return
flow
Primary
C
23.0
25.2
20.0
22.4
23.0
24.0
20.3
21.0
Pressure
loss
Primary
kPa
20
45
20
45
35
45
35
45
Flow
rate
Secondary
l/h
630
822
816
1128
1280
1426
1730
1940
Substation type
Type 2
w/AVTB 20
up to 4 households
-
Supply
DHW
flow
Capacity
Primary
kW
C
34.7
60
47.1
60
45.1
70
65.6
70
-
Return
flow
Primary
C
24.4
26.8
21.3
23.8
-
Pressure
loss
Primary
kPa
20
45
20
45
-
Flow
rate
Secondary
l/h
744
1014
972
1410
-
Gemina Termix A/S Member of the Danfoss Group Navervej 15-17 DK-7451 Sunds Denmark
Tel.: +45 9714 1444 Fax: +45 9714 1159 mail@termix.dk www.heating.danfoss.com
DEN-SMT/PL
Termix Novi
Instantaneous water heater for flats, single-family houses and small
apartment buildings with up to 4 flats.
Instantaneous water heater with heat exchanger and flow compensated temperature controller.
Designed for wall-mounting.
Application
The Termix Novi is an instantaneous water
heater featuring superb heat extraction
and high performance. The Termix Novi is
suitable for flats, single-family houses as
well as for small apartment buildings. The
water heater is available in two sizes, either
for 1 apartment, or up to 4 apartments. The
Termix Novi is applicable for decentralized
heating systems as well as for district heating networks with summer operation at low
temperatures or with changes in differential
pressure. The heat exchanger in Termix Novi
cools the district heating water very efficiently, thereby creating a very good operation economy.
Domestic hot water (DHW)
The domestic hot water is prepared in the
heat exchanger and the temperature is regulated by a flow-compensated temperature
controller with a integrated differential pressure controller. The Danfoss IHPT valve ensures a stable hot water temperature by
Construction
All pipes are made of stainless steel. The connections are made by nuts and gaskets. The
Termix Novi is delivered with an attractive
grey full insulation in modern design, emphasising the high level of quality and comfort which characterises this product.
Options
The water heater can be supplied with a built
in non-return valve and safety valve mounted in the cold water supply. The water heater
can also be supplied with a thermostatic circulation valve and a non-return and pressure
equalizer (GTU).
Capacity: up to 61 kW DHW
DHW in sufficient quantity
Operates independently of differential
pressure and flow temperature
Minimum space required for installation
Pipes and plate heat exchanger made of
stainless steel
Minimized risk of lime scale and bacteria
formation
Optimum temperature regulation up to
DH supply temperature 100 C
Termix Novi
Circuit diagram example
DH supply
DHW
B Water heater
9 Strainer
72 IHPT
72
9
CWM
DH return
Technical parameters:
Nominal pressure:
DH supply temperature:
DCW static pressure:
Brazing material (HEX):
Connections:
1 Domestic cold water (DCW)
2 Domestic hot water (DHW)
3 District heating flow (DH)
4 District heating return (DH)
PN 16
Tmax = 120 C
pmin = 1,0 bar
Copper
Wall
Connections sizes:
DH + DCW + DHW: G (ext. thread)
Options:
Booster pump (increases DH flow)
Grey-lacquered steel cover
Safety valve and non-return valve (10 bar)
Safety valve with thermostatic circulation set
Thermostatic circulation set
Non-return and pressure equalizer (GTU)
Dimensions (mm):
With insulation:
H 432 x W 300 x D 155
With cover:
H 442 x W 315 x D 165
DHW
Capacity
kW
Supply
flow
Primary
C
Return
flow
Primary
C
DHW
C
Pressure
loss
Primary
kPa
DHW
Tap load
l/min
32,3
41,5
43
53
30
35
41
50
60
60
70
70
60
60
70
70
19
21
17
18
23
24
19
21
10/45
10/45
10/45
10/45
10/50
10/50
10/50
10/50
19
29
19
29
19
29
19
29
13,3
16,6
17,7
21,8
10,5
12,6
14,8
18,0
Novi Type 1
Novi Type 2
32,3
38
39
48,7
50
57
36
43
48
58,5
55
55
60
60
70
70
60
60
70
70
Return
flow
Primary
C
DHW
C
19
20
17
19
16
16
21
22
17
19
10/45
10/45
10/45
10/45
10/45
10/45
10/50
10/50
10/50
10/50
Pressure
DHW
loss
Tap load
Pr i m a r y
l/min
kPa
18
26
19
28
19
24
19
28
19
28
13,3
15,7
15,7
20,1
20,6
23,3
12,3
15,9
17,3
21,2
Gemina Termix A/S Member of the Danfoss Group Navervej 15-17 DK-7451 Sunds Denmark
Tel.: +45 9714 1444 Fax: +45 9714 1159 mail@termix.dk www.heating.danfoss.com
DEN-SMT-PL
Akva Vita II
Instantaneous water heater for single-family houses and flats
Pressure controlled instantaneous water heater with heat exchanger. Unique DHW temperature
control with esaveTM function and cold heat exchanger during standby.
Application
The Akva Vita II is an instantaneous water
heater featuring high performance and
simple operation. It is especially suitable for
single-family houses and for systems with a
similar domestic hot water requirement.
The Akva Vita II can be used directly on district heating networks with a differential
pressure of max. 2.5 bar.
Construction
The Akva Vita II water heater is prefabricated
with a brazed, highly efficient Danfoss plate heat exchanger for domestic hot water production, a domestic hot water controller Danfoss PM2+P, as well as a Danfoss
FJVR thermostat for control of the bypass/
circulation temperature. All pipes are made
of stainless steel and the connections are
made by nuts and gaskets. As an option and
if approved by local regulations the water
heater can be supplied with a Danfoss AVE
expansion unit to avoid having to establish
a discharge pipe.
Design
The Akva Vita II is designed for wallmounting and the design emphasizes a
user-friendly placement of the controllers.
The Akva Vita II can be supplied with a brushed or white-lacquered stainless steel cover
in an elegant and modern design.
Bypass (thermostatic circulation)
The water heater is supplied with a thermostatically controlled bypass, which ensuVL.GP.J1.02 Danfoss 10/2012
res that hot water is produced immediately, when tapping starts. The bypass temperature is set with due consideration of the best
possible DHW comfort and economy.
Domestic hot water circulation
The water heater is prepared for domestic
hot water circulation. If the household piping includes hot water recirculation the
water heater must be connected to the hot
water recirculation system and a circulation pump and a non-return valve must be
mounted on the circulation pipe and a safety valve must be mounted in the DCW inlet. The pump must be installed so that it
pumps towards the water heater. Domestic
hot water circulation ensures that hot water is available at the tapping point without
waiting time and waste of water. The circulation temperature is set independently of
the set DHW temperature. This ensures the
best possible DHW comfort, very low standby losses and thus a very good district heating economy. Please note that Akva Vita II
with AVE expansion unit should not be used
on systems with domestic hot water recirculation.
Heat exchanger for DHW heating
The water heater is based on a brazed, highly
efficient plate heat exchanger type XB 06H-1
26, which is controlled by a pressure controlled DHW controller, Danfoss PM+P with integrated differential pressure controller and
esaveTM function, which ensures that the
heat exchanger is cold during standby. Af-
Akva Vita II
Circuit diagram Example
1.
6 5
3.
DHW circ.
6.
DHW
DH.
return
Connections:
1. Domesctic cold water (DCW)
2. Domestic hot water (DHW)
3. District heating (DH) supply
4. District heating (DH) return
5. Circulation (not part of dly)
255
PN 16 / PN 16
120 C
pmin = 2.0 bar
See capacity examples
Max. 300 mg/l
9 kg
Cover:
Brushed steel
Dimensions (mm):
Without cover:
With cover:
H420xW250xD150
H420xW255xD160
55
420
200
391
Design specifications:
Nominal pressure (prim/sec.):
Max. supply temperature:
DCW static pressure:
Min. P:
Chloride compounds:
DH
Supply
60
80
60
(5)
1
XB 06H-1 26 + AVE
40
Connections sizes:
DH, DCW, DHW:
R ET (ext. thread)
Circulation: R ET (ext. thread))
Code Nos:
XB 06H-1 26
160
DCW
Bypass
Top view
Cover:
Code no.:
w/o
brushed
brushed
004U8376
004U8378
004U8379
Options
Cover, brushed stainless steel H397xW225 x D160 mm
Circulation set for mounting on site
Safety valve set
AVE expansion unit*
* requires local approval
Supply flow
Primary
C
55
60
60
70
Return flow
Primary
C
21.8
18.9
20.4
16.8
DHW
tap load
l/min
13.16
13.16
16.96
16.86
Pressure loss*
Primary
bar
0.28
0.18
0.31
0.17
Flow rate
Primary
l/h
840
680
900
670
*) Stated pressure loss values are complete, incl. pipes, heat exchanger and valves.
DKDHR
Akva Lux II GW
Instantaneous water heater for low-temperature district heating
Thermostatic and pressure controlled instantaneous water heater with heat exchanger. Unique DHW
temperature control with esaveTM function and cold heat exchanger during standby.
Application
Akva Lux II GW is an instantaneous water
heater featuring high performance. It meets
the future energy demands for low energy
consumption and very low standby heat losses. It is especially suitable for large villas with
for instance several bathrooms or jacuzzi and
for the large family, for which an exceptionally large amount of water is required. The Akva
Lux II GW is also very suitable for small apartment houses with 2-4 apartments.
Construction
The Akva Lux II GW water heater is prefabricated with a gasketed, highly efficient plate
heat exchanger for domestic hot water production, a domestic hot water controller Danfoss PTC2+P, as well as a Danfoss FJVR thermostat for control of the bypass/circulation
temperature. A circulation set, a safety set or,
if approved by local regulations, a Danfoss
AVE expansion unit to avoid having to establish a discharge pipe, is available as optional
equipment.
Design
The Akva Lux II GW is designed for wallmounting and the design emphasizes a userfriendly placement of the controllers. The
Akva Lux II GW can be supplied with a whitelacquered cover in modern design.
Bypass (thermostatic circulation)
The water heater is supplied with a thermostatically controlled bypass, which ensures
VL.GP.H1.02 Danfoss 10/2012
standby. After completion of the tapping process, the controller immediately blocks the
district heating flow, to avoid standby losses
and to protect the heat exchanger from the
formation of lime scale and growth of bacteria. The heat exchanger is cold during standby, so the heat loss is very low. The integrated
differential pressure controller compensates
for variations in supply temperature and varying differential pressure and thereby ensures
a constant hot water temperature at all times.
Service and maintenance
The water heater is very service-friendly and
easy to install. It is mounted on the wall and
as all pipes are placed in pipe bracket distance, it is possible to establish a nice piping.
Akva Lux II GW
Circuit diagram Example
1. Gasketed plate heat exchanger in stainless steel, type
U141RH
2. Domestic hot water controller Danfoss PTC2+P with esaveTM
function (= cold heat exchanger during standby).
3. By-pass/circulation thermostat Danfoss FJVR.
4. Connection of capillary tube from Danfoss FJVR acting as by-pass
(standard function).
6 5
DHW
circ.
---------------------------------------------------------------------------------Bypass
DHW circulation:
DCW
DHW
Design specifications:
Nominal pressure (prim/sec.):
Max. supply temperature:
DCW static pressure:
Min. P:
Chloride compounds:
Weight incl. cover:
(incl. packing)
DH
Supply
DH
Return
PN 16 / PN 16
120 C
pmin = 2.0 bar
See capacity examples
Max. 300 mg/l
Connections:
1. Domesctic cold water (DCW)
2. Domestic hot water (DHW)
3. District heating (DH) supply
4. District heating (DH) return
5. Circulation (not part of dly)
17 kg
Code Nos:
Akva Lux II GW
water heater with
heat exchanger
Cover: White-lacquered
steel
Dimensions (mm):
Without cover:
With cover:
(Please note that AVE must not be used on systems with DHW circulation. For
systems with DHW recirculation the water heater must be supplied with circulation pump, non-return valve and safety valve mounted in the cold water
supply).
(5)
U141RH
H463xW280xD230
H463xW300xD240
Code no.:
w/o cover
w. cover
004U8366
004U8367
Options:
Cover H 430 x W 300 x D 240 mm
AVE pressure equalizer *
Circulation set for mounting on site
Safety valve set
Wall
Connections sizes:
DH, DCW, DHW:
G ET (ext. thread)
Circulation:
R ET (ext. thread)
Cover
(5)
Top view
Plate heat
exchanger
U141RH
U141RH
U141RH
U141RH
Supply flow
primary
C
55
60
60
60
Return flow
primary
C
22
18
20
22
DHW
tap load
l/min
13.16
13.16
16.86
21.84
Pressure loss*
Primary
bar
0.23
0.16
0.24
0.45
Flow rate
Primary
l/h
840
660
880
1200
*) Stated pressure loss values are complete, incl. pipes. heat exchanger and valves
DKDHR
ThermoDual
Domestic hot water charging system for hospitals, hotels, restaurants,
sport centres as well as industrial buildings and dwelling houses
Domestic hot water charging system with heat exchanger
and optional self-acting or electronic controls
Application
ThermoDual is a compact and
effective domestic hot water (DHW)
charging system. It optimally
combines the system of storage
water heater and instantaneous water
heating system. The ThermoDual
system is suitable for hospitals,
hotels, restaurants, sport centres
as well as industrial buildings and
dwelling houses, where the constant
DHW temperature even during peak
consumption periods is needed.
ThermoDual can be supplied from
local and district heating systems,
low-temperature or condensing
boilers, boiler systems as well as solar,
process and waste heat systems. The
system is available in two different
types with integrated DHW storage
tank and integrated brazed (S) or
gasketed (GS) plate heat exchanger.
Domestic hot water (DHW)
The ThermoDual system can
be delivered with self-acting or
electronic controller for controlling
ThermoDualS/GS
ThermoDual
Circuit diagram - example
CVS/CVE
HEL TC
SFV
3
37
balancing valve
TC
DTA
LPU
Connections:
1
2
3
4
5
37
Technical parameters:
Type S
Nominal pressure: PN 16 (25)2
DH supply temp.: Tmax = 100 (150)2 C
Type GS
Nominal pressure: PN 3
DH supply temp.: Tmax = 110 C
Options:
Stainless steel DHW storage tank, series
SE, capacity 100 ... 8000 liters
Tube and shell heat exchanger,
stainless steel, series SHRVAA
DHW-adequate bronze or stainless
steel charging pump
Balancing valve
Stainless steel sensor pockets
Available on request.
Type
200-010
500-060
1000-060
300-030
-GS 500-020
1000-050
-S
DHW
temperatures
prim./sec.
C
70->25/10->60
65->35/10->60
Performance
index
NL3
8
72
87
35
30
87
Connected
load
kW
25
150
150
100
60
150
Dimensions
Input
W4
l/10 min
l/h
H
mm
W
mm
D
mm
388
1294
1973
817
925
1973
902
4373
5051
2864
2157
5051
1540
1765
2080
1705
1765
2080
800
1050
1150
1375
1450
1570
700
950
1250
975
1100
1200
max.87
Connections
Net
weight
kg
1, 2
68
103
169
150
173
244
11/2
2
11/2
2
3
3/4
1
4, 5
DN 20
(26,9mm)
3/4
G 11/4
Performance index NL acc. to DIN 4708 in relation to a storage tank water temperature of 60 C.
Charging pump; A.C. 1~230 V / 50 Hz; thermal motor overload protection or motor protection by integrated thermo switch.
3
4
DEN-SMT/PL
heating and lime scale formation. The sensor accelerator and AVTB valve also works
as a bypass keeping the house supply line
warm. This shortens the waiting periods during summer when the heating system is in
reduced operation. The sensor accelerator
helps to ensure a stable hot water temperature by varying loads, flow temperatures and
differential pressure without the need for
readjusting the valve. There is no additional
pressure loss on the secondary side of the
DHW heat exchanger with a thermostatic
control. Therefore this type of regulation can
be used by low pressure on the in the cold
water mains.
Construction
All pipes are made of stainless steel. The connections are made by nuts and gaskets. The
Termix One comes with a complete fully insulated cover thus minimizing the heat loss
both during tapping of domestic hot water
but also in standby mode.
DH
supply
DHW
DH
return
DCW
Technical parameters:
Nominal pressure:
DH supply temperature:
DCW static pressure:
Brazing material (HEX):
PN 16
Tmax = 120 C
pmin = 0,5 bar
Copper
Weight:
10 - 12 kg
(incl. packing)
Connections sizes:
DH + DCW + DHW:
G (ext. thread)
Connections:
1 Domestic cold water (DCW)
2 Domestic hot water (DHW)
3 District heating (DH) supply
4 District heating (DH) return
Dimensions (mm):
H 435 x W 355 x D 195 (type 1+2)
Options:
Booster pump (increases DH flow)
Safety valve and non-return valve (10
bar)
Safety valve with thermostatic circulation set
Thermostatic circulation set
Non-return and pressure equalizer
(GTU)
Wall
DHW
Capacity
kW
Type 1
w/AVTB 15
1 household
29.3
38.2
37.8
52.3
Supply
flow
Primary
C
60
60
70
70
Return
flow
Primary
C
23.0
25.2
20.0
22.4
Pressure
loss
Primary
kPa
20
45
20
45
Flow
rate
Secondary
l/h
630
822
816
1128
Substation type
Type 2
w/AVTB 20
up to 4 households
Supply
DHW
flow
Capacity
Primary
kW
C
34.7
60
47.1
60
45.1
70
65.6
70
Return
flow
Primary
C
24.4
26.8
21.3
23.8
Pressure
loss
Primary
kPa
20
45
20
45
Flow
rate
Secondary
l/h
744
1014
972
1410
Gemina Termix A/S Member of the Danfoss Group Navervej 15-17 DK-7451 Sunds Denmark
Tel.: +45 9714 1444 Fax: +45 9714 1159 mail@termix.dk www.heating.danfoss.com
DEN-SMT/PL
Data sheet
ThermoDual
Domestic hot water charging system
Description/Application
S
150
25
ThermoDual-S
Compact DHW charging system with stainless
steel domestic hot water storage tank and
brazed plate heat exchanger as well as
pre-installed piping assembly with allrequired
fittings for installation.
DEN-SMT/PL
GS
110
3
Circulation water/DHW
Secondary
90
10
ThermoDual-GS
Compact DHW charging system with stainless
steel domestic hot water storage tank and
gasketed plate heat exchanger as well as
pre-installed piping assembly with all required
fittings for installation.
Data sheet
Ordering
Code No.
004F7468
004F7469
004U1700
004U1701
004U1702
004U1703
004U1707
004U1708
004U1709
004U1710
004U1711
004U1712
004U1714
004U1715
004U1716
004U1717
004U1718
004U1719
004U1721
004U1722
004U1723
004U1724
004U1725
004U1726
004U1727
004U1729
004U1730
004U1731
004U1732
004U1733
004U1734
004U1737
004U1738
004U1739
004U1740
004U1741
Code No.
004U1743
004U1744
004U1748
004U1749
004U1753
004U1754
004U1755
004U1756
004U1758
004U1759
004U1760
004U1761
004U1763
004U1764
004U1765
004U1766
DEN-SMT/PL
Data sheet
Accessories
Type
Code
Vpc min
dp
Vpc max
dp
[l/min]
[kPa]
[l/min]
[kPa]
connection
lenght L
weight
[mm]
[kg]
3a
3b
R1"
R1
544
5,3
TD-Z 25-25-I
004U1624
80
20
70
TD-Z 25-25-II
004U1625
10
80
40
40
R1
R1
544
5,3
TD-Z 25-32-I
004U1626
20
70
60
15
R1
R1
535
5,5
DEN-SMT/PL
Data sheet
Technical data
[l/10
min]
10 -> 45 C
[l/h]
10 -> 60 C
[l/h]
Heating
water
flow
[l/h]
Pressure
loss
HEX
[kPa]
380
542
759
1083
431
479
13
690
766
11
1034
1149
1379
1532
11
616
431
479
13
986
690
766
11
1906
1477
1034
1149
757
2399
1970
1379
1532
11
100
839
2892
2463
1724
1915
10
130
962
3630
3201
2241
2489
11
12
25
603
1116
616
431
479
13
350-016
18
40
664
1486
986
690
766
11
350-026
26
60
746
1977
1477
1034
1149
350-030
34
80
828
2470
1970
1379
1532
11
350-040
39
100
910
2963
2463
1724
1915
10
350-050
48
130
1033
3701
3201
2241
2489
11
500-010
15
25
817
1330
616
431
479
13
21
40
879
1700
986
690
766
11
500-026
30
60
960
2191
1477
1034
1149
500-030
39
80
1043
2684
1970
1379
1532
11
500-040
48
100
1125
3177
2463
1724
1915
10
500-050
63
130
1248
3915
3201
2241
2489
11
500-060
72
150
1330
4407
3693
2585
2872
10
750-016
27
40
1236
2057
986
690
766
11
750-026
36
60
1318
2548
1477
1034
1149
750-030
45
80
1400
3041
1970
1379
1532
11
750-040
55
100
1482
3534
2463
1724
1915
10
750-050
70
130
1605
4272
3201
2241
2489
11
750-060
80
150
1687
4764
3693
2585
2872
10
1000-026
43
60
1675
2906
1477
1034
1149
1000-030
52
80
1757
3399
1970
1379
1532
11
1000-040
62
100
1839
3892
2463
1724
1915
10
1000-050
77
130
1962
4630
3201
2241
2489
11
1000-060
87
150
2044
5122
3693
2585
2872
10
300-020
23
60
675
1906
1477
1034
1550
14
300-030
35
100
839
2892
2463
1724
2605
16
350-020
26
60
746
1977
1477
1034
1550
14
350-030
40
100
910
2963
2463
1724
2605
16
500-020
30
60
960
2191
1477
1034
1550
14
500-030
48
100
1125
3177
2463
1724
2605
16
500-040
63
130
1248
3915
3201
2241
3328
15
500-050
72
150
1330
4407
3693
2585
3738
12
36
60
1318
2548
1477
1034
1550
14
750-030
55
100
1482
3534
2463
1724
2605
16
750-040
70
130
1605
4272
3201
2241
3328
15
750-050
80
150
1687
4764
3693
2585
3378
12
1000-020
43
60
1675
2906
1477
1034
1550
14
1000-030
62
100
1839
3892
2463
1724
2605
16
1000-040
77
130
1962
4630
3201
2241
3328
15
3738
12
Connected
load [kW]
22
233
686
543
44
324
1227
1084
200-010
25
388
902
616
200-016
11
40
450
1272
986
200-026
15
60
532
1763
1477
200-030
20
80
614
2256
1970
300-010
11
25
531
1045
300-016
17
40
593
1415
300-026
23
60
675
300-030
29
80
300-040
35
300-050
43
350-010
100-020
100-036
500-016
-GS
Performance
index NL*
Type
-S
750-020
DHW
temperatures
prim./sec. [C]
70->35/10->60
70->25/10->60
65->35/10->60
[l/h]
1000-050
87
150
2044
5122
3693
2585
* Performance index l NL acc. to DIN 4708 in relation to a storage tank water temperature of 60 C
** Charging pump; A.C. 1 ~ 230 V / 50 Hz; thermal motor overload protection or motor protection by integrated thermo switch
Input
[W]**
max.87
DEN-SMT/PL
Data sheet
CVS/CVE
HEL TC
SFV
3
37
balancing valve
TC
DTA
LPU
Connections:
1 Domestic water cold
2 Domestic water hot
3 Circulation (options)
4 Heating supply
5 Heating return
37 Domestic water load
Components:
DTA Domestic buffer tank
HEL HEX charging/load
LPU Charging pump/load
SFV Safety valve
CVE Control valve electrical (accessory)
CVS Control valve self-acting (accessory)
DEN-SMT/PL
Data sheet
DEN-SMT/PL
Data sheet
Sizing
Example:
Performance index:.......... NL 60
Selected:
Storage tank capacity:..... 750 liters
DEN-SMT/PL
Evaluated:
Power consumption:........ 110 kW
Data sheet
Mounting
ThermoDual-S
After the storage tank has been set up, the heat
exchanger is attached. The pre-mounted fitting
set, charging pump and stainless steel pipe can
be easily installed due to mainly flat screw-top
connections. The blow-off pipe of the safety
valve is to be installed by the customer, based on
local conditions and requirements.
ThermoDual-GS
Connect the storage tank and the heat
exchanger with the pre-mounted piping set,
fitting sets and charging pump.
The blow-off pipe of the safety valve is to
be installed by the customer, based on local
conditions and requirements.
Dimensions
ThermoDual-S-100
ThermoDual-GS
05
01
04
02
02
03
04
05
01
ThermoDual-S 2001000
DEN-SMT/PL
Data sheet
Type
-S
-GS
100-020
100-036
200-010
200-016
200-026
200-030
300-010
300-016
300-026
300-030
300-040
300-050
350-010
350-016
350-026
350-030
350-040
350-050
500-010
500-016
500-026
500-030
500-040
500-050
500-060
750-016
750-026
750-030
750-040
750-050
750-060
1000-026
1000-030
1000-040
1000-050
1000-060
300-010
300-020
300-030
350-010
350-020
350-030
500-010
500-020
500-030
500-040
500-050
750-020
750-030
750-040
750-050
1000-020
1000-030
1000-040
1000-050
connections
[mm]
[mm]
approx.9
[mm]
approx.9
[mm]
670
730
1290
610
575
1540
590
760
835
1705
640
860
885
1725
690
895
935
1,2
Rp
3
Rp
4,5
DN/G
"
20/257
1765
790
895
1035
2080
890
1020
1135
1"
2"
2080
990
1105
1255
1705
640
1270
920
1725
690
1295
970
1765
790
1345
1070
2080
890
1395
1155
18
1
2
2080
1030
1465
1275
weight6
[kg]
40
45
68
69
70
71
72
73
74
75
77
79
79
80
81
82
84
86
93
94
95
96
98
100
103
140
141
142
144
146
149
161
162
164
166
169
140
145
150
146
151
156
168
173
178
181
184
191
195
199
202
223
237
241
244
DEN-SMT/PL
Data sheet
10
DEN-SMT/PL
Akva Therm II LV
Domestic hot water charging system for hospitals, restaurants,
sporting centres as well as commercial buildings and apartment blocks
Domestic hot water charging system. Can be supplied directly from district heating supply networks, from
low-temperature or condensing boilers, solar-, process- or waste heat systems.
Application
The Akva Therm II LV is a compact and
effective domestic hot water (DHW)
charging system.
It optimally combines the two systems,
storage water heating and instantaneous water heating and is applicable
for hospitals restaurants, sport centres
as well as commercial buildings and
apartment blocks, where a constant
DHW temperature even during peak
consumption periods is needed.
The Akva Therm II LV can be supplied
from district heating supply networks,
from low-temperature or condensing
boilers, solar-, process- and waste heat
systems.
Domestic hot water
The Akva Therm II LV charging system is
delivered as a set consisting of a stainless steel DHW cylinder, a brazed, stainless steel plate heat exchanger, Danfoss
XB37H-1, Danfoss ECL 310 for control of
the charging temperature and temperature in the DHW cylinder, Wilo low-energy circulation pump, shut-off valves,
balancing valves / flow limiter, safety
valves, thermometers as well as readyto-mount pipes and fittings.
Long life
The use of acid-resistant, stainless steel for pipes, tank and heat exchanger,
and dezincification-resistant brass for Tpieces, components and valves, as well
as approved components secures the
charging system a long life.
Akva Therm II LV
Circuit diagram - example
DH
Supply
DHW
Circ.
DH
Return
Supply limit
DCW
LV20-500
LV36-750
LV50-1000
Dimensions, tank:
LV16-350:
LV20-500:
LV36-750:
LV50-1000:
H 1750 x D 720 mm
H 1890 x D 720 mm
H 2130 x D 920 mm
H 2180 x D 1060 mm
340
128
571
79 kg
95 kg
145 kg
169 kg
350 L: 1750
500 L: 1890
750 L: 2130
1000 L: 2180
300
155
Technical parameters:
Nominal pressure:
PN 16 / PN 10
Max. temperature: 95 C (construction temp.)
Min. P:
See capacity examples
3 5
1000 L: Dia.1060
750 L: Dia.920
350 - 500 L: Dia.720
Connections:
1. District heating (DH) supply
2. District heating (DH) return
3. Domestic cold water (DCW)
4. Domestic hot water (DHW)
5. Circulation (optional)
6. Circulation
Connections (examples):
LV16-350:
DCW,DHW 1
LV20-500:
DCW,DHW 1
LV36-750:
DCW,DHW 2
LV50-1000:
DCW,DHW 2
DH., Circ.
DH ., Circ. 1
DH., Circ. 1
DH., Circ. 1
200
Akva Therm II
LV Type
LV16-350
LV20-350
LV20-500
LV36-350
LV36-500
LV36-750
LV50-500
LV50-750
LV36-750
Tank
volume
350
350
500
350
500
750
500
750
1000
No. of
apartments.
(guiding)*
15
18
22
36
41
47
58
63
69
Heat
exchanger
(kW)
25
40
40
80
80
80
110
110
110
Capacity
Constant,
Max. capacity
DHW
(l/h)
(l/h)
537
800
860
1123
860
1235
1720
1983
1720
2095
1720
2283
2365
2740
2365
2928
2365
3115
Primary
Max. capacity
l/10 min.)
Pressure loss
bar
Flow
(l/h)
352
406
518
549
662
849
769
957
1144
0.19
0.19
0.19
0.25
0.25
0.25
0.21
0.21
0.21
478
764
764
1529
1529
1529
2102
2102
2102
DKDHR
Termix One-B
Instantaneous water heater for flats, single-family houses
and small apartment buildings with up to 10 flats
Instantaneous water heater with heat exchanger
and thermostatic control. Designed for wallmounting.
Application
The Termix One is an instantaneous
water heater featuring superb heat
extraction and high performance.
The Termix One is suitable for flats,
single-family houses as well as for
small apartment buildings with up
to 10 apartments. The water heater
is available in three sizes, either for
1 apartment, for 14 apartments or
for 5 up to 10 apartments. The Termix
One is applicable for decentralized
heating systems as well as for district heating networks with summer
operation at low temperatures or
changes in differential pressure. The
Termix One heat exchanger cools the
district heating water very efficiently,
thereby creating a very good operation economy.
Domestic hot water (DHW)
The domestic hot water is prepared in
the heat exchanger and the temperature is regulated with a thermostatic
control valve. The patented sensor accelerator accelerates the closing of the
Danfoss AVTB valve and protects the
heat exchanger against overheating
and lime scale formation. The sensor accelerator and AVTB valve also works as
a bypass keeping the house supply line
districtenergy.danfoss.com
Termix One-B
Circuit diagram example
DH
Supply
DHW
21
7
DH
Return
62
DCW
DH
Supply
DHW
21
6
B
2
4
6
7
21
Circ.
DH
Return
DCW
Technical parameters:
Nominal pressure:
DH supply temperature:
DCW static pressure:
Brazing material (HEX):
PN16
Tmax = 120C
Pmin = 0.5bar
Copper
1012kg
(incl. packing)
Connections:
1. Domestic cold water (DCW)
2. Domestic hot water (DHW)
3. District Heating (DH) supply
4. District heating (DH) return
Connections sizes:
DH + DCW + DHW:
wall
Cover:
Grey-lacquered steel
Dimensions (mm):
Without cover:
H428 W312 D155
H468 W312 D155
With cover:
H430 W315 D165
H470 W315 D165
G (ext. thread)
Options:
Booster pump (increases DH flow)
Grey-lacquered steel cover
Safety valve and
non-return valvve (10bar)
Safety valve with
thermostatic circulation set
Pressure equalizer (GTU)
(type 1+2)
(type 3)
(type 1+2)
(type 3)
Type 1
w/AVTB 15
1 household
Type 3
w/AVTB 20
5 to 10* households
DHW
capacity
[kW]
Supply
flow
primary
[C]
Return
flow
primary
[C]
Pressure
Flow
loss
rate
primary secondary
[kPa]
[l/h]
29.3
38.2
37.8
52.3
60
60
60
70
70
60
23.0
25.2
20.0
22.4
23.0
20
45
20
45
35
630
822
816
1128
1280
66
60
24.0
45
1426
80
90
70
70
20.3
21.0
35
45
1730
1940
DHW
capacity
[kW]
Supply
flow
primary
[C]
Return
flow
primary
[C]
34.7
47.1
45.1
65.6
60
60
70
70
24.4
26.8
21.3
23.8
20
45
20
45
744
1014
972
1410
Substation
type
Type 2
w/AVTB 20
up to 4 households
Pressure
Flow
loss
rate
primary secondary
[kPa]
[l/h]
Gemina Termix A/S Member of the Danfoss Group Navervej 15-17 DK-7451 Sunds Denmark
Tel.: +45 9714 1444 Fax: +45 9714 1159 mail@termix.dk www.heating.danfoss.com
DENSMT/PL
Akva Lux II
Fully insulated instantaneous water heater for low-temperature
district heating
Thermostatic and pressure controlled instantaneous water heater
with heat exchanger. Unique DHW temperature control with energy
saving function and cold heat exchanger during standby.
Application
Akva Lux II is a fully insulated instantaneous water heater featuring high performance. It meets the future energy demands for low energy consumption and
very low standby heat losses. It is especially suitable for large villas with for instance several bathrooms or jacuzzi and
for the large family, for which an exceptionally large amount of water is required. The Akva Lux II is also very suiable for small apartment houses with
2-4 apartments.
Construction
The Akva Lux II water heater is prefabricated with a brazed, highly efficient
Danfoss plate heat exchanger for domestic hot water production, a domestic
hot water controller Danfoss PTC2+P,
as well as a Danfoss FJVR thermostat for
control of the bypass/circulation temperature. A circulation set and a safety set
is available as optional equipment.
Design
The Akva Lux II is designed for wallmounting and much importance has
been assigned to a user-friendly and
easily accessible placement of all system
components, including the controllers.
The Akva Lux II is fully insulated in an
EPP insulation box and can be supplied
with a white-lacquered cover in modern
design.
Bypass (thermostatic circulation)
The water heater is supplied with a thermostatically controlled bypass, which
ensures that hot water is produced immediately, when tapping starts. The by-
districtenergy.danfoss.com
pass temperature is set with due consideration of the best possible DHW comfort and economy.
Domestic hot water recirculation
The water heater is prepared for domestic hot water circulation. If the household piping includes hot water recirculation the water heater must be connected to the hot water recirculation
system and a circulation pump and a
non-return valve must be mounted on
the circulation pipe and a safety valve
must be mounted in the DCW inlet. The
pump must be installed so that it pumps
towards the water heater. Domestic hot
water recirculation ensures that hot water is available at the tapping point without waiting time and waste of water.
The circulation temperature is set independently of the set DHW temperature. This ensures the best possible DHW
comfort, very low standby losses and
thus a very good district heating economy.
Heat exchanger for DHW heating
The water heater is based on a brazed, highly efficient plate heat exchanger type XB 06H-1 26 or XB 06H-1 40,
which is controlled by a thermostatic
and pressure controlled DHW controller, Danfoss PTC2+P with integrated differential pressure controller and energy
saving function, which ensures that the
heat exchanger is cold during standby.
After completion of the tapping process,
the controller immediately blocks the district heating flow, to avoid standby losses and to protect the heat exchanger
from the formation of lime scale and
Akva Lux II
Circuit diagram example
2. Danfoss, copper brazed plate heat exchanger in stainless
steel AISI 316, type XB 06H-1 26 or XB 06H-1 40.
38. Domestic hot water controller Danfoss PTC2+P with energy saving
function (= cold heat exchanger during standby).
40. By-pass/circulation thermostat Danfoss FJVR.
----------------------------------------------------------------------------------
38
C B
DHW
circ.
DHW circulation:
A. Connection of capillary tube from Danfoss FJVR acting as by-pass
(standard function).
B. Connection of capillary tube from Danfoss FJVR acting as circulation
thermostat.
C. Connection of circulation hose. Circulation set for control
2 change from bypass
to DHW recirculation
is not part of5 the delivery and
3
4
must be ordered seperately.
40
A
A
For
systems with DHW
recirculation the 4water heater must 5be supplied with
3
2
circulation
pump, non-return valve and safety valve mounted in the cold
200
water supply.
PN16 / PN16
120C
pmin = 2.0bar
See capacity examples B
Copper
DH
return
XB06H-1 26 = 8kg
Insulation:
EPP 0.039
200
Code Nos:
Akva Lux II water
heater with heat
exchanger type:
Cover:
White-lacquered steel
D
306
80
60
306
(5)
80
XB 06H-1 40
60
XB 06H-1 26
XB 06H-1 26
XB 06H-1 40
XB 06H-1 40
XB 06H-1 26
XB 06H-1 26
XB 06H-1 40
XB 06H-1 40
Supply
flow
F
primary
[C]
1
F 55
60
1
55
60
60
70
60
70
w/o cover
w. cover
w/o cover
w. cover
004U8243
004U8245
004U8244
004U8246
Projection
Replace
Projection
Return flow
primary
[C]
2
21.8
18.9
2
19.0
17.0
20.4
16.8
19.1
15.7
DHW
tap load
[l/min]
3
13.16
13.16
3
13.16
13.16
16.86
16.86
21.84
21.84
Pressure loss*
primary
[bar]
4
0.28
0.18
4
0.19
0.13
0.31
0.17
0.39
0.25
Approval
Weight
Replace
Flow rate
primary
[l/h]
840
680
770
650
900
670
1127
850
kg
Scale
1:5
Danfoss Re
Design
Not to be handed over to, copied or used by third party. Two- or three
Approval
Danfoss Red
* Stated pressure loss values are complete, incl. pipes, heat exchanger and valves.
Danfoss Redan A/S District Heating Omega 7, Sften DK-8382 Hinnerup Denmark
Tel.: +45 87 43 89 43 Fax: +45 87 43 89 44 redan@danfoss.com www.redan.danfoss.dk
Scale
1:5
kg
Weight
Code no.:
Options:
Cover H 410 x W 310 x D 210 mm
Circulation set for mounting on site
Safety valve set
60
DHW
capacity
[kW]
32.3
32.3
32.3
32.3
41.0
41.0
53.0
53.0
Insulated*
* Akva Lux II is fully insulated and available with out w/o white cover.
190
60
40
40
Connections sizes:
DH, DHW, DCW:
Circulation:
XB 06H-1 26
190
Dimensions (mm):
Insulated:
Insulated with cover:
Connections:
1. Domestic cold water (DCW)
2. Domestic hot water (DHW)
3. District heating (DH) supply
4. District heating (DH) return
5. Circulation
463
403
145,5
Design specifications:
Nominal pressure (prim/sec.):
Max. supply temperature:
DCW static pressure:
Min. P:
Brazing material (HEX):
DH
supply A
145,5
DHW
463
403
DCW
DKDHR
Termix
One Solar Light
Domestic hot water module for flats, single-family houses
and apartment buildings with up to 10 apartments
Domestic hot water module with heat exchanger
and thermostatic control. Designed for wall-mounting.
Application
The Termix One Solar Light is an instantaneous water heater, featuring
superb heat extraction and high performance. The Termix One Solar Light
is applicable for heating systems
with buffer accumulators, solar systems or for other heat sources, where
avery low return temperature is preferred. The water heater is available
in three sizes, either for 1 apartment,
for 1-4 apartments or for 5 up to 10
apartments. The large heat exchanger cools out the water in the primary
return line very efficiently, thereby
creating a very good operation
economy. A flow switch in cold water
mains is controlling the primary heating pump. An optional circulation
pump together with a thermostat can
maintain the circulating temperature
at adesired temperature.
Domestic hot water (DHW)
The domestic hot water is prepared in
the heat exchanger and the temperature is regulated with a thermostatic
control valve. The patented sensor
accelerator accelerates the closing
of the thermostatic control valve and
protects the heat exchanger against
overheating and lime scale formation.
districtenergy.danfoss.com
The sensor accelerator and the thermostatic control valve also works as
a bypass keeping the heat exchanger
and supply line warm. This shortens
the waiting periods. The sensor accelerator helps to ensure a stable hot
water temperature by varying loads,
flow temperatures and differential
pressure without the need for readjusting the valve. There is no additional pressure loss on the secondary
side of the DHW heat exchanger with
a thermostatic control. Therefore this
type of regulation can be used by low
pressure in the cold water mains.
Options
M
21
1
230V
21
13
1
21
35
48
45
11A
1
2
39
63
B
Termix One Solar Light
O Termix Sensor Accelerator
B Heat exchanger DHW
M Electrical wiring box
1 Ball valve
Technical parameters:
Nominal pressure:
DH supply temperature:
DCW static pressure:
Brazing material (HEX):
PN16
Tmax = 120C
Pmin = 0,5bar
Copper
13 Charging pump
21 To be ordered separately
35 Ball valve / non-return valve
39 Connection closed
45 Flow switch
wall
Options:
Safety valve and
non-return valve (10bar)
Circulation
Cover
4 ball valves
4 ball valves; hereof 2 with DVGW
approval (ball valve length,
incl. 1 gasket: 60mm) (DVGW ball valve
length, incl. 1 gasket: 79mm)
Connections:
1. Domestic cold water (DCW)
2. Domestic hot water (DHW)
3. Buffer tank (BT) supply
4. Buffer tank (BT) return
5. Circulation
Connections sizes:
All connections:
G (int. thread)
Cover:
Grey-lacquered
steel sheet
Dimensions (mm):
Without cover:
With cover:
With circulation
With cover:
DHW
capacity
[kW]
29,3
38,2
37,8
52,3
60,0
66,0
80,0
90,0
Substation
type
Type 2
w/AVTB 20
up to 4
households
DHW
capacity
[kW]
34,7
47,1
45,1
65,6
Gemina Termix A/S Member of the Danfoss Group Navervej 15-17 DK-7451 Sunds Denmark
Tel.: +45 9714 1444 Fax: +45 9714 1159 mail@termix.dk www.heating.danfoss.com
DENSMT/PL
Data sheet
ThermoClean
Domestic water heating system with legionella growth
prevention through thermal disinfection
Description/Application
Secondary
DL/Combi
100 (150)2
16 (25)2
Circulation water
90
10
DHW
DEN-SMT/PL
Data sheet
ThermoClean-DL
Domestic water heating system with electronic
controls, a stainless steel reaction storage tank,
charging and re-cooling brazed plate heat
exchangers as well as charging pump, shut-off
valves and complete stainless steel piping.
Ordering
ThermoClean-Combi
Domestic water heating system with electronic
controls, a combined stainless steel reaction and
domestic hot water storage tank, charging and
re-cooling brazed plate heat exchangers as well
as charging pump, shut-off valves and complete
stainless steel piping.
The ThermoClean-Combi requires less
installation space provided adequate height in
the installation place is available.
Code No.
-DL
004X1347
004X1348
004X1349
004X1350
004X1351
004X1352
-Combi
004X1343
004X1344
004X1345
004X1346
-
DEN-SMT/PL
Data sheet
Accessories 4
ThermoClean-DL
1. Domestic hot water storage tank
The ThermoClean system must be combined
with additional domestic hot water storage
tanks to provide the required capacity for peak
consumption. The required storage tank capacity
is based on the calculated peak flow and the
length of the consumption period.
The recommendations provided overleaf for the
total storage tank capacity are based on peak
consumptions lasting 1 hour or according to
customer demands. If the consumption periods
are shorter, the storage tank capacity can be
reduced accordingly.
We recommend the utilization of the following
storage tanks:
- Stainless steel domestic hot water storage tank
series SE,
- Tank sizes: 150 ... 8000 liters,
- Optimum adaptation to requirements due
to optional combination of multiple storage
tanks.
2. Over-tapping protection
Several unexpected factors can result in the
complete consumption of the available storage
tank capacity, which again can lead to the
addition of domestic cold water to the hot water
network that has not run through a proper
thermal disinfection. The potential causes are for
example:
- Heating medium not available in sufficient
quantity or at the adequate temperature,
- Insufficient heat transfer in the heat exchanger
due to fouling,
- Technical defect of a system component (e.g.,
failure of the charging pump),
- Peak consumption continues longer than the
calculated consumption period.
Technical data
Type
Perfor
mance
index
Max. power
Connected
for peak
load
consumption
NL5
kW
kW
200
-6
84 .. 46
140
350
-6
147 .. 80
245
500
-6
210 .. 114
350
-DL
750
-6
315 .. 171
525
1000
-6
420 .. 228
700
1300
-6
546 .. 296
910
350
15 .. 9
55 .. 30
91
500 28 .. 13
71 .. 39
119
-Combi
750 41 .. 21
88 .. 48
147
1000 52 .. 29
101 .. 55
168
5
Performance index NL acc. to DIN 4708
6
Dependent on the additional storage tank(s)
DEN-SMT/PL
Heating
(Hot)
water flow
at VL = 75 C
l/h
2480
4440
6480
9650
12960
16980
1620
2120
2620
2970
Charge
flow
total
Circ.
flow
(max.)
l/h
2400
4200
6000
9000
12000
15600
1560
2040
2520
2880
l/h
1070 .. 1800
1870 .. 3150
2670 .. 4500
4000 .. 6750
5330 .. 9000
6930 .. 11700
690 .. 1170
910 .. 1530
1120 .. 1890
1280 .. 2160
Resistance
Heating DHW
Circ.
water (max.) (max.)
kPa
kPa
kPa
24
54
19
20
64
20
22
58
20
23
59
23
29
65
27
35
86
30
20
56
18
21
56
19
22
49
14
24
49
14
Data sheet
CPU
ECD
1
HEL
45
47
4
CVE
DTA
RTA
SFV
CVD
5
HEC
LPU
46
RTA
HEL
HEC
LPU
CPU
SFV
CVE
ECD
CVD
DTA
reaction tank/vessel
HEX charging/load
HEX cooling
charging pump/load
circulation pump (on site/by customer)
safety valve
control valve electrical
electronic controller DHW
control valve electrical domestic
domestic buffer tank (accessory)
shut off device
balancing valve
check valve
sampling valve
DEN-SMT/PL
Data sheet
Sizing
Mounting
ThermoClean-DL
After setting up, connect reaction and DHW
storage tank, charge/re-cooling system unit
via the pre-installed connections. Next the
heating and domestic water connections, mains
connections. Commissioning as described in the
installation and operating instructions.
ThermoClean-Combi
After setting up, connect combination and DHW
storage tank, charge/re-cooling system via the
pre-installed connections. Next the heating
and domestic hot water connections, mains
connections. Commissioning as described in the
installation and operating instructions.
Dimensions
ThermoClean-DL ThermoClean-Combi
B1
B1
B2
45 46
1 4 3
47
2
3
H2
H1
H1
4
2
25
H2
25
B2
T2
47
3
D
d
T2
T1
D
d
46
T1
45
B1
approx.
B2
approx.
mm
1905
1915
2025
2365
2570
mm
740
930
980
mm
1730
1795
1845
1970
2220
1080
2245
2680
mm
1565
2065
2110
2270
2550
mm
mm
200
350
500
750
1000
500
640
600
7509
8009
1300
2575
9009
Type
-DL
H2
approx.
H1
1000
T1
T2
approx. approx.10
mm
mm
725
600
1100
1200
825
990
965
1250
995
Weight
1, 2
4, 5
45-47
G/Rp
G 1
G 1
G/Rp
G 1
G 1
G 1
G 23/8
Rp 2
Rp
21/2
DN
25/20
40
G/Rp
G 1
G 1
6509
G 23/8
920
Rp
2
350
1995
500
640
1500
500
2035
600
740
1600
7509
-Combi
1800
800
750
2115
750
890
1750
9
1000 2115
850
990
1900
750
7
For ThermoClean type -DL incl. charging unit
8
Mounted on the ThermoClean-Combis tank
9
min. door width; when needed components has to demounted
10
max. width of frame
11
raw weight (without insulation/package)
All connection axis measures are approximate and have a tolerance of +/- 15 mm.
DEN-SMT/PL
Connections
50/40
65/50
G 1
G 1
20
25/20
G 1
G 1
32/20
G 23/8
Rp 2
Storage
tank11
Re-cooling
unit7
Charging
unit8
kg
70
90
90
155
210
kg
140
160
170
230
250
kg
-
235
300
100
15
20
105
25
70
90
145
195
Data sheet
DEN-SMT/PL
Data sheet
DEN-SMT/PL
Data sheet
DEN-SMT/PL
Data sheet
Maximum operating
parameters
Materials
Primary
Maximum permissible supply temperature, primary
Maximum permissible operating pressure, primary
Rated pressure, primary
Maximum permissible pressure differential, primary
Secondary
Maximum permissible temperature, secondary
Maximum permissible operating pressure, secondary
1.0 bar(g)
PN10
230V DC / 4.0 A
Capacity
[kW]
140
210
280
350
420
455
DEN-SMT/PL
90C
10 bar(g)
Code numbers
VD.IQ.I2.02
Pump +
3-way mixing valve
004X1400
004X1401
004X1402
004X1403
004X1404
004X1405
Danfoss 09/2014
Code no.
Pump control
2-way valve
(PWM control signal) (without safety function)
004X1406
004X1412
004X1407
004X1413
004X1408
004X1414
004X1409
004X1415
004X1410
004X1416
004X1411
004X1417
2-way valve
(with safety function)
004X1418
004X1419
004X1420
004X1421
004X1422
004X1423
1
Data sheet
Circuit
diagram
3-Ways (MIX)
Pump
2-Ways
Shut-off valve
Non-return valve
Check valve
Balancing valve
Air vent
Drain
Dain
sampling valve
(optional)
Technical data
FRp
(70->25C)
[m3/h]
Pump
dpr
[kPa]
140
2.4
210
280
350
420
455
3.8
5.1
6.3
7.8
8.0
Type
ThermoDual
Capacity
[kW]
CM 140
CM 210
CM 280
CM 350
CM 420
CM 455
HEL
LPU
HPU
CPU
SFV
CVE
ECD
Circulation (inlet)
Heating supply
Heating return
TC
2-way
dp
[kPa]
3-way
dpr
[kPa]
FRTW
(10->60C)
[m3/h]
52
21
38
2.4
61
44
34
17
23
30
29
30
30
22
47
34
19
17
17
3.6
4.8
6.0
7.2
7.8
FRC*
(55->60C)
[m3/h]
C
dpr**
[kPa]
41
1.0/2.4
80/43
57
45
30
17
16
1.5/2.4
2.0/2.4
2.5/3.4
3.0/3.4
3.3/3.4
70/43
57/43
51/30
38/30
34/31
DW
dpr
[kPa]
FR: Flow rate p: primary dpr: Remaining pump head dp: Pressure loss DW: Domestic water C: Circulation
* flow rate: standard setup / maximal possible
** remaining pump head for: standard setup / maximal possible
VD.IQ.I2.02
Danfoss 09/2014
Data sheet
Function
ECD
TC
DTA
CPU
HEL
TC
TC
CVE
5
TC
TC
LPU
ECD
TC
DTA
CPU
HEL
TC
TC
CVE
5
TC
TC
LPU
ECD
TC
DTA
CPU
HEL
TC
TC
CVE
4
5
TC
TC
LPU
VD.IQ.I2.02
Danfoss 09/2014
Data sheet
Dimensions
Connections:
Type
ThermoDual
DW C/H
Circ.
1/2 G ISO
3 G ISO
1 "A
1 "A
1 "A
1 "A
1 "A
1 "A
1 "A
1 "A
1 "A
1 A
1 "A
1 A
CM 140
CM 210
CM 280
CM 350
CM 420
CM 455
Weight [kg]
HTG (DN)
SL, RL
4/5 PN10
Rp
1 "
1 "
1
1 "
2
2"
HTG (DN)
SL, RL
4/5 PN25
WELD
42.4
42.4
48.3
48.3
60.3
60.3
Pump +
3-way v.
Pump
control
(PWM)
2-way v.
86
93
99
104
113
119
83
89
95
99
104
110
92
96
104
108
118
124
156
174
174
110-160
VD.IQ.I2.02
Danfoss 09/2014
411
634
1830
910
Correlation of connections
1
Circulation (inlet)
Data Sheet
General Description/Use
Maximum operating
parameters
Materials
Primary
Maximum permissible supply temperature, primary
Maximum permissible operating pressure, primary
Rated pressure, primary
Maximum permissible pressure differential, primary
Secondary
Maximum permissible temperature, secondary
Maximum permissible operating pressure, secondary
1.0 bar(g)
PN10
230V DC / 4.0 A
Capacity
[kW]
140
210
280
350
420
455
DEN-SMT/PL
90C
10 bar(g)
Code numbers
Pump +
3-way mixing valve
004X1424
004X1425
004X1426
004X1427
004X1428
004X1429
Code no.
Pump control
2-way valve
(PWM control signal) (without safety function)
004X1430
004X1436
004X1431
004X1437
004X1432
004X1438
004X1433
004X1439
004X1434
004X1440
004X1435
004X1441
2-way valve
(with safety function)
004X1442
004X1443
004X1444
004X1445
004X1446
004X1447
1
Data Sheet
Circuit diagram
Shut-off valve
Non-return valve
Check valve
Balancing valve
Air vent
Drain
Drain, sampling valve
(optional)
Flow sensor
Technical data
FRp
(70->25C)
[m3/h]
Pump
dpr
[kPa]
140
2,4
210
280
350
420
455
3,8
5,1
6,3
7,8
8,0
Type
ThermoDual
Capacity
[kW]
FLS 140
FLS 210
FLS 280
FLS 350
FLS 420
FLS 455
HEL
HPU
CPU
SFV
CVE
ECD
STW
BTA
Heat exchanger
Heating pump
Circulation pump
Safety valve
Motorized control valve (2/3-way)
Electronic domestic hot water controller (ThermoControl-3)
Safety thermostat (optional)
Hot water buffer tank (installed by customer)
Circulation (inlet)
Heating supply
Heating return
TC
2-way
dp
[kPa]
3-way
dpr
[kPa]
FRDW
(10->60C)
[m3/h]
52
21
38
2,4
61
44
34
17
23
30
29
30
30
22
47
34
19
17
17
3,6
4,8
6,0
7,2
7,8
FRC*
(55->60C)
[m3/h]
C
dpr**
[kPa]
12
1,0/2,4
80/43
26
28
33
41
39
1,5/2,4
2,0/2,4
2,5/3,4
3,0/3,4
3,3/3,4
70/43
57/45
51/30
38/30
34/31
DW
dp
[kPa]
FR: Flow rate p: primary dpr: Remaining pump head dp: Pressure loss DW: Domestic water C: Circulation
* flow rate: standard setup / maximal possible
** remaining pump head for: standard setup / maximal possible
2
Data Sheet
Function
Flow systems provide heated domestic water when requested. By a heat exchanger (HEL), the cold
water flowing into connection (1will be heated up to set point and provided to the consumer at the
connection (2). The electronic controller (ECD) is measuring the relevant temperatures and controls the
target values that are held constant in all operating conditions. This is i.e. achieved by influencing the
speed of the heating pump (HPU), so that the outlet temperature always matches the specified value.
In case of using a control valve, the flow is directly controlled by an electrical actuator. Short-term peaks
in consumption are registered at the flow sensor to intervene quickly and avoid large temperature
fluctuations. The cooled- circulation water from the network (connection 3) is constantly heated in
heat exchanger (HEL), even in times of draw-off , reheated and the temperature control (sensor) in the
amount of the controlled circulation pump ( CPU) influenced so that only the necessary amount flows
to maintain constant power set point.
The capacity for the peak load is to ensure either by buffering heating water in a tank (BTA) or there
must be a sufficiently large connection value available. The Recharging of a buffer (e.g. from a boiler)
can a requisition (sensor / switch contact) on controller (ECD) using an on-site charging pump (LPU).
The operation of the system by a controlled heating pump (HPU) is only possible without differential
pressure between the connections (4) and (5).
Dimensions
Connections:
Type
ThermoDual
FLS 140
FLS 210
FLS 280
FLS 350
FLS 420
FLS 455
DW C/H
Circ.
1/2 G ISO
3 G ISO
1 A
1 A
1 A
1 A
1 A
1 A
1 A
1 A
1 A
1 A
1 A
1 A
Weight [kg]
HTG (DN)
SL, RL
4/5 PN10
Rp
1
1
1
1
2
2
HTG (DN)
SL, RL
4/5 PN25
WELD
42,4
42,4
48,3
48,3
60,3
60,3
Pump +
3-way v.
Pump
control
(PWM)
2-way v.
82
85
91
96
105
111
79
82
87
91
95
101
88
89
96
100
109
115
429
1830
550
223
910
174
174
411
156
634
Correlation of connections
1
Circulation (inlet)
Data Sheet
Accessories
Materials
tank (shell)
Insulation (from 750 Liter as bypack/not mounted)
Maximum operating
parameters
Type
I
H
mm
H1
mm
H2
mm
TZ
110C
PZ
6bar
H3
mm
H4
mm
H5
mm
H6
mm
H7
mm
HMa
mm
d
mm
Dx
mm
D
mm
Tilted
height mm
4/5
G
4/5
DN/PN
Weight
kg
300
1470
1270
1070
780
620
320
215
115
1130
550
660
710
1550
1 1/4"
85
500
1880
1665
1430
990
650
350
245
145
1550
600
710
800
2010
2"
115
750
1890
1635
1400
1000
670
370
265
165
1500
750
860
950
1945
2"
175
1000
1930
1655
1370
1020
690
390
285
185
1500
850
960
1050
2090
2"
240
1500
2050
1740
1505
1070
725
445
320
220
1550
1000
1110
1200
2160
50/16
325
2000
2330
1995
1750
1220
770
510
375
265
1770
1100
1210
1300
2450
65/16
375
d
24
22
4
Dx
22
H max
45
H1
H2
22
25
22
5
H5
H6
H7
H4
H3
4
45
5
26
4
5
6
22
24
25
26
ThermoClean
Domestic water heating system for hospitals, sports centers, hotels
as well as dwelling-houses
Domestic water heating system with legionella growth prevention
through thermal disinfection
Application
ThermoClean is a compact and
eective
system
solution
for
legionella-free
domestic
water
heating. ThermoClean is suitable for
hospitals, sports centers, hotels and
dwelling houses, where effectively
prevent the development and
growth of legionella is needed. The
system is available in two different
types with separate reaction (-DL) or
combination (-Combi) storage tank
which contains the charging and recooling unit. These units are equipped
with brazed (-DL/-Combi) plate heat
exchangers.
Domestic hot water (DHW)
The ThermoClean system uses
the thermal disinfection method,
whereby the reaction temperature
inside the installation is kept at a
constant temperature of 70 C. It is
dimensioned in such a way that the
water is warranted to remain in the
reaction area of the device for at least
5 minutes. The system is equipped
with electronic controls for controlling
ThermoClean
Circuit diagram - example
RTA reaction tank/vessel
HEL HEX charging/load
HEC HEX cooling
LPU charging pump/load
CPU circulation pump (on site/by customer)
SFV safety valve
CVE control valve electrical
ECD electronic controller DHW
CVD control valve electrical domestic
DTA domestic buffer tank (accessory)
CPU
ECD
1
HEL
45
47
4
CVE
DTA
RTA
CVD
SFV
HEC
LPU
46
thermometer
shut off device
balancing valve
check valve
Technical parameters:
Type -DL/-Combi
Nominal pressure: PN 16 (25)2
DH supply temp.: Tmax = 100 (150)2 C
sampling valve
Options:
Additional buffer storage tank
Butterfly valve with electrical actuator
Control thermostat with stainless steel
immersion pocket
Available on request
-DL
-Combi
200
500
1000
350
500
1000
Performance
index
NL3
-4
-4
-4
15 .. 9
28 .. 13
52 .. 29
Connected
load
kW
84 .. 46
210 .. 114
420 .. 228
55 .. 30
71 .. 39
101 .. 55
Max. power
for peak
consumption
kW
140
350
700
91
119
168
Circ.
flow
(max)
l/h
1070 .. 1800
2670 .. 4500
5330 .. 9000
690 .. 1170
910 .. 1530
1280 .. 2160
Resistance
Heating
water
kPa
24
22
29
20
21
24
DHW
(max)
kPa
54
58
65
56
56
49
Dimensions
Circ.
(max)
kPa
19
20
27
18
19
14
H
mm
W
mm
D
mm
1730
2110
2550
1995
2035
2115
1905
2025
2570
1500
1600
1900
640
740
980
640
740
990
Connections
Weight
kg
1, 2
210
260
460
185
210
325
11/2
23/8
21/2
11/2
11/2
13/4
11/4
13/4
2
11/4
11/4
11/2
4, 5
45-47
25/20 11/2
50/40 23/8
50/40 21/2
20
25/20
32/20
-
3
4
DEN-SMT/PL