Electrical Machine 8 - 2 4: Synchronous Machines (Alternators)
Electrical Machine 8 - 2 4: Synchronous Machines (Alternators)
8-24
B
(a) Star connection
Fig. 8.24
Practically most of the alternators are star connected due to following reasons :
1. Neutral point can be earthed from safety point of view.
2. For the same phase voltage, voltage available across the terminal is more than
delta connection.
3. For the same terminal voltage, the phase voltage in star is -^L- times line value.
v3
This reduces strain on the insulation of the armature winding.
Example 8.4 : An alternator runs at 250 r.p.m. and generates an e.m.f. at 50 Hz. There
are 216 slots each containing 5 conductors. The winding is distributed and full pitch. All the
conductors of each phase are in series and flux per pole is 30 mWb which is sinusoidally
distributed. If the winding is star connected, determine the value of induced e.m.f. available
across the terminals.