Fire Fighting Course

Prepared BY

Eng. Hossam ELdin Samir


e.hosam2000@gmail.com

Supervised By
Eng. Mahmud Abdelaty
Senior Electromechanical Engineer
Engmah111@gmail.com

July, 2015

Fire fighting course

Prepared by \ eng.hosam eldin samir

Fire Fighting Course


...............................................
Course contents
1- Fire science :
1-1 Fire safety
1-2 Fire alarm
1-3 Fire fighting

2- Fire fighting systems:


2-1 water suppression system
2-1-1 sprinkler system;
A)
B)
C)
D)

Types of sprinklers
Zone station
Sprinkler system design (no. of sprinkler, location, net work)
Special sprinkler systems :( dry, pre action, deluge)

2-1-2 cabinet systems: (class: I, II, III);


2-1-3 hydrant system;
2-1-4 Siamese connection;

2-2 gaseous suppression system


2-2-1 Weight of gas cylinder;
2-2-2 sequence of operation;

2-3 fire extinguisher


2-3-1 class;
2-3-2 material;
2-3-3 design;

3- Fire fighting tank


4- Fire fighting pumps

Note that:
All tables which
needed, putted on the
final pages

5- fire fittings
e.hosam2000@gmail.com

Page 2

Fire fighting course

Prepared by \ eng.hosam eldin samir

1- Fire science :
1-1 Fire safety

1-2 Fire alarm

:
fire rated wall
- fire , smoke,
temperature
: 30 min, 60min, 120min

escape staircase

*

inputs
controller
sensors
output
- types of sensors:
- smoke, heat , multi
detector
: FACP
Fire Alarm Control
Panel

1-3 Fire fighting


*
The Fire Triangle:
Three things must be
present at the same time to
produce fire:
1. Enough OXYGEN to sustain
combustion
2. Enough HEAT to reach ignition
temperature
3. Some FUEL or combustible
material

Together, they
produce the CHEMICAL
REACTION that is fire
Take away any of these
things and the fire will be
extinguished

NFPA:
National Fire Protection Association

e.hosam2000@gmail.com

Page 3

Fire fighting course

Prepared by \ eng.hosam eldin samir

2- Fire fighting systems:

2-1 water suppression system:


2-1-1 sprinkler system:
2-1-1-a) Types of sprinklers:
Firstly:
According to concept of work

1- Glass bulb type

2- Fusible link type

glass bulb
sprinkler body
mercury

fusible link
" "

Deflector :

e.hosam2000@gmail.com

Page 4

Fire fighting course

Prepared by \ eng.hosam eldin samir

Secondly:
According to direction of flow

1- Pendent

-direction of flow
down word
- fall ceiling is found
"
"

2- Upright

-direction of flow is up
word
- fall ceiling not found
" "
- fall ceiling is found:
When ceiling void >= 90 cm

"


" 90 =>

Pendent, upright, side wall

e.hosam2000@gmail.com

pendent, upright

3- side wall

-direction of flow is linear



pendent
& upright
:
"



"

side wall

Page 5

Fire fighting course

Prepared by \ eng.hosam eldin samir

2-1-1-b) Zone control station: ZCS


ZCS

ZCS

Main line
ZCS

Discharge line

cross main
ZCS

Suction line

branches
ZCS

Riser

FF
tank

Pump

. *
* Zone

control station: ZCS consists of the following components:

1) OS&Y gate valve: outside screw & yoke . (Normally open)


e.hosam2000@gmail.com

Page 6

Fire fighting course

Prepared by \ eng.hosam eldin samir

2) tamper switch:
OS&Y gate valve

Tamper switch

,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,

3) Flow switch:
fire switch
" " switch

,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,

4) Check valve: none return valve

e.hosam2000@gmail.com

Page 7

Fire fighting course

Prepared by \ eng.hosam eldin samir

5) Pressure gauge: 0.5: 12.1 bar

,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,

6) Pressure reducing valve: PRV


Where required

,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,

7) Test & drain valve: normally closed


test flushing

* must be the lowest point in the net work

e.hosam2000@gmail.com

Page 8

Fire fighting course

Prepared by \ eng.hosam eldin samir

Zone control station: ZCS

Beam

Test & drain

ZCS
External additional flushing connection

* must be the lowest point in the net work

e.hosam2000@gmail.com

Page 9

Fire fighting course

Prepared by \ eng.hosam eldin samir

2-1-1-C) Sprinkler system design:


a) No. of sprinkler & its location
Steps:
1- Determine the space hazard; depend on space occupants
: NFPA 1- Light hazard

e.hosam2000@gmail.com

2- Ordinary hazard

3- extra hazard

Page 10

Fire fighting course

Prepared by \ eng.hosam eldin samir

2- From NFPA tables ; according to hazard


We get four important notes which used in our design:
a) Maximum spacing between two sprinkler equal to (4.6 m)
b) Minimum spacing between two sprinkler equal to (1.8 m)
c) Maximum spacing between sprinkler & wall equal to (half of the
space between two sprinkler = (4.6\ 2) = (2.3 m)
d) Minimum spacing between sprinkler & wall equal to (4 = 10.2cm =
102mm)

3- Making distribution for sprinkler:

A) (length \ 4.6) =

B) (width \ 4.6) =

C) x, 2x ; y, 2y :

e.hosam2000@gmail.com

Page 11

Fire fighting course

Prepared by \ eng.hosam eldin samir

:
( ) m 5 * m 10 :

10


=3

= )A) (length \ 4.6


(10 \ 4.6) = 2.2

( )3
width :D


=2

= )B) (width \ 4.6


(5 \ 4.6) = 1.1

)2(

Page 12

e.hosam2000@gmail.com

Fire fighting course

Prepared by \ eng.hosam eldin samir

C) x, 2x ; y, 2y :
sprinkler :
2X X - :
Y

2X

2X

2Y

10 = X *
X = 1.6 m 6X = 10
5 = Y *
Y = 1.25m 4Y = 5
:

a) Maximum spacing between two sprinkler equal to (4.6 m)


b) Minimum spacing between two sprinkler equal to (1.8 m)
c) Maximum spacing between sprinkler & wall equal to (half of the
space between two sprinkler = (4.6\ 2) = (2.3 m)
d) Minimum spacing between sprinkler & wall equal to (4 = 10.2cm =
102mm)

e.hosam2000@gmail.com

Page 13

Prepared by \ eng.hosam eldin samir

Fire fighting course

:
-:

Page 14

e.hosam2000@gmail.com

Fire fighting course

Prepared by \ eng.hosam eldin samir

a) No. of sprinkler & its location


b) Net work sizing:
Steps:

1- Rooting:
( simple, symmetrical)

2- Sizing:
We get the sizing from pipe schedules which depend on (hazard, no.
of sprinkler)
Locke @ table (22.5.2.2.1 light hazard pipe schedule) , (22.5.3.4 ordinary hazard
pipe schedule) , (A.22.5.4 extra hazard pipe schedule) page 66 in this file.

:
22.5.2.2.1 Light hazard pipe schedule
Pipe sizing
1
1.25

No. of sprinkler
1, 2
3, 4

e.hosam2000@gmail.com

Page 15

Fire fighting course

Prepared by \ eng.hosam eldin samir

net work sizing


: light

Design net work


: sizing

e.hosam2000@gmail.com

Page 16

Fire fighting course

Prepared by \ eng.hosam eldin samir

: side wall sprinkler


Firstly lock @ table 8.7.2.2.1 page 67 for standard side wall sprinkler
Where:
S

4.25 =

3.75 =
:

Secondly lock @ table 8.9.2.2.1 page 67 for extended coverage side wall sprinkler
Where:
S

8.5 : 4.25 =>

" "3.75 =
,,,,,,,,,,,,,,,,,,,,,,,
8.5 S 8.5 ( .
)

e.hosam2000@gmail.com

Page 17

Fire fighting course

Prepared by \ eng.hosam eldin samir

2-1-1-D) Special sprinkler systems:


1- Wet pipe system

2- Dry pipe system

- Zone station valve is normally open. - Zone station valve is normally open
but after it we put clapper arm to
- Normal condition: 0: 74 C; 1 bar.
prevent the water from crossing.
- Single acting system
(
)

fire -

: clapper arm zone station




.



compressed water

compressed air

clapper arm

- Single acting system

e.hosam2000@gmail.com

Page 18

Prepared by \ eng.hosam eldin samir

4- Deluge system

Fire fighting course

3- Pre action system

- Zone station valve is normally closed. - Zone station valve is normally closed.


SPK
. zone valve
SPK
( )
- Single acting system

SPK Nozzle


- double acting system


:
1- Single knock:
2- Double knock:
( HD ) SD

Page 19

e.hosam2000@gmail.com

Fire fighting course

Prepared by \ eng.hosam eldin samir

2-1-2 cabinet systems: (class: I, II, III);


- Manual
- Inside the building
:

1- Class I
- it called civil defense
cabinet
- D = 2.5 inch
- design condition:
* 250 GPM
* Mini. Pressure 6.9 bar
* Max. pressure 12.1 bar
note that:
- When P>12.1 bar;
pressure reducing valve
must used PRV.

e.hosam2000@gmail.com

2- Class II
- normal users

3- Class III
- fire hose station
-

- D = 1 inch or 1.5 inch


- design condition:
* 100 GPM
* Mini. Pressure 4.5 bar
* Max. pressure 6.9 bar
note that:
- When P>6.9 bar;
pressure reducing valve
must used PRV.

- D = 1 inch and 2.5 inch


- design condition:
* 250 GPM
* Mini. Pressure 6.9 bar
* Max. pressure 12.1 bar
-note that:
- For 1 connection;
pressure reducing valve
must used PRV.
- For 2.5 connection;
some levels must have
PRV when P>12.1 bar.

Page 20

Fire fighting course

Prepared by \ eng.hosam eldin samir

- Design of cabinet system:


1- Travel distance:
* Standard length reel = 30 meter
Note that:
- 30 meter is a travel distance not across distance.
- Projector which composed on the reel spewing water through 6 meter

2- Guide location:
- Escape stair case
- Escape corridor
- @ car park in main inlet, main exit

,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
-: - Poly line: reel
- List properties L I enter:

e.hosam2000@gmail.com

Page 21

Fire fighting course

Prepared by \ eng.hosam eldin samir

2-1-2_ hydrant system:


- Infra net work
- Street fire hydrant
30

hydrant . 50 hydrant 2

- Location of hydrant: exposed

e.hosam2000@gmail.com

Page 22

Fire fighting course

Prepared by \ eng.hosam eldin samir

2-1-3 Siamese connection;


ZCS

ZCS

Main line
ZCS

Discharge line

cross main
ZCS

Suction line

branches
ZCS

FF
tank

N
Pump

Check valve

Siamese connection

" : . "
- Siamese connection:* supply the system with water.
* connected on the pump discharge.
* check valve must be used with it;
.

e.hosam2000@gmail.com

Page 23

Fire fighting course

Prepared by \ eng.hosam eldin samir

2.5 inch dry pipe Siamese : discharge

- Location of Siamese connection:


- exposed location
- note that; minimum 1 Siamese connection for the project.
<<<<<<<<<<<<<<<<<<<<<
:
.

e.hosam2000@gmail.com

Page 24

Fire fighting course

Prepared by \ eng.hosam eldin samir

Deluge system

e.hosam2000@gmail.com

Page 25

Fire fighting course

Prepared by \ eng.hosam eldin samir

3- Fire fighting tank design


3-1 tank capacity volume:

Volume = pump flow in GPM * required storage time in minute


Where:

- Pump flow

in GPM calculated

- required storage time


hazard

in minute depend on hazard

Light

required storage time in minute

30: 60 min

ordinary
60: 90 min

extra
90: 120 min

,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,

3-2 tank connections & construction:


Important notes:
a) Same tank fire fighting & plumbing
b) Divide the tank in to two 2 equal partition.

e.hosam2000@gmail.com

Page 26

Fire fighting course

Prepared by \ eng.hosam eldin samir

- Puddle flinch: -
puddle flinch -

,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,

Connection on tank
1234567-

Fire fighting suction pipe


Fire fighting test line
Filling lines
Over flow line
Drain line
Domestic suction pipe
Vent pipe

e.hosam2000@gmail.com

diameter

height

Fire fighting
Fire fighting
plumbing
plumbing
plumbing
plumbing
plumbing

25: 30 cm


cm "10 :5" +
Inside depression
Fire fighting storage hff = vff \ Atank
over flow

Page 27

Fire fighting course

Prepared by \ eng.hosam eldin samir

Vent pipe:

,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
- To avoid cavitations:
1- anti vortex plate 2D where D is suction pipe diameter.
2- The distance between anti vortex plate & depression = 6 inch=
150mm= 15cm.

- Other benefits of this distance are; turbulence , air bubbles

- Trench drain:
:
- Drainer pipe
- Over flow line
- Pump room water
plumbing

e.hosam2000@gmail.com

Page 28

Fire fighting course

e.hosam2000@gmail.com

Prepared by \ eng.hosam eldin samir

Page 29

Fire fighting course

Prepared by \ eng.hosam eldin samir

4- Fire fighting pumps


4-1 Fire fighting pumps:
1- Electrical
2- Stand by pump
pump
a) Diesel
b) electrical with
generator
It work when:
- Failure in elect. pump
- elect. Pump not enough for the
system demand.

3- Jockey pump

NFPA pressure main pump

stand by elect. jockey control panel -

e.hosam2000@gmail.com

Page 30

Fire fighting course

Prepared by \ eng.hosam eldin samir

4-2 hydraulic calculation:


. jockey stand by elect. -

:
1- cabinet system only

a) Class II

2- sprinkler system only

3- combined system

b) Class I,III

,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
4-2-1 cabinet system only:

a) Class II;
100 GPM; 4.5 bar: 6.9 bar

- flow calculation:
100 GPM class II -

- Head calculation:

Hp = Hst + Hres + Hf
Where:
- Hp

pump head

- Hst

static head

bar 10
- Hres

residual head bar 4.5 =

e.hosam2000@gmail.com

Page 31

Fire fighting course

- Hf

Prepared by \ eng.hosam eldin samir

friction head
hazen-williams formula -

Pl = hf= (4.52 * . ) \ (. * . )
Where:
-Q

the flow in GPM = 100

-C

friction loss coefficient = 120; from table 22.4.4.7 hazen-williams C values page 67

-D

diameter of the pipe; from table 5-7 pipe schedule page 68


distance of pipe in inch GPM D -

inch 1 class II inch 4 -

,,,,,,,,,,,,,,
Ex:

4, 100 GPM

FF
tank

Pump

2.5

2.5

2.5

25 ft

25 ft

25 ft

25 ft

100 GPM

100 GPM

100 GPM

100 GPM

68 5-7 sizing * . D GPM


D inch 1 class I inch 4 -

e.hosam2000@gmail.com

Page 32

Fire fighting course

Prepared by \ eng.hosam eldin samir

: sections " diameter flow "

5
4

4, 100 GPM

FF
tank

Pump

2.5

2.5

2.5

25 ft

25 ft

25 ft

25 ft

100 GPM

100 GPM

100 GPM

100 GPM

: sr
1
2
3
4
5

section
1-2
2-3
3-4
4-5

GPM D
hf
Lpipe
100
2
100 2.5
100
4
100
1

Where:

Pl = hf= (4.52 * . ) \ (. * . )

Leq

From

Ltotal

Hf

Lpipe + Leq

hf * Ltotal

Table 6.4.3.1
page 68

Hf 1.1 Hf head Hp

e.hosam2000@gmail.com

Page 33

Fire fighting course

Prepared by \ eng.hosam eldin samir

b) Class I ,III;
2.5 , 1 , 2.5
250 GPM; 6.9 bar: 12.1 bar

- flow calculation:
500 GPM = 2 Flow class III,I 250 GPM GPM 1250 Pump Flow .

1500 1250 Riser 5


.

250 GPM

250 GPM

FF
tank

Pump

e.hosam2000@gmail.com

1250 GPM

1250GPM

1000 GPM

750 GPM

500 GPM

Page 34

Fire fighting course

Prepared by \ eng.hosam eldin samir

- Head calculation:

Hp = Hst + Hres + Hf
Where:
- Hp

pump head

- Hst

static head

bar 10
- Hres
- Hf

residual head bar 6.9 =


friction head
hazen-williams formula -

Pl = hf= (4.52 * . ) \ (. * . )
Where:
-Q

the flow in GPM

-C

friction loss coefficient = 120; from table 22.4.4.7 hazen-williams C values page 67

-D

diameter of the pipe; from table 5-7 pipe schedule page 68


distance of pipe in inch GPM D -

inch 2.5 class I,III inch 4 -

,,,,,,,,,,,,,,

e.hosam2000@gmail.com

Page 35

Fire fighting course

Prepared by \ eng.hosam eldin samir

Ex:

2.5
250 GPM
250 GPM

4, 500 GPM
250 GPM
FF
tank

Pump

250 GPM

250 GPM

25 ft

25 ft

25 ft

25 ft

1250 GPM

1000 GPM

750 GPM

500 GPM

68 5-7 sizing * . D GPM


D inch 2.5 class I,III inch 4 -

: sections " diameter flow "


4

Ex:

2.5

3
1

250 GPM

250 GPM

4, 500 GPM
250 GPM
FF
tank

Pump

250 GPM

25 ft

25 ft

25 ft

25 ft

1250 GPM

e.hosam2000@gmail.com

250 GPM

1000 GPM

750 GPM

500 GPM

Page 36

Fire fighting course

Prepared by \ eng.hosam eldin samir

: sr
1
2
3
4
5
6
7

section
1-2
2-3
3-4
4-5
5-6
6-7

GPM D
hf
Lpipe
1250 6
1000 6
750
5
500
4
250
4
250 2.5

Where:

Pl = hf= (4.52 * Q^1.85) \ (C^1.85 * D^4.86)

Leq

From

Ltotal

Hf

Lpipe + Leq

hf * Ltotal

Table 6.4.3.1
page 68

Hf 1.1 Hf head Hp

e.hosam2000@gmail.com

Page 37

Fire fighting course

Prepared by \ eng.hosam eldin samir

4-2-2 Sprinkler system only:

Steps:
1- Most demand area:
" " NFPA demand

Hazard

Most demand Area


139 2 , 1500 ft 2
139 2 , 1500 ft 2
232 2 , 2500 ft 2

Light Hazard
Ordinary Hazard
Extra Hazard
,,,,,,,,,,,,,,,,,,,

2- Sprinkler density:
NFPA demand

Sprinkler density GPM\ 2

Hazard
Light Hazard
Ordinary Hazard
Extra Hazard

0.1
0.15: 0.2
0.3 : 0.4
,,,,,,,,,,,,,,,,,,,

3- K factor; flow & pressure:

Q = K
5.65 = KSP FM UL Factory
mutual

e.hosam2000@gmail.com

Under writer laboratories uniform listed



:D

Page 38

Fire fighting course

Prepared by \ eng.hosam eldin samir

Ex:
Required:
- make a complete design for the fire fighting pump which
serves a building; the most demand area is as shown.
Note that; the hazard is ordinary hazard.
NFPA

e.hosam2000@gmail.com

Page 39

Fire fighting course

Prepared by \ eng.hosam eldin samir

Where:
Sp1 , qsp1 , psp1 : -


,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,

: X -

Pl1

losses

Most demand area

139

,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,

Steps of the solution:


a) Location of most demand area
b)
c)
Most remote sprinkler
,,,,,,,,,,,,,,,,,,,,,,,,,,,
2

1- most demand area = 1500 ordinary hazard


2- from NFPA Chart = 0.15 GPM\ 2
3- Discharge of the most remote sprinkler:

1 = 1 *

Where:

Protection Area Limitations per Sprinkler

Protection Area Limitations per Sprinkler


Hazard
Light Hazard
Ordinary Hazard
Extra Hazard

Area ( )

Distance between sprinkler (m)

200
130
100

4.6
4.6
3.7

0.15 =

1 = 130 * 0.15 = 19.5 GPM = 1

e.hosam2000@gmail.com

Page 40

Fire fighting course

Prepared by \ eng.hosam eldin samir

4- Calculate the pressure @ the most remote sprinkler:

1 = K
Where

sprinkler K factor 5.65



19.5 = 5.65

1 = 11.9

Note that:
- The minimum residual pressure for any sprinkler is 7 psi = 0.5 bar.

5- Calculate the friction losses per unit of pipe from the most
remote sprinkler to the adjacent sprinkler by using hazenwilliam formula.

4.52 Q 1.85
C 1.85 D 4.87
Where:

Frictional losses per unit feet psi\ feet


Coefficient of friction for the pipe material = 120 black steel

Diameter on inch from table.


Flow on GPM
Apply this formula for

e.hosam2000@gmail.com

. ..

= .

Page 41

Fire fighting course

Prepared by \ eng.hosam eldin samir

6- Multiply friction losses per feet (

pl1

feet)* total length


(Pipe length + eq. length)

,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
7- Calculate the residual pressure on adjacent sp2

= 1 + 1 = 13.5 psi
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
8- Calculate the discharge @ this adjacent remote sprinkler

2 = k
2

= 5.65 13.5 = 20.7 psi

,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
9- Calculate the discharge in this pipe section

2 = 1 + 2
2 = 40.2 GPM
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
10-

3 9 8 7 6 5
:
2 \\ 3 = ( 2 +2 ) \\ 3 \\ 3

11-

4 9 8 7 6 5
:
3 \\ 4 = ( 3 +3 ) \\ 4 \\ 4

e.hosam2000@gmail.com

Page 42

Fire fighting course

Prepared by \ eng.hosam eldin samir

,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
demand area branch -

,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
Note that:

Sp5 will be ignored in the calculation as it isnt included in the most


demand area

,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,

4 =

12-

Multiply friction losses per feet (

4.52 Q 4 1.85
C 1.85 D 4.87

)* total length
(Pipe length + eq. length)

,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
SPK X - 13

= 4 + 4
= 4 = 3 + 4
14- Calculate K factor for the pipe

K=

=
e.hosam2000@gmail.com

Page 43

Fire fighting course

Prepared by \ eng.hosam eldin samir

4.52 Q 4 1.85

5 =

15-

Multiply friction losses per feet (

C 1.85 D 4.87

spk

)* total length
(Pipe length + eq. length)

,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
16-

py = px + pl5
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,

17-

5 =

,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,

18-

6 = 5 + 4
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
4.52 Q 6 1.85

6 =

19-

Multiply friction losses per feet (

C 1.85 D 4.87

)* total length
(Pipe length + eq. length)

,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
20-

pz = py + 6
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,

21-

7 =

e.hosam2000@gmail.com

Page 44

Fire fighting course

Prepared by \ eng.hosam eldin samir

,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
22-

8 = 7 + 6

e.hosam2000@gmail.com

:
Pump flow ##

Page 45

Fire fighting course

Prepared by \ eng.hosam eldin samir

- Head calculation:

Hp = Hst + Hres + Hf
Where:
- Hp

pump head

- Hst

static head
bar 10

- Hres
- Hf

residual head pz = demand area


friction head

Hf
demand area - 1
" diameter flow " section - 2

= 4 in
: sr
1
2

section

GPM

hf

Lpipe

Leq

Ltotal

Where:
Pl = hf= (4.52 * Q^1.85) \ (C^1.85 * D^4.86)

Hf

From

Lpipe + Leq

hf * Ltotal

Table 6.4.3.1
page 68

Hf 1.1 Hf head Hp

e.hosam2000@gmail.com

Page 46

Fire fighting course

Prepared by \ eng.hosam eldin samir

4-2-3 combined system:

Steps:
A) Calculate the flow for cabinet system only.
B) Add for this flow :
1- Light hazard
2- Ordinary hazard
3- Extra hazard
GPM 150 -

GPM 500 -

C) Head calculation:
- calculate head for cabinet
- calculate head for sprinkler
*** take the larger

cabinet head %75 -

Riser = 6 in combined system -

e.hosam2000@gmail.com

Page 47

Fire fighting course

Prepared by \ eng.hosam eldin samir

4-3 jockey pump calculation:


Head = + 1 bar
stand by elect. > jockey

Flowjockey = 5:20 GPM

Flowjockey = 1% system flow


,,,,,,,,,,,,,,,,,,,,,

Hp =
Horse power

e.hosam2000@gmail.com


3960
0 .65

Page 48

Fire fighting course

Prepared by \ eng.hosam eldin samir

4-4 pumps hock up:


1- Two(2) isolating valve OS&Y gate valve with tamper
switch ; jockey not need OS&Y
2- Check valve
3- Pressure gage
4- Flow meter
5- Eccentric reducer
6- Automatic air vent AAV
7- Two(2) flexible connection to prevent vibration
8- Floating floor spring cap, rubber pad
9- Flow switch ; jockey not need it
(6)

Pump

(1)

(8)

e.hosam2000@gmail.com

(7)

(3)

(2) (9)

(4)

(1)

Page 49

Fire fighting course

Prepared by \ eng.hosam eldin samir

For site engineer


5- Fire fighting fittings
5-1 Material takes off
1- Deign package

2- Construction

Design drawing
BOQ pumps, pipes
, spk, co2 or fm200 system,
cabinet
Specs specification

Cost estimation
Requesting order

Pipes fittings, hangar

,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,

5-2 Fittings:
123-

threaded fittings
weld fittings
grooved fittings

,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,

e.hosam2000@gmail.com

Page 50

Fire fighting course

Prepared by \ eng.hosam eldin samir

5-2-3 Grooved fittings:


: -

5-2-3-1 end grooved fittings


(Elbow, Tee, Reducer)

,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
5-2-3-2 coupling
:

a) rigid
coupling
b) flexible

" "

rigid flexible coupling % 10


coupling **
reducer coupling -

,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
5-2-3-3 mechanical Tee
:

a) one branch configuration (grooved or threaded)


b) cross branch (2grooved or 2threaded or grooved threaded)

e.hosam2000@gmail.com

Page 51

Fire fighting course

e.hosam2000@gmail.com

Prepared by \ eng.hosam eldin samir

Page 52

Fire fighting course

Prepared by \ eng.hosam eldin samir

Ex:
fittings

e.hosam2000@gmail.com

Page 53

Fire fighting course

Prepared by \ eng.hosam eldin samir

:
1- grooved Tee 4 * 2.5 * 4
2- two(2) rigid coupling 4
3- one(1) rigid coupling 2.5
4- grooved elbow 2.5
5- two(2) rigid coupling (RC) 2.5

reducer
1- grooved Tee 4 * 3 * 4
2- reducer 4 * 2.5
3- one(1) rigid coupling 2.5
4- one(1) rigid coupling 4
5- one(1) rigid coupling 3
6- grooved elbow 3
7- two(2) rigid coupling (RC) 3
Note that:
mechanical Tee
NFPA main mechanical Tee

e.hosam2000@gmail.com

Page 54

Fire fighting course

Prepared by \ eng.hosam eldin samir

,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
RN: riser nipple 10 = ~

,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,

e.hosam2000@gmail.com

Page 55

Fire fighting course

e.hosam2000@gmail.com

Prepared by \ eng.hosam eldin samir

Page 56

Fire fighting course

Prepared by \ eng.hosam eldin samir

Ex:

mechanical Tee
fittings

,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
Note that:
* Pipe schedule:
4 sch 40 40 "4

**

Schedule

pipe thickness

,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,

** groove
a) roll groove

b) cut groove
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
*** Diameters:

Pipe diameter

e.hosam2000@gmail.com

thickness

stress

Page 57

Fire fighting course

Prepared by \ eng.hosam eldin samir

Fittings:
1- Threaded
2- Weld
3- Grooved (roll groove or cut groove)
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,

From NFPA for fittings we get:


1- Threaded & cut groove

2- Weld & roll groove

Sch40 " 8 < D -

Sch10 " 5 D -

Sch30 " 8 > D -

NFPA "5 > D

For pipes: 1 , 114 " , 112 " , 2


threaded sch40
For pipes: 212 weld roll groove sch10

e.hosam2000@gmail.com

Page 58

Fire fighting course

Prepared by \ eng.hosam eldin samir


2-2 Fire extinguishers fire ext.
2-2-1 Type of fire ext. Class of fire
2-2-2 Location of fire ext.
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
2-2-1 Type of fire ext. Class of fire

Class A

Class B

Class C

Class D

Class K

Surface fire
:
Wood paper
clothes

Fire in
combustible
material in
liquid
material

Fire in
energized elect
Equipment

Fire in
combustible
material in
solid state

Fire in cooking
media

,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
2-2-2 Location of fire ext.

* Travel distance

30 m

** Guide location:
- escape stair case
- escape corridor

e.hosam2000@gmail.com

Page 59

Fire fighting course

Prepared by \ eng.hosam eldin samir

electro galvanized sheet *


:

Hot deep galvanized

Electro static

" "

,,,,,,,,,,,,,,,,,,,,,,,,,,,
** Type of fire ext. according to its shape:
Portable
" "

wheeled

automatic matic

Matic
Sprinkle
r

e.hosam2000@gmail.com

Page 60

Fire fighting course

Prepared by \ eng.hosam eldin samir

How to Use a Fire Extinguisher


Its easy to remember how to use a fire extinguisher if
you remember the acronym PASS:

Pull
Aim
Squeeze
Sweep
Aim

e.hosam2000@gmail.com

Page 61

Fire fighting course

Prepared by \ eng.hosam eldin samir

2-3 Gaseous system:


General note:
1- Gaseous system; Special system in case water system no applicable.
Such as:

Electrical room, severe room, IT room


Banks document rooms,
,,,,,,,,,,,,,,,,,,,,,,,,,,,,
2- Concept:
Inert gas 2 2 , 200

,,,,,,,,,,,,,,,,,,,,,,,,,,,,
3- design:
a) Weight of required gas. not volume
b) Sequence of operation.
..
A) Weight of required gas. not volume
It depends on:
- Volume of space
- Temperature of space
- Type of fire

e.hosam2000@gmail.com

Page 62

Fire fighting course

Prepared by \ eng.hosam eldin samir

Steps:
1- Calculate the volume of the space.
Volume = length * width * height

W=v*f

2-

Where:
W

required gas weight ( kg or lb )

volume of space

flooding factor

( 3 or 3 )

or 3 )

It passed on:
- Type of gas
- Type of fire
- Type of gas

By

table 1

, concentration factor

- Type of fire

C
By

table 2

F = 0.0341

Temp. Of space 70 , 22

e.hosam2000@gmail.com

Page 63

Fire fighting course

Prepared by \ eng.hosam eldin samir

Table 1:

Table 2:

e.hosam2000@gmail.com

Page 64

Fire fighting course

Prepared by \ eng.hosam eldin samir

b) Sequence of operation:

1- Detectors sends signal to FACP


2- Signal from FACP to motor in solenoid:a) Gives signal to output to alarm (fire strop)

) non manual stopping manual stopping (
.b non manual stopping

b) Sends signal to close the door


holder magnetic door

c) Sends signal to compressor



d) Sends signal to solenoid valve to start releasing the gas.

,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
* Standard weight for 2 is 45 kg
** For Fm200 no standard

e.hosam2000@gmail.com

Page 65

Fire fighting course

Prepared by \ eng.hosam eldin samir

weight
Plumbing Works Calculations

e.hosam2000@gmail.com

Page 66

Fire fighting course

e.hosam2000@gmail.com

Prepared by \ eng.hosam eldin samir

Page 67

Fire fighting course

e.hosam2000@gmail.com

Prepared by \ eng.hosam eldin samir

Page 68

Fire fighting course

e.hosam2000@gmail.com

Prepared by \ eng.hosam eldin samir

Page 69

Fire fighting course

e.hosam2000@gmail.com

Prepared by \ eng.hosam eldin samir

Page 70

Fire fighting course

Prepared by \ eng.hosam eldin samir

Fire alarm system


:
Inputs

Processing

outputs

1-Input:
1-1 automatic :
1-1-a) smoke detector (SD)
1-1-b) heat detector (HD)
1-1-c) gas detector (GD)
1-1-d) carbon monoxide detector (CD)
1-1-e) duct smoke detector (DS)
1-1-f) beam detector (S,R)

1-2 Manual:
- Manual pull station, break glass, call point

2-Data processing:
- FACP (fire alarm control panel)

3-Out put :
3-1 Bell
3-2 serine
3-3 horn
3-4 strobes light
3-5 flusher

e.hosam2000@gmail.com

Page 71

Fire fighting course

Prepared by \ eng.hosam eldin samir

1-Input:
1-1 automatic :

)1-1-a) smoke detector (SD


:
- 1 ionized smoke
detector .
- 2
optical detector
photo electric detector
,,,,,,,,,,,,,,,,,,,,,

average area

7.5 .,,,,,,,,,,,,,,,,,,,,,

: detector 7.5 detector


,,,,,,,,,,,,,,,,,,

detector ,,,,,,,,,,,,,,,,,,,

corridor 10 15 ( )7.5+7.5 over lap








10

Page 72

e.hosam2000@gmail.com

Fire fighting course

Prepared by \ eng.hosam eldin samir

)1-1-b) heat detector (HD


:
1- Fixed temp.

.

2- Rate of rise:
,,,,,,,,,,,,,,,,,,,,,,,,,

5 corridor 8 10 ) )5+5 over lap


,,,,,,,,,,,,,,,,,,,,,,,,,

)1-1-c) gas detector (GD


valves -

5,,,,,,,,,,,,,,,,,,,,,,,,,

)1-1-d) carbon monoxide detector (CD


fan fresh air exhaust .

5 8 10 ) )5+5 .over lap

Page 73

e.hosam2000@gmail.com

Fire fighting course

Prepared by \ eng.hosam eldin samir

1-1-e) duct smoke detector (DS)


supply duct
duct -

,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
1-1-f) beam detector (S,R)
receiver receiver transmitter sender . sender
100 50 R T .
. 7 T,R T,R -

IR

7m

e.hosam2000@gmail.com

7m

IR

Page 74

Fire fighting course

Prepared by \ eng.hosam eldin samir

flame detector **

) (
,,,,,,,,,,,,,,,,,,,,,,,
1-2 Manual:
- Manual pull station, break glass, call point
. 1.20 . 40 =

,,,,,,,,,,,,,,,,,,,,,,,
** wet area, stair, outdoors; not have alarm

,,,,,,,,,,,,,,,,,,,,,,,

e.hosam2000@gmail.com

Page 75

Fire fighting course

e.hosam2000@gmail.com

Prepared by \ eng.hosam eldin samir

Page 76

Fire fighting course

Prepared by \ eng.hosam eldin samir

2- Output:
3-1 Bell:
,,,,,,,,,,,,,,,,,,,,,,,
3-2 serine

90 db

60 db -

,,,,,,,,,,,,,,,,,,,,,,,
3-3 horn

120 db : outdoors

,,,,,,,,,,,,,,,,,,,,,,,
3-4 strobes light:
3-6 flusher :
2.20

manual input

,,,,,,,,,,,,,,,,,,,,,,,

3- Data processing:
- FACP (fire alarm control panel)

: FACP (Monitor, PCB, Battery)

- Monitor:
- PCB: electronic devices
fire alarm - Battery

e.hosam2000@gmail.com

Page 77

Fire fighting course

Prepared by \ eng.hosam eldin samir

controller :
- Conventional type:
50

zones zone zone .

Page 78

e.hosam2000@gmail.com

Fire fighting course

Prepared by \ eng.hosam eldin samir

- addressable type :

monitor address address
micro processor

. closed loop addressable

closed loop . micro processor

e.hosam2000@gmail.com

Page 79

Fire fighting course

Prepared by \ eng.hosam eldin samir

:
branch : loop element 100 : loop ) 24 20 16 12 8 4 2 1 ( loops element : riser diagram fault isolator element 15 riser diagram *
. element riser diagram element

S: smoke detector
H: heat detector
FS: flow switch
TS: tamper switch "
G: generator
TR,RC: Beam detector
L: elevator
DS: duct smoke detector

Note that:
- Fire alarm system

DC 24 Volt

- Fire alarm electrical cable is red & black


- Fire alarm electrical cable is fire resistant cable for 3hr, it 2 * 2.52 , shielded

e.hosam2000@gmail.com

Page 80

Fire fighting course

Prepared by \ eng.hosam eldin samir

***Shop drawing***
Fire fighting drawings
1- Design drawing
2- Shop drawing

- level
- dimensions
- supports
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
1- Design drawing
* Steps:
: -1
* Delete for any not required data
color 8 **
one block ***
**** Closed layer
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,

: - 2
* Main fire fighting network from FF tank & FF pump room
. Fire

,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,

3- For each level:


*Sprinkler design
Single line net work SPK

** Cabinet system design

LI

Enter
: one block ***
enter block

e.hosam2000@gmail.com

Page 81

Fire fighting course

Prepared by \ eng.hosam eldin samir

Design drawing SPK : cad


**
- 1
- 2 CadLinear Dimension
- 3 4.6
- 4 .
- 5 * 2 X
Cad Diversion DivEnter
- 6
- 7Select object
- 8
- 9 XEnter
- 10

- 11

- 12

- 13

move

Spk
- 14

- 15

div

- 16

main

Page 82

e.hosam2000@gmail.com

Fire fighting course

Prepared by \ eng.hosam eldin samir

2- Shop drawing
double single line - 1
Dimensions - 2

Walls, columns, Axes

"Pipe Levels - 3

*
** Level depend on:
- F.C.H+ 75mm
- Main pipe = F.C.H+ 100mm
- Branch pipe =main + 100mm

Support -4
:Material takes off -5

Lock @:
- Shop drawing LC 306
- Shop drawing, Fire Fitting, fitting, 01

e.hosam2000@gmail.com

Page 83