Rev.A
Data Sheet
No part of this publication may be reproduced by whatever means without the prior written permission of Ingeteam Power
Technology.
One of the main aims of Ingeteam Power Technology lies in the continuous improvement of the companys equipment and,
therefore, the information contained in this catalogue may be modified without prior notification.
For further information, consult the corresponding manual or contact us directly.
Table of contents
Table of contents
Model Code Selection ....................................................................................................... 7
Functions table and functional diagrams ...................................................................... 9
Communication ................................................................................................................11
Protection functions ........................................................................................................11
Differential protection ............................................................................................................................................ 11
Percentage differential protection ................................................................................................................ 12
Second harmonics restraining ...................................................................................................................... 12
Second harmonics blocking .......................................................................................................................... 12
Cross blocking .................................................................................................................................................. 12
Instantaneous differential protection ........................................................................................................... 12
CT error detection............................................................................................................................................. 12
Saturation detector........................................................................................................................................... 12
Load compensation ......................................................................................................................................... 12
87N Restricted ground differential................................................................................................................ 12
Directional supervision ................................................................................................................................... 12
Over-excitation by 5th harmonic................................................................................................................... 12
Over-excitation v/f ............................................................................................................................................ 12
Function 86 ........................................................................................................................................................ 13
Distance units.......................................................................................................................................................... 13
Zone 1 extension .............................................................................................................................................. 14
Zone of quick operation .................................................................................................................................. 14
Overcurrent monitoring .................................................................................................................................. 14
Phase identification.......................................................................................................................................... 14
Fault detector..................................................................................................................................................... 14
Directional monitoring ..................................................................................................................................... 14
Lines with CVT .................................................................................................................................................. 14
Fuse failure 68 FF ............................................................................................................................................. 14
Load zone encroachment 68 ZC ................................................................................................................... 14
Power swing (Out of step) .............................................................................................................................. 14
Ingeteam Power Technology, S.A. 2012 All rights reserved.
Rev. A
Table of contents
Locator ...............................................................................................................................20
Monitoring functions .......................................................................................................20
CT monitoring.................................................................................................................................................... 20
Power supply monitoring ............................................................................................................................... 20
External power supply monitoring ............................................................................................................... 20
Ingeteam Power Technology, S.A. 2012 All rights reserved.
Rev. A
Table of contents
Logics .................................................................................................................................22
Logical functions based on IEC 61131-3..................................................................................................... 22
Communication protocols..............................................................................................23
Parallel Redundancy Protocol (PRP) ........................................................................................................... 23
Link failover redundancy ................................................................................................................................ 23
High-availability Seamless Redundancy (HSR)......................................................................................... 23
Rev. A
Table of contents
Rev. A
INGEPAC EF LD MODEL
INGEPAC EF-
I/O 8
I/O 7
I/O 6
I/O 5
I/O 4
I/O 3
I/O 2
ETH2
ETH1
COM6
COM5
COM4
COM3
COM2
COM1
I/O 1
MODEL
87, 87N, 5th armonic and V/f overexcitation, SOTF, 68FF, 67, 67N, 50/51, 50N/51N,
50G/51G, 67Q, 46FA, 37, 49, 25, 79, 74TC/CC, 50BF, Stub bus, Fault locator
87, 87N, 5th armonic and V/f overexcitation, 21,POTT (21),POTT (67N/67Q),
SOTF, 68LE,68FF,78, 67, 67N, 50/51, 50N/51N, 50G/51G, 67Q, 46FA, 37, 49, 59,
27, 59N, 47, 81M/m, 81R, 32, 25, 79, 74TC/CC, 50BF, Stub bus, Fault locator
A
B
A
B
C
D
Note 1
Note 1
A
B
C
D
F
G
COM-1
COM-2
COM-3 (Note 9)
COM-4 (Note 10)
COM-5
COM-6
ETH-1
ETH-2
A
B
C
Note 2
(Note 3)
Board
Board
Board
Board
Board
Board
2 (Note
3
4 (Note
5 (Note
6 (Note
7 (Note
4)
5)
5)
5)
5)
Pag. 7
The following figures show the board position acording to model encoding.
Fig. 1.1
Fig. 1.3
19 chassis
Fig. 1.2
Fig. 1.4
19 chassis
Pag. 8
LD1
V/f Overexcitation
Directional supervisin
CT error detector
Saturation detector
Load compensation
86 function
Differential functions
Distance functions
Quadrilateral (5 areas)
MHO (5 areas)
21 High Speed
Zone 1 extension
Double lines
27 Undervoltage
59 Overvoltage
47 V2 overvoltage
50N/51N (67N)
37 Undercurrent
49 Thermal image
32 Power units
Stub bus
Teleprotection
Teleprotection (21)
Teleprotection (67/67Q)
Monitoring units
78 Power swing
Fault locator
Pole discordance
Fault locator
Breaker monitoring
Pag. 9
LD0
LD1
Synchronism
Coupling
Breaker monitoring
Oscillographs
Historical reports
Automatism
Tbl. 1.1
Fig. 1.5
General diagram
T7 Free
T2 IB Phase B current
T3 IC Phase C current
T9 VN Neutral voltage
T4 IN Neutral current
T6 Free
Fig. 1.6
Pag. 10
Communication
Protection functions
Communication
The line differential scheme is based on the data exchange
(measurement and signal) between the devices placed on the
sides of the line. It allows two and three terminal lines.
It allows line with intermediate transformer.
The communication uses the serial channels with baud rates
between 64kbits and 128kbits and port types RS232 and FO
multimode and singlemode (up to 60km). With external
converters it can be used in G703 nets.
In 2 ends configuration for simple communication the port
Com-3 is used and for redundant Com-3 and Com-4 ports. In
3 ends configuration Com-3 and Com-4 ports are used.
The communication can be:
Differential protection
TRIP
Ib
Ib
Ic
Ic
Ic
TRIP
Ib
Master/Master
Setting
Minimum
Maximum
Step
Scheme type
2 / 3 ends
Reference end
A/B/C
10000
0,1
10000
0,1
10000
0,1
End A CT ratio
10000
0,1
End B CT ratio
10000
0,1
End C CT ratio
10000
0,1
1A / 5A
1A / 5A
1A / 5A
Intermediate transformer
NO / SI
Y/D/Z
Y/D/Z
Y/D/Z
11
11
11
NO / SI
NO / SI
NO / SI
5000
0,1
0,1
20
0,01
Ia
Fig. 1.7
Fig. 1.8
Master/Slave
Minimum
Maximum
Step
0,1
20
0,01
Conecction type
Master / Slave
0,1
20
0,01
Port 1
End A polarity
Incoming / Outgoing
64Kb / 128Kb
End B polarity
Incoming / Outgoing
Remote end 1
A/B/C
End C polarity
Incoming / Outgoing
Remote ID 1
I0 type:measure/calculated
Measured / Calculated
Port 2
1A / 5A
64Kb / 128Kb
Remote end 2
A/B/C
Neutral CT ratio
10000
0,1
Remote ID 2
1A / 5A
250
10
Ground CT ratio
10000
0,1
Allow 21 Backup
Local end
A/B/C
Allow 67 Backup
Local ID
Pag. 11
Protection functions
CT error detection
Saturation detector
Detection of saturation in any of the current transformer. It
analyses each phase independently to detect the instant
when the saturation happens.
Load compensation
Fig. 1.9
Setting
Minimum
Maximum
Enabled
Step
Yes/ NO
Sensitivity (xTap)
0,15
0,01
0,01
20
0,01
Slope 1 (%)
100
Slope 2 (%)
200
60000
Mnimo
Mximo
Paso
Enabled
Minimun threshold
0,08
20
0,01
10
1000
10
Minimum
Maximum
Step
Enabled
NO/Yes
10
100
0,15
0,01
Minimum
Maximum
Step
Enabled
NO/Yes
10
100
0,15
0,01
Cross blocking
Tripping of the three phases can be blocked when there is a
high percentage of harmonics in any of the phases. This
general block is only permitted during an adjustable time
period.
Setting
Minimum
Maximum
Step
Enabled
NO / OR / Two of three
5000
10
Minimum
Maximum
Pickup (xTap)
20
0,01
60000
Enabled
Step
Minimum
Maximum
Sensitivity (A)
0,05
20
0,01
Slope (%)
0%
100%
1%
600000
10
Enabled
Step
Yes/ NO
Directional supervision
It detects if the fault is internal or external. In external faults, it
changes the characteristics and delays the trip.
Setting
Minimum
Maximum
0,02
25
0,01
45
90
Enabled
Step
Yes/ NO
Minimum
Maximum
0,1
10
0,01
100
600000
10
Enabled
Step
Yes/ NO
Over-excitation v/f
This feature prevents the transformers operate at a flux
density greater than that for which they were designed,
avoiding overheating and consequent damage to the
transformer that would arise before an overdrive. Can be
detected by the 5th harmonic intensity or by the V/f relation.
Yes /NO
Pag. 12
Protection functions
Setting
Minimum
Maximum
Step
Enabled
Yes/ NO
Operation type
Vph-gnd FUND
Vph-ph FUND
Vph-gnd RMS
Vph-ph RMS
Standard
0,8
40
0,01
50
99
50
150
Mho characteristic
Quadrilateral characteristic
0,05
30
600000
Reset type
10
Instantaneous / Timed
Function 86
This consists in activating the programmed relays when a
differential trip occurs (instantaneous or percentage) or in
activating a signal to be used to block the circuit breaker
closing circuits.
Setting
Minimum
Maximum
Step
Enabled
NO / Yes
Logical input
Activate Trip 86
Logical input
Distance units
Setting
Minimum
Maximum
Non-directional
Forward
Following trip
Following pickup
Directional Mode
Characteristic Angle ()
Step
90
NO / YES
Mho
Quadrilateral
Mho and quadrilateral
600,000
10
0.05
500
0.01
0.05
500
0.01
X Reach Forward(Ph)
0.05
500
0.01
An analysis is carried out for each phase (AN, BN, CN, AB,
BC, CA), characteristic (Quadrilateral and Mho) and zone of
operation (5 areas).
0.05
500
0.01
R Blinder Angle(Ph)
90
Enabled (Gnd)
NO / YES
Mho
Quadrilateral
Mho and quadrilateral
600,000
10
Kn Module
0.5
10
0.01
Kn Angle ()
90
Km Module
0.5
10
0.01
Km Angle()
90
0.05
500
0.01
0.05
500
0.01
X Reach Forward(Gnd)
0.05
500
0.01
0.05
500
0.01
R Blinder Angle(Gnd)
90
-10
10
1
Disabled
Timing
Continuous
500
10
I0
I2
Max (I0, I2)
Pag. 13
Protection functions
Zone 1 extension
Setting
Minimum
Maximum
0.1
0.001
0.1
0.001
Enabled
Step
NO / YES
Options
Zone 1 enabled
NO / YES
Zone 4 enabled
NO / YES
Logical input
Logical input
Setting
Remarks
Enabled
NO / YES
CVT type
Pasive / Active
Fuse failure 68 FF
It detects if a fuse has blown up in the secondary circuit of the
voltage transformers. While this situation is detected, the
blocking of the operation of other protection functions is
allowed.
Setting
Overcurrent monitoring
10000
Step
Step
Maximum
NO / YES
Setting
0.05
150
0.01
Enabled
0.05
150
0.01
0.05
150
0.05
150
Minimum
Maximum
0.05
25
0.01
0.01
Z forward (Ohm)
0.01
500
0.01
0.01
90
270
359
Z reverse (Ohm)
0.01
500
0.01
90
180
180
270
Maximum
Forward threshold
0.05
150
0.01
Reverse threshold
0.05
150
0.01
Enabled
10
Minimum
Enabled
Setting
Maximum
YES / NO
Setting
Minimum
Enabled
Step
NO / YES
Step
NO / YES
Fault detector
This function detects the beginning of a fault, checking the
differences among the zero-sequence, direct and inverse
sequences measurements of the present current and the
ones of the two previous cycles.
Directional monitoring
It monitors the direction of a fault, so that it only permits the
faults produced in the direction set for each area.
Setting
Minimum
Maximum
Step
Ph-Ph angle ()
359
Ph-Ph amplitude ()
90
170
Gnd angle ()
359
Gnd amplitude ()
90
170
Pag. 14
Protection functions
Setting
Min
Max
Step
Enabled
NO / YES
Memory Enabled
NO / YES
Setting
Minimum
Maximum
Step
Step trip
Permissive overreaching
Permissive underreaching
Direct. comparison blocking
Direct. comparison unblock
Scheme type
Zone 1 Blocking
NO / YES
NO / YES
1000
10
Teleprotection Blocking
NO / YES
1000
10
0.05
500
0.01
150
10
0.05
500
0.01
200
10
Middlezone Top X
0.05
500
0.01
200
10
0.05
500
0.01
ECHO enabled
0.05
500
0.01
10000
10
0.05
500
0.01
1000
10
0.05
500
0.01
200
10
Slope angle
0.05
500
0.01
0.1
0.1
10000
100
NO
IN_ZMED
OUT_ZMED
0,1
200
Trip Enabled
Trip Time (ms)
100
60
10000
I2 threshold (A)
Trip delay
100
1000
1000
NO / YES
NO / YES
10
NO / YES
0,1
Logical input
Logical input
GSLRx_67 line 1
Logical input
GSLRx_67 line 2
Logical input
TP Trip Block
Logical input
Logical input
Logical input
Block ECHO
Logical input
Logical input
Logical input
0.01
5
5
1000
Minimum
Maximum
Step
Enabled
NO / YES
Operation type:
Programmable
V&I
Z2 or (V&I)
Z2
YES / NO
YES / NO
0.01
200.0
0.01
100
1000
10
Current units
Directional
There are directional units per phases, inverse sequence and
neutral.
Each of the overcurrent units can be set in directional mode
with the "Torque control" setting. If it is FORWARD or
REVERSE, it indicates that the function works as directional
(in one sense or the other) and if it is NO, then it works as
NON-DIRECTIONAL.
Phase directional
Trip schemes
Setting
Directional method
Step trip
Permissive overreach
Permissive underreach
Directional blocking
Directional unblocking
Minimum
Maximum
Step
Quadrature
Quadrature 2 of 3
Direct sequence
Inverse and direct sequence
Torque angle ()
359
200
0.1
Zone amplitude ()
90
170
YES / NO
67 directional Inversion
Logical input
Logical input
Minimum
Maximum
Step
Torque angle ()
359
Zone amplitude ()
90
170
200
0.1
Z2 offset
100
Minimum I2 / I1 Ph (%)
100
100
S2 Directional inversion
Logical input
Blocking input
Logical input
Pag. 15
Protection functions
Neutral directional
Setting
Minimum
Maximum
Step
"Angular criteria"
Icos
Isen
Watt-metric
Torque angle()
359
Zone amplitude ()
90
170
200
0.1
100
V
IPOL
IPOL V
IPOL o V
IPOL o V
Setting
Polarization method
S0
S2
S2 y S0
S2 y S0
S2 S0
S0 S2
Automatic
Offset Z0 (Ohm)
100
100
YES / NO
100
100
0.01
100
Logical input
100
Minimum
Maximum
YES / NO
Operation type:
TRIP
PICK UP
0.02
150.0
0.01
600,000*
10
Torque control
NO
Forward
Reverse
Nothing
Inhibit
Block
Enable
Operating Quantity
Phasor
Rms
Logical input
Logical input
Setting
Minimum
Maximum
Step
NO / YES
Operation type:
ALWAYS
YES WITH 52
100
0.1
7,200,000
10
200
0.1
20
0.1
Minimum
Maximum
Step
Enabled
YES / NO
Operation type:
TRIP
PICK UP
IOC1 BLOCK
IOC1, 2 BLOCK
IOC1, 2, 3 BLOCK
0.02
150.0
0.01
Extreme ANSI-EI. Inverse
ANSI-MI Very inverse
Normal inverse
ANSI-MODI Moderately inverse
IEC-I Normal inverse
IEC-MI Very inverse
IEC-EI Extreme. Inverse
IEC-IC Short inverse
IEC-IL Long inverse
IEC-MIEs Very inverse special
User curves 1
User curves 2
User curves 3
User curves 4
Definite time
Curve type
Time dial
0.05
30.0
0.01
600,000*
10
Torque control
Reset type
NO
Forward
Reverse
Remarks
Enabled
Setting
Step
Enabled
Minimum
Maximum
Step
NO / YES
Only in closure
Enabled
I2nd harm. / Ifund. threshold (%)
10
100
0.1
150.0
0.01
Mnimo
Mximo
100
100
0,1
150
0,01
Enabled
Paso
NO/YES
NO/YES
Nothing
Inhibit
Block
Enable
NO/YES
NO/ YES
NO/ YES
Instantaneous
Timed
NO/ YES
NO/ YES
Operating Quantity
Phasor
Rms
Logical input
Pag. 16
Protection functions
Timed
Thermal image 49
Setting
Minimum
Maximum
Heating constant
30
18,000
Cooling constant
30
18,000
50
100
50
95
0.1
150.0
0.01
Enabled
Minimum
Maximum
NO / YES
Operation type:
Standard
Vphase-earth FUND
Vphase-phase FUND
Vphase-earth RMS
Vphase-phase RMS
Step
NO / YES
0.5
200
0.01
Extreme ANSI-EI. Inverse
ANSI-MI Very inverse
Normal inverse
ANSI-MODI Moderately inverse
IEC-I Normal inverse
IEC-MI Very inverse
IEC-EI Extreme. Inverse
IEC-IC Short inverse
IEC-IL Long inverse
IEC-MIEs Very inverse special
User curves 1
User curves 2
User curves 3
User curves 4
Definite time
Undercurrent 37
This unit protects from current losses in the power supply,
preventing the no-load operation of the engines. The
equipment has 2 independently programmable units.
Setting
Minimum
Maximum
Step
Enabled
NO / YES
Operation type:
Threshold (A)
0.02
10
0.01
600,000
10
Minimum
Maximum
Enabled
Step
NO / YES
0.02
200
0.01
600,000
10
0.02
200
0,001
600,000
10
Voltage units
Time dial
0.05
30.0
0.01
7,200,000
10
Instantaneous
Setting
Minimum
Maximum
Step
Enabled
NO / YES
Operation type:
Standard
Vphase-earth FUND
Vphase-phase FUND
Vphase-earth RMS
Vphase-phase RMS
0.5
200
0.01
7,200,000
10
Minimum
Maximum
Step
50
99
101
110
50
99
50
99
Step
Enabled
Calculated/
Measurement
Setting
Minimum
Maximum
0.5
200
Enabled
Start value (V)
NO / YES
0.01
Extreme ANSI-EI. Inverse
ANSI-MI Very inverse
Normal inverse
ANSI-MODI Moderately inverse
IEC-I Normal inverse
IEC-MI Very inverse
IEC-EI Extreme. Inverse
IEC-IC Short inverse
IEC-IL Long inverse
IEC-MIEs Very inverse special
User curves 1
User curves 2
User curves 3
User curves 4
Definite time
Overvoltage 59
The overvoltage function acts whenever there is a voltage
increase. The equipment has 1 timed unit and 2
independently
programmable
units.
Step
Time dial
0.05
30.0
0.01
7200000
10
Instantaneous
Setting
Minimum
Maximum
0.5
200
0.01
7200000
10
Enabled
Step
NO / YES
Pag. 17
Protection functions
Maximum
0.5
200
Enabled
Start value (V)
Time dial
Delay time (ms)
0.05
0
30.0
Step
NO / YES
Setting
Minimum
Maximum
Step
0.01
40
200
15
10
600,000
10
600,000
10
45
65
0.01
600,000
10
0.01
7200000
Timed
Setting
Frequency units
10
Step 1. Enabled
YES / NO
Maximum/Minimum
YES / NO
45
65
0.01
600,000
10
Maximum/Minimum
Instantaneous
Setting
Minimum
Maximum
0.5
200
0.01
7200000
10
Enabled
Step
NO / YES
Undervoltage 27
It detects voltage drops in any phase. The equipment has 1
timed unit and 2 independent instantaneous units.
Setting
Minimum
Maximum
Step
Enabled
YES / NO
Step
Operation Type
Negative
Positive
Negative
positive
Enabled
NO / YES
100.0
0.1
15
10
Operation type:
Standard
Vphase-earth FUND
Vphase-phase FUND
Vphase-earth RMS
Vphase-phase RMS
7,200,000
10
40
70
0.01
0.01
0.20
0.05
2,000
10
40
70
0.01
0.20
0.05
2,000
10
Timed
Setting
Minimum
0.5
Maximum
200
Time dial
0.05
30.0
0.01
7200000
10
Minimum
Maximum
Instantaneous
Setting
and
Step
Enabled
NO / YES
Operation type:
Standard
Vphase-earth FUND
Vphase-phase FUND
Vphase-earth RMS
Vphase-phase RMS
0.5
200
0.01
7200000
10
Pag. 18
Automatic functions
Automatic functions
Recloser 79
Setting
Minimum
Maximum
Step
1.0
200.0
0.1
60000
10
Enabled
YES / NO
Setting
Setting
Minimum
Maximum
Step
0.1
0.1
0.1
0.1
0.1
0.1
Breaker units
Open pole detection
It detects whether one of the poles is open. It is used in other
functions, as an input value, that determinates the status of
the poles.
Setting
Minimum
Maximum
Step
Minimum
Maximum
Step
Enabled
YES / NO
Reclose mode
1 POLE
3 POLES
1P/3P
DEPENDENT
Reclose number
0.05
600
0.01
600
600
600
0.05
600
0.01
600
600
600
600
Incomplete sequence
YES / NO
Logical input
Logical input
Logical input
Logical input
Pause input
Logical input
Logical input
Configurable autoreclose
Logical input
Logical input
Breaker failure 50 BF
Logical input
Vref supervision
Enabled
NO / YES
V&I
I&52
V&I&52
V&I or 52
Operation type:
10.0
165.0
0.01
0.1
0.5
0.01
YES / NO
Setting
Parameter
Minimum
Maximum
Minimum
Maximum
0.05
600
0.01
0.05
600
0.01
Step
Enabled
Enabled
NO / YES
Start type
External trips
Internal trips
Both
Operation type
Three-pole
Single-pole
Sealed by current
NO / YES
120000
Supervision by current
1
NO / YES
0.02
150
0.01
0.02
150
0.01
60000
0.5
60000
0.5
Step
YES / NO
Logical input
Synchrocheck Supervision
Setting
Minimum
Maximum
Step
Synchrocheck type:
Internal
External
YES / NO
YES / NO
0.05
600
0.01
Logical input
Pag. 19
Locator
Synchronism 25
Locator
The
synchronism
checking
function,
also
called
"synchrocheck", is used in order to set conditions for the
closure of the breaker.
The function compares the voltage signals of a phase (in
module and angle) of the two sides of the breaker, giving
permission to close the breaker when the set conditions are
met. It can be used for both manual and automatic closure.
Maximum
0.1
5,000
0.1
0.01
300
0.01
Step
Z1 angle ()
359.9
0.1
Enabled
NO / YES
Z0 Imp.(Ohm p.u.length)
0.01
300
0.01
Z0 angle ()
359.9
0.1
A /AB
B /BC
C /CA
Y1(1/ohm p.u.length)*10e-9
50,000
0.1
Y0(1/Ohm p.u.length)*10e-9
50,000
0.1
0.01
300
0.01
359.9
0.1
0.01
300
0.01
359.9
0.1
0.01
300
0.01
359.9
0.1
0.01
300
0.01
359.9
0.1
NO
Without compensation
With compensation 0
With compensation
200
0.1
200
0.1
200
0.1
7,200
Setting
Minimum
Maximum
0.1
0.01
330
30
10
200
0.1
10
200
0.1
Closing time
100,000
10
NO
Without compensation
With compensation 0
With compensation
Description
Enabled
Step
YES / NO
90
0.1
0.01
0.01
Angle difference ()
360
Line type
Sync.Time Man.closing(ms)
100,000
10
0.01
300
0.01
100,000
10
359.9
0.1
10
200
0.1
Filter enabled
10
200
0.1
200
Without permission
A not and B yes
A yes and B not
A not and B not
A not or B not
A xor B
Autoreclose condition
Without permission
A not and B yes
A yes and B not
A not and B not
A not or B not
A xor B
YES / NO
1
Simple / Double
YES / NO
0.1
Monitoring functions
CT monitoring
It allows the detection of a fault in any of the relay's input
channels (adaptation transformer + internal wiring),
comparing the absolute value of three times the zerozequence current 3I0 (calculated on the basis of the phase
currents) with the current measured in the neutral
transformer, taking into account the phase and neutral
transformation ratio. None of the phases should surpass 1.5
times the rated current.
Setting
Options
Enabled
YES / NO
Pag. 20
General configuration
Setting
Minimum
Maximum
10
280
10
280
Enabled
Step
YES / NO
General configuration
Temperature monitoring
Setting
Options
Language
Spanish / English
Setting
Step
NO / YES
YES / NO
NO / YES
Minimum
Maximum
Enabled
Minimum temperature (C)
-40
NO / YES
50
100
Leds Blocking
NO / YES
NO / YES
IRIG-B format
Local/remote selection
Logical input
Erase records
Logical input
Breaker monitoring
It checks different parameters to detect anomalies in the
breaker.
Excessive number of trips: It checks whether the number of
trips is superior to what was programmed in a programmed
time. With the closure, a new period of time begins.
NO / YES
Remote/Local Type
Flicker Enable
NO / YES
Options
Relay ON
NO / YES
Phase order
ABC / ACB
Logical input
Logical input
Logical input
Logical input
Logical input
Logical input
Secondary / Primary
Minimum
Maximum
Step
KI2
KI
KI2t
100
10
100,000
100,000
60
500
VT Characteristics
Setting
Minimum
Maximum
Operating Voltages
Mechanical opening T (ms)
5,000
5,000
Phase selection
Frequency
Ground voltage ratio (VN)
Electrical opening T (ms)
5,000
5,000
10,000
1,000
1,000
Step
50Hz/60Hz
1
10,000
0.1
Minimum
Maximum
Change P sign
Step
YES / NO
Change Q sign
YES / NO
1,000
1,000
Pag. 21
Logics
Logics
Oscillography
Logical functions based on IEC 61131-3
Statistics
Protection logics:
Breaker information:
Reclosure counter
Events
It records up to 1,000 events with the following info:
Historical reports
Event description
Maximum
voltages
Faults
It stores up to 20 faults with the description of the fault:
and
minimum
average
phase-to-earth
Measurements
Depending on the model, the measurements below are
available:
Distance to fault.
Frequency (Hz)
Tripped phases.
Pag. 22
Communication protocols
Internal battery
Equipment temperature ( C)
Communication protocols
Front Ethernet port (RJ45)
61850 protocol
Sincronization
GOOSE subscription
SNTP/NTP synchronisation.
FTP/WEB access
Pag. 23
Technical specifications
Technical specifications
Auxiliary power supply
110-125-220 Vcc
DC operating range
85 300 Vcc
AC operating range
85 265 Vca
Burden
24-48 Vcc
DC operating range
18 60 Vcc
Burden
Current circuits
Phases/neutral/polarisation current thermal capacity (Unified Rated Current 1/5A)
Measurement range
0.02 A to 200 A
Permanent
20 A
Thermal current 10 s.
50 A
Short duration
500 A
1,250 A
Burdens at In= 5 A
<0.2 VA
Burdens at In= 1A
<0.02 VA
Voltage circuits
Thermal capacity
Measurement range
1 to 200 Vac
Rated voltages
Thermal capacity
Permanent
250 Vca
Short duration
Burden at 63.5 V
<0.015 VA
Burdens at 100 VA
<0.03 VA
7.62 mm (staggered)
85 350 Vcc
Accuracy
2 % FS
Mechanical Features:
19 chassis and 5 U models approximate weight (without I/O modules)
3,5 kg.
4,9 kg.
0,4 kg.
Front IP
IP30
Optional Front IP
IP54
Pag. 24
Technical specifications
Environmental conditions
Operating temperature
-40 to +60 C
Storage temperature
-40 to +85 C
Relative humidity
Tests
Climatic test
Standard
Cold
IEC -60068-2-1
-40C, 16 hours
Dry Heat
IEC -60068-2-2
+85C, 16 hours
IEC -60068-2-78
+40C/93%RH, 96 hours
IEC -60068-2-30
IEC -60068-2-14
IEC60529
IP30
Electromagnetic test
Standard
IEC 60255-22-1
2.5kV MC
2.5kV MD
IEC 61000-4-18
2.5kV MC
2.5kV MD
IEC 61000-4-2
8kV/15kV
IEC 61000-4-4
4kV,5kHz
IEC 61000-4-5
4kV MC
2kV MD
IEC 61000-4-29
100% 300 ms
60% 300 ms
30% 5s
IEC 61000-4-11
IEC 61000-4-17
IEC 60255-22-7
Class B
IEC 61000-6-4
Class A
IEC 61000-4-3
10V/m
IEC 61000-4-6
10Vrms
IEC 61000-4-8
IEC 61000-4-9
1000 A/m
IEC 61000-4-10
100 A/m
Standard
Dielectric test
IEC 60255-5
2.5 kVac
IEC 60255-5
IEC 60255-5
5kV MC
5kV MD
IEC 61131-2
30 A 0.1
IEC 60255-272
Pag. 25
Technical specifications
Mechanical test
Standard
Vibration (sinusoidal)
IEC 60255-21-1
Class I
IEC 60255-21-2
Class I
Seismic
IEC 60255-21-3
Class I
I/O modules
Available in 24 Vcc/48 Vcc/125 Vcc/250 Vcc. Features:
Digital inputs:
24 Vcc.
48 Vcc.
125 Vcc.
250 Vcc.
Voltage levels
12-72 Vcc
37-72 Vcc
87-300 Vcc
172-300 Vcc
Inactive below:
9 Vcc.
32 Vcc.
82 Vcc.
165 Vcc.
Burden
<3 mA
Digital outputs:
Independent standard and trip outputs
Carry (Permanent)
8 A at 25 C
Make (1 s.)
30 A
Connection capacity
125 Vcc.
48 Vcc.
0.7 A
1.0 A
1.5 A
1.0 A
1.5 A
2.0 A
Operating time
5 ms ON, 8 ms OFF
5 A at 25 C
Make (1 s.)
20 A
30 A
220 Vcc.
125 Vcc.
48 Vcc.
0.1 A
0.2 A
0.5 A
0.2 A
0.4 A
1A
Operating time
8 ms ON/OFF
8 A at 25 C
Make (1 s.)
30 A
Connection capacity
125 Vcc.
48 Vcc.
10 A (L/R=20 ms)
10 A (L/R=40 ms)
10 A (L/R=40 ms)
10 A
10 A
10 A
Cyclic capacity
Operating time
Analogue inputs
Type
AI 1
AI 2
AI 3
AI 4
AI 5
AI 6
AI 7
AI 8
+/- 5mA
+/- 5mA
+/- 2.5mA
+/- 2.5mA
+/- 2.5mA
+/- 2.5mA
+/- 20mA
+/- 20mA
Options for each input: 1mA, 2.5mA, 5mA, 20mA, 5V, 10V
Pag. 26
Technical specifications
Module types
Redundant power supply module
32 inputs module
Pag. 27
Technical specifications
Communication ports
Front communication port
Ethernet RJ45
RJ45 connector
Cable type
Cable length
Insulation
Communication speed
USB
Version
Operating mode
Speed
Insulation
RJ45 female
Shielded
100 m max.
500 V
10/100 Mbps
Compatible with USB 2.0
Master
480 Mbps (high-speed), 12 mbps (full-speed) or 1.5 Mbps (low-speed)
500 V
RS485
GFO
PFO
RS232C connector
Cable type
Cable length
Insulation
RS485 connector
Cable type
Cable length
Insulation
GFO connector
Wavelength
Permitted attenuation
Multimode GFO
Maximum distance
ST
820 nm
8 db with 62.5/125 m GFO
62.5/125 m
1.5 km
PFO connector
Wavelength
Permitted attenuation
HP standard
660 nm
24,7 db with plactic cable of 1mm
22 db with 200/125 m silica cable
115 m with 1 mm plastic cable
1.9 km with 200 m silica cable
60km (E/F)
ST or LC
1310 nm
30 db
9 / 125 nm
60 Km
Maximum distance
FO single-mode
Connector
Wavelength
Permitted attenuation
Singlemode GFO
Distance
C37.94 glass optical fiber
Connector
Wavelength
Permitted attenuation
Multimode GFO
Distance
20-120km (M/N)
ST o LC
1550nm
35 dB
9 / 125nm
Maximum 120km / Minimum 20km
ST
850 nm
8 db
50/125m and 62.5/125 m
2 Km
Ethernet RJ45
RJ45 connector
Cable type
Cable length
Insulation
Communication speed
RJ45 female
Shielded
100 m max.
500V
10/100 Mbps
Pag. 28
Technical specifications
GFO Ethernet
GFO connector
Wavelength
Permitted attenuation:
Multimode GFO
Communication speed
Maximum distance
LC Ethernet
LC connector
Wavelength
Permitted attenuation:
Multimode GFO
Communication speed
Maximum distance
ST
1,300 nm
8 db with GFO
62.5/125 m
100 Mbps
1.5 km
LC duplex
1,310 nm
8 db
62.5/125 u m and 50/125um
100 Mbps
1.5 km
Irig-B input
IRIG-B output
Input
Input level
Cable type
Insulation
Demodulated
TTL
2 shielded wires
2,000 V
Demodulated
TTL
2 shielded wires
2,000 V
Measurements
Frequency
Frequency of the programmable system
Operating range
50 or 60 Hz
Fn 5 Hz
Measurement accuracy
Current
Measurement range (0 to 1.2 x In)
At In=1/5A
0.5 % FS
Protection range (0 to 200 A)
Accuracy
1 % over the measurement or 2 mA
Voltage
Measurement range (0 to 1.2 x Vn)
At Vn=63.5/120 Vac
0.5 % FS
Protection range (0 to 200 Vac)
Accuracy
1 % over the measurement or 50 mV
Angle of phase different
Accuracy
1
Power
Measurement range (0 to 1.2 x In x 1.2 x Vn)
At In=1 A
Class 1 (1 % of Pn)
At In=5 A
Class 0.5 (0.5% of Pn)
Time accuracy
Additional time = 0ms. Currents must be above 100mA, depending on Measurement/start value:
From 1 to 1,5 times: Up to 40ms (typical 35ms)
2 times: Between 30-35ms
From 3 times: Under 30ms
Additional time higher than 50ms.
30ms or 3% of the theorical value (the higher of the two)
Pag. 29
Construction features
Construction features
Pag. 30
Rear views
Rear views
Fig. 1.13 Ingepac EF rear view with half a 19" chassis and 5U
Pag. 31
Keypad/Local display
Keypad/Local display
Pag. 32
Keypad/Local display
1. 5 functional keys.
Pag. 33
Interconnection diagrams
Interconnection diagrams
The following images show the different interconnection options of the analogue inputs, according to the inputs available.
Pag. 34