Reactive Power CRS
Reactive Power CRS
Problem
ABB
Month DD, YYYY | Slide 2
ABB
Month DD, YYYY | Slide 3
Supply reactive
Demand reactive
ABB
Month DD, YYYY | Slide 4
ABB action
Trap change effect to voltage at inverter terminal reduced from 306 to 298 Vac
Proving the reactive power trend and voltage relation which correspond with
the theory
ABB
Month DD, YYYY | Slide 5
ABB
Month DD, YYYY | Slide 6
Capture
Grid background
The PEA overvoltage limit is 23100 volt which correspond to 314.8 Volt of
inverter output which the output voltage of inverter not reach to 314.8 volt while
voltage at feed in point over the limit already (23100 volt).
ABB
Month DD, YYYY | Slide 7
ABB
Month DD, YYYY | Slide 8
Solution
Adjust parameter of phi angle from 3 degree to 0 degree due to the leading
power factor (Positive reactive) increase the voltage level
Limitation
ABB
Month DD, YYYY | Slide 9
Summary
The voltage limit by grid owner (PEA) 20.9 23.1 kV but by switch gear tripping
limit is 19.7 24.2 kV
The reactive power balance is the best solution for control grid voltage which
trending is
We can reduced the grid voltage at feed in point by zero or negative phi degree
which negative or positive may a bit effect to active power production.
Adjustment the phi angle ref to 0 degree is the last action which result show the
voltage a bit reduced of the voltage and the reactive power not over -500 kVAR at
peak power
ABB