PVS800 case CRS


Overvoltage while peak power
ABB
Month DD, YYYY | Slide 1

Problem

Grid voltage over the regulation limit

Event on early April on most of mid day

Voltage limit by grid owner is 20.9 23.1 kV

Voltage switchgear tripping limit is 19.7 24.2 kV

ABB
Month DD, YYYY | Slide 2

Review the cause

Reactive power management

Balancing the demand side and supply side

Grid voltage behavior

Reactive power demand > Reactive power supply

= Grid under voltage

Reactive power demand < Reactive power supply

= Grid Over voltage

ABB
Month DD, YYYY | Slide 3

Reactive power management

Supply reactive

Generator , Synchronous condensers

Demand reactive

Reactor load , Losses

ABB
Month DD, YYYY | Slide 4

ABB action

Change transformer trap 1 step for reduce background voltage of inverter


terminal

Trap change effect to voltage at inverter terminal reduced from 306 to 298 Vac

Proving the reactive power trend and voltage relation which correspond with
the theory

ABB
Month DD, YYYY | Slide 5

Checking the background voltage (Turn off the switchgear )

ABB
Month DD, YYYY | Slide 6

Capture

on 11-4-2013 time 12.09 12.12 at Main switchgear

Grid background

Transformer ratio is 22000 : 300 Volt which is 74.33 : 1 Volt

The PEA overvoltage limit is 23100 volt which correspond to 314.8 Volt of
inverter output which the output voltage of inverter not reach to 314.8 volt while
voltage at feed in point over the limit already (23100 volt).

Background voltage over the limit 0.9 % and a bit oscillate

ABB
Month DD, YYYY | Slide 7

Voltage & Active Power at Feed in Point

Plotting the trend of photo capture when plant running


The 2 led line and 2 green line
show the same active power feed
into grid but the voltage are
difference

This trend show the voltage and


active power not direct variation
with active power in partial
condition which respond to the
balance of grid reactive power
theory

ABB
Month DD, YYYY | Slide 8

Solution

Adjust parameter of phi angle from 3 degree to 0 degree due to the leading
power factor (Positive reactive) increase the voltage level

Record the result

Max reactive -480 kVAR

Max Voltage are nearly the limit

Limitation

ABB
Month DD, YYYY | Slide 9

Reactive power drawn out not over -500 kVAR

Summary

The grid voltage over the limit when peak power

The voltage limit by grid owner (PEA) 20.9 23.1 kV but by switch gear tripping
limit is 19.7 24.2 kV

The reactive power balance is the best solution for control grid voltage which
trending is

Reactive power demand > Reactive power supply

= Grid under voltage

Reactive power demand < Reactive power supply

= Grid Over voltage

We can reduced the grid voltage at feed in point by zero or negative phi degree
which negative or positive may a bit effect to active power production.

Adjustment the phi angle ref to 0 degree is the last action which result show the
voltage a bit reduced of the voltage and the reactive power not over -500 kVAR at
peak power