2.

POTABLE WATER DEMAND CALCULATION


A.POTABLE WATER STORAGE CALCULATION

FIXTURE DESCRIPTION

NUMBER OF
FIXTURES

DEMAND
LITRES/DAY

TOTAL DEMAND
LITRES

WC

180

360.0

LAVATORY

90

180.0

SERVICE SINK

180

540.0

HOSE BIB

14

90

1260.0

HEALTH FAUCET

90

180.0

TOTAL WATER DEMAND PER DAY


SAY

2520.0
3 m3

TOTAL POTABLE WATER STORAGE REQUIREMENT CONSIDERING 5


DAYS STORAGE

15 m3

WATER MIST STORAGE REQUIREMENTS

30 m3

TOTAL POTABLE WATER TANK STORAGE REQUIREMENT

45 m3

B. IRRIGATION WATER STORAGE CALCULATION


Irrigation water storage requirement = 70 m3/day
Note:
Irrigation water storage input by landscape team

3. INCOMING POTABLE WATER FLOWRATE CALCULATION

IWT 1 CAPACITY (m)

IWT 2 CAPACITY
(m)

DWT 1 CAPACITY
(m)

DWT 2 CAPACITY
(m)

TOTAL (m)

35

35

22.5

22.5

115

Q=V/T
Where:

Q = Flow
V = Total Volume
T = Filling Time
Q = 115000 li / 14400 sec

Q = 7.986 l/s

; Which is 115m = 115000 Li


; 4hrs = 14400 sec.