Professional Documents
Culture Documents
Method Statement For Fire Alarm System Installation PDF
Method Statement For Fire Alarm System Installation PDF
& Testing
Below is the method statement for the installation of fire alarm system which can be modified for
different type of systems like HSSD or Vesda etc. The steps are very general and should be
customized depending upon the project specific requirements, specifications and applicable NFPA
or other standards.
Wiring & Connections
Verify that hardware and devices are NRTL listed for use with fire-alarm system before making
connections.
Make addressable connections with a supervised interface device to the following devices and
systems. Install the interface device less than 3 feet (1 m) from the device controller. Make an
addressable confirmation connection when such feedback is available at the device or system being
controlled.
1.
2.
3.
4.
5.
6.
7.
8.
9.
Alarm-initiating connection to activate emergency shutoffs for gas and fuel supplies.
Supervisory connections at valve supervisory switches.
Supervisory connections at low-air-pressure switch of each dry-pipe sprinkler system.
Supervisory connections at elevator shunt trip breaker.
10.
Comply with NFPA 72, Smoke-Sensing Fire Detectors & Heat-Sensing Fire Detectors.
Smooth ceiling spacing shall not exceed 30 feet (9 m).
Fire-Alarm Control Unit: Surface mounted, with tops of cabinets not more than 72 inches
(1830 mm) above the finished floor.
Annunciator: Install with top of panel not more than 72 inches (1830 mm) above the finished
floor.
Fault Finding
To prevent damage to the system, disconnect the batteries & power down the system,
disconnect the power & harnesses from the Power Supply.
Connect the Multi-meter to the battery leads (with batteries disconnected), power up &
measure the voltage. Calculate the difference between the measured voltage & 27.6v. NOTE: After
90 seconds, the voltage will drop to <24v. If this happens, power down & start again.
Positive/Negative Earth Ground Faults:
Fire Panels have the ability to detect positive or negative Earth Ground Faults. An Earth Ground
Fault occurs when an electrical circuit is shorted to ground
Inspection, testing and commissioning
All inspection and testing for fire alarm system shall be carried out in accordance with specifications.
Work shall be carried out by the experienced site team under the guidance of engineer and shall
further be checked and approved by quality engineer.
a)
b)
c)
d)
e)
Inspection shall be based on completed and approved drawings and system documentation
as per NFPA.
f)
Comply with Visual Inspection Frequencies Table in the Inspection Section of the
Inspection, Testing and Maintenance Chapter in NFPA 72; retain the
g)
h)
System Testing: Comply with Test Methods Table in the Testing Section of the Inspection,
Testing and Maintenance Chapter in NFPA 72.
i) Test audible appliances for the public operating mode according to manufacturers written
instructions. Perform the test using a portable sound-level meter complying with Type 2
requirements in ANSI S1.4.
j) Test audible appliances for the private operating mode according to manufacturers written
instructions.
k) Test visible appliances for the public operating mode according to manufacturers written
instructions.
l) Factory-authorized service representative shall prepare the Fire Alarm System Record of
Completion in the Documentation Section of the Fundamentals of Fire Alarm Systems Chapter in
NFPA 72 and the Inspection and Testing Form in the Records Section of the Inspection, Testing
and Maintenance Chapter in NFPA 72.
m) Re-acceptance Testing: Perform re-acceptance testing to verify the proper operation of added or
replaced devices and appliances. Test all the field loop devices with the control panel.
n)
Check the detectors with the artificial test smoke spray. Use forms developed for initial tests
and inspections.
p)
q)
Manufacturers Field Service: Engage a factory-authorized service representative to inspect,
test, and adjust components, assemblies, and equipment installations, including connections.
r)
s)
After testing & commissioning provide training demonstration to facility management team.
t)
Conduct Cause effect inspection as per programmed cause & effect matrix. Test all the
connected devices responds as per the matrix.
u)
Identify system components, wiring, cabling, and terminals. Comply with requirements for
identification specified in specifications.
v)