TM Uat 1114 B

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 92

Table of Contents

1. Model Name........................................................................................................... 1

2. Features................................................................................................................. 2
3. Specifications......................................................................................................... 3
General Data............................................................................................... 3
Safety Data................................................................................................ 13
4.

5.

Selection Process................................................................................................. 15
Application Information......................................................................................... 31
Operating Range....................................................................................... 31
Refrigerant Diagram.................................................................................. 32

6. Installation............................................................................................................ 39
7. Wiring Diagram..................................................................................................... 54
8. Servicing & Maintenance..................................................................................... 59
9. Troubleshooting................................................................................................... 62
10. Dimensional Data................................................................................................. 66
11. Exploded View & Part List.................................................................................... 71

Note : Installation and maintenance are to be performed only by qualified personnel who are

familiar with local codes and regulations, and experienced with this type of equipment.
Caution : Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them.
Warning : Moving machinery and electrical power hazard. May cause severe personnel

injury or death. Disconnect and lock off power before servicing equipment.

1. Model Name
UAT

60

Y1

Changeable Air Discharge


X : Non-Changeable

Power Supply
Y1 : Three Phase, 380-415V, 50Hz

Series
A : A Series
C : C Series

Capacity Index
60 : Based on Btu/hr

Refrigerant
P
: R407C
Blank : R22

Type of Air-Conditioner

TM-UAT-1114-B

UAT : Air-Cooled Rooftop Unit

2. Features
High Efficiency
The Daikin rooftop unit is supplied with high efficiency and reliable scroll compressor .

Package Unit
Dubbed the Plug and Play equivalent in the air-conditioning industry, the single unit configuration allows
hassle free installation. No additional piping work is required as both the indoor and outdoor sides are
pre-connected. Refrigerant is factory pre-charged to ensure clean and efficient operation.

Flexibility Of Air Supply


Daikin rooftop unit uses a belt driven fan such that the air volume and static required can be adjusted
according to the requirement. This flexibility allows for wider application.

Flat Top Design

TM-UAT-1114-B

Daikin rooftop units flat top design allows for maximum utilization of warehouse and container space.

3. Specifications
General Data - Cooling Only (R22)
MODEL
Btu/hr
W
W
A
Btu/hr / W

COOLING CAPACITY
TOTAL INPUT POWER
TOTAL RUNNING CURRENT
EER
REFRIGERANT TYPE / CONTROL
REFRIGERANT CHARGE
POWER SOURCE
CONTROL

kg / Ib
V/Ph/Hz
AIR DISCHARGE
OPERATION

AIR FLOW
EXTERNAL STATIC PRESSURE
CONDENSATE DRAIN SIZE
TYPE
QUANTITY
MATERIAL
FAN
DRIVE
DIAMETER
LENGTH
TYPE
EVAPORATOR
FAN MOTOR

TM-UAT-1114-B

COIL

QUANTITY
INDEX OF PROTECTION (IP)
INSULATION GRADE
POWER SOURCE
RATED INPUT POWER
RATED RUNNING CURRENT
MOTOR OUTPUT
POLES
MATERIAL
TUBE
DIAMETER
MATERIAL
FACE AREA
FIN
ROW
FIN PER INCH

AIR FLOW
SOUND PRESSURE LEVEL
TYPE
QUANTITY
FAN
MATERIAL
DRIVE
DIAMETER
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
INSULATION GRADE
FAN MOTOR
POWER SOURCE
RATED INPUT POWER
RATED RUNNING CURRENT
MOTOR OUTPUT
POLES
CONDENSER
TYPE
QUANTITY
OIL TYPE
OIL AMOUNT
INSULATION GRADE
COMPRESSOR
POWER SOURCE
CAPACITOR
RATED INPUT POWER
RATED RUNNING CURRENT
LOCKED ROTOR AMP.
MATERIAL
TUBE
DIAMETER
MATERIAL
COIL
FACE AREA
FIN
ROW
FIN PER INCH
HEIGHT
UNIT
WIDTH
DIMENSION
DEPTH
HEIGHT
PACKING
WIDTH
DIMENSION
DEPTH
UNIT WEIGHT
TYPE
QUANTITY
LENGTH
AIR QUALITY FILTER RAIL
WIDTH
SIZE
THICKNESS
MATERIAL
CASING
INSULATION / THICKNESS

l/s / CFM
Pa / in.wg.
mm / in

mm/in
mm/in

V/Ph/Hz
W
A
W

mm/in
m/ ft

l/s / CFM
dBA

mm / in

V/Ph/Hz
W
A
W

cm/ fl.oz
V/Ph/Hz
F
W
A
A
mm / in
m/ ft

mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/Ib
pc
mm/in
mm/in
mm/in

UAT60AY1X
59,000
17,292
5610
10.4
10.5
R22 / TXV
5.2 / 11.5
380- 415 / 3 / 50
DUCTED
AUTOTRANSFORMER
850 / 1800
100 / 0.4
25.4 / 1
CENTRIFUGAL
2
PLASTIC
BELT DRIVE
254 / 10
254 / 10
THREE PHASE SQUIRREL CAGE
INDUCTION MOTOR
1
IP22
B
380-415 / 3 / 50
580
1.6
750
4
S.I.G.C
9.52 / 3/8
ALUMINIUM
0.53 / 5.70
3
16
2124 / 4500
63
PROPELLER
1
GALVANISED STEEL
DIRECT DRIVE
609.6 / 24.0
INDUCTION MOTOR
1
IP54
F
220 - 240 / 1 / 50
600
2.52
400
6
SCROLL
1
SONTEX 200LT
1770 / 59.3
F
380 - 415 / 3 / 50
N/A
4540
8.0
74
S.I.G.C
9.52 / 3/8
ALUMINIUM
1.41 / 15.17
2
16
1000 / 39.4
1100 / 43.3
1530 / 60.2
1090 / 42.9
1250 / 49.2
1680 / 66.1
295 / 650
FILTER (OPTIONAL)
1
820 / 32.3
615 / 24.2
25.4 / 1
ELECTRO GALVANISED MILD STEEL
PE / 10 mm

UAT80AY1X
80,000
23,447
8100
15.4
9.9
R22 / CAPILLARY TUBE
4.0 / 8.8
380- 415 / 3 / 50
DUCTED
AUTOTRANSFORMER
1334 / 2826
100 / 0.4
25.4 / 1
CENTRIFUGAL
2
GALVANISED STEEL
BELT DRIVE
254 / 10
254 / 10 & 203.2 / 8.0
THREE PHASE SQUIRREL CAGE
INDUCTION MOTOR
1
IP22
B
380-415 / 3 / 50
1200
2.1
1100
4
SEAMLESS COPPER
9.52 / 3/8
ALUMINIUM
0.65 / 6.96
3
15
2667 / 5650
65
PROPELLER
1
GALVANISED STEEL
DIRECT DRIVE
660.4 / 26.0
INDUCTION MOTOR
1
IP44
F
380 - 415 / 3 / 50
500
1.50
550
6
SCROLL
1
SONTEX 200LT
2510 / 83.7
F
380 - 415 / 3 / 50
N/A
6400
11.8
95
SEAMLESS COPPER
9.52 / 3/8
ALUMINIUM
1.41 / 15.17
2
16
1000 / 39.4
1300 / 51.2
1530 / 60.2
1090 / 42.9
1450 / 57.1
1680 / 66.1
370 / 816
FILTER (OPTIONAL)
1
1020 / 40.2
615 / 24.2
25.4 / 1
ELECTRO GALVANISED MILD STEEL
PE / 10 mm

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
2) ALL UNITS ARE BEING TESTED AND COMPLY TO IS0 13253
3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING -27C DB/ 19C WB INDOOR AND 35C DB / 24C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE MEASURED IN SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.
5) S.I.G.C - SEAMLESS INNER GROOVED COPPER

MODEL
Btu/hr
W
W
A
Btu/hr / W

COOLING CAPACITY
TOTAL INPUT POWER
TOTAL RUNNING CURRENT
EER
REFRIGERANT TYPE / CONTROL
REFRIGERANT CHARGE
POWER SOURCE
CONTROL

kg / Ib
V/Ph/Hz
AIR DISCHARGE
OPERATION

AIR FLOW
EXTERNAL STATIC PRESSURE
CONDENSATE DRAIN SIZE
TYPE
QUANTITY
MATERIAL
FAN
DRIVE
DIAMETER
LENGTH
TYPE
EVAPORATOR
FAN MOTOR

COIL

QUANTITY
INDEX OF PROTECTION (IP)
INSULATION GRADE
POWER SOURCE
RATED INPUT POWER
RATED RUNNING CURRENT
MOTOR OUTPUT
POLES
MATERIAL
TUBE
DIAMETER
MATERIAL
FACE AREA
FIN
ROW
FIN PER INCH

AIR FLOW
SOUND PRESSURE LEVEL
TYPE
QUANTITY
FAN
MATERIAL
DRIVE
DIAMETER
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
INSULATION GRADE
FAN MOTOR
POWER SOURCE
RATED INPUT POWER
RATED RUNNING CURRENT
MOTOR OUTPUT
POLES
CONDENSER
TYPE
QUANTITY
OIL TYPE
OIL AMOUNT
INSULATION GRADE
COMPRESSOR
POWER SOURCE
CAPACITOR
RATED INPUT POWER
RATED RUNNING CURRENT
LOCKED ROTOR AMP.
MATERIAL
TUBE
DIAMETER
MATERIAL
COIL
FACE AREA
FIN
ROW
FIN PER INCH
HEIGHT
UNIT
WIDTH
DIMENSION
DEPTH
HEIGHT
PACKING
WIDTH
DIMENSION
DEPTH
UNIT WEIGHT
TYPE
QUANTITY
AIR QUALITY FILTER RAIL
LENGTH
SIZE
WIDTH
THICKNESS
MATERIAL
CASING
INSULATION / THICKNESS

l/s / CFM
Pa / in.wg.
mm / in

mm/in
mm/in

V/Ph/Hz
W
A
W

mm/in
m/ ft

l/s / CFM
dBA

mm / in

V/Ph/Hz
W
A
W

cm/ fl.oz
V/Ph/Hz
F
W
A
A
mm / in
m/ ft

mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/Ib
pc
mm/in
mm/in
mm/in

UAT100AY1X
100,000
29,308
10,500
18.2
9.5
R22 / CAPILLARY TUBE
5.9 / 13
380- 415 / 3 / 50
DUCTED
AUTOTRANSFORMER
1667 / 3532
100 / 0.4
25.4 / 1
CENTRIFUGAL
2
GALVANISED STEEL
BELT DRIVE
254 / 10
254 / 10 & 203.2 / 8.0
THREE PHASE SQUIRREL CAGE
INDUCTION MOTOR
1
IP22
B
380-415 / 3 / 50
1900
2.7
1500
4
SEAMLESS COPPER
9.52 / 3/8
ALUMINIUM
0.65 / 7.00
4
15
2667 / 5650
66
PROPELLER
1
GALVANISED STEEL
DIRECT DRIVE
660.4 / 26.0
THREE PHASE INDUCTION MOTOR
1
IP44
F
380 - 415 / 3 / 50
670
1.30
550
6
SCROLL
1
SONTEX 200LT
3250 / 108.3
F
380 - 415 / 3 / 50
N/A
7930
14.2
125
SEAMLESS COPPER
9.52 / 3/8
ALUMINIUM
1.42 / 15.28
3
16
1000 / 39.4
1300 / 51.2
1530 / 60.2
1090 / 42.9
1450 / 57.1
1680 / 66.1
400 / 882
FILTER (OPTIONAL)
1
1020 / 40.2
615 / 24.2
25.4 / 1
ELECTRO GALVANISED MILD STEEL
PE / 10 mm

UAT120AY1X
116,000
33,998
11,560
22.1
10.0
R22 / TXV
6.2 / 13.7
380- 415 / 3 / 50
DUCTED
AUTOTRANSFORMER
1699 / 3600
100 / 0.4
25.4 / 1
CENTRIFUGAL
2
GALVANISED STEEL
BELT DRIVE
254 / 10
254 / 10 & 203.2 / 8.0
THREE PHASE SQUIRREL CAGE
INDUCTION MOTOR
1
IP22
B
380-415 / 3 / 50
1340
2.6
1500
4
S.I.G.C
9.52 / 3/8
ALUMINIUM
0.65 / 7.00
4
14
3776 / 8000
68
PROPELLER
1
GALVANISED STEEL
DIRECT DRIVE
762 / 30.0
THREE PHASE INDUCTION MOTOR
1
IP44
E
380 - 415 / 3 / 50
960
2.40
580
8
SCROLL
1
SONTEX 200LT
3250 / 108.3
F
380 - 415 / 3 / 50
N/A
9600
17.1
125
S.I.G.C
9.52 / 3/8
ALUMINIUM
1.42 / 15.28
3
14
1000 / 39.4
1300 / 51.2
1530 / 60.2
1090 / 42.9
1450 / 57.1
1680 / 66.1
425 / 937
FILTER (OPTIONAL)
1
1020 / 40.2
615 / 24.2
25.4 / 1
ELECTRO GALVANISED MILD STEEL
PE / 10 mm

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
2) ALL UNITS ARE BEING TESTED AND COMPLY TO IS0 13253
3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING -27C DB/ 19C WB INDOOR AND 35C DB / 24C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE MEASURED IN SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.
5) S.I.G.C - SEAMLESS INNER GROOVED COPPER

TM-UAT-1114-B

General Data - Cooling Only (R22)

General Data - Cooling Only (R22)


MODEL
Btu/hr
W
W
A
Btu/hr / W

COOLING CAPACITY
TOTAL INPUT POWER
TOTAL RUNNING CURRENT
EER
REFRIGERANT TYPE / CONTROL
REFRIGERANT CHARGE
POWER SOURCE
CONTROL

kg / Ib
V/Ph/Hz
AIR DISCHARGE
OPERATION

AIR FLOW
EXTERNAL STATIC PRESSURE
CONDENSATE DRAIN SIZE
TYPE
QUANTITY
MATERIAL
FAN
DRIVE
DIAMETER
LENGTH
TYPE
EVAPORATOR
FAN MOTOR

TM-UAT-1114-B

COIL

QUANTITY
INDEX OF PROTECTION (IP)
INSULATION GRADE
POWER SOURCE
RATED INPUT POWER
RATED RUNNING CURRENT
MOTOR OUTPUT
POLES
MATERIAL
TUBE
DIAMETER
MATERIAL
FACE AREA
FIN
ROW
FIN PER INCH

AIR FLOW
SOUND PRESSURE LEVEL
TYPE
QUANTITY
FAN
MATERIAL
DRIVE
DIAMETER
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
INSULATION GRADE
FAN MOTOR
POWER SOURCE
RATED INPUT POWER
RATED RUNNING CURRENT
MOTOR OUTPUT
POLES
CONDENSER
TYPE
QUANTITY
OIL TYPE
OIL AMOUNT
INSULATION GRADE
COMPRESSOR
POWER SOURCE
CAPACITOR
RATED INPUT POWER
RATED RUNNING CURRENT
LOCKED ROTOR AMP.
MATERIAL
TUBE
DIAMETER
MATERIAL
COIL
FACE AREA
FIN
ROW
FIN PER INCH
HEIGHT
UNIT
WIDTH
DIMENSION
DEPTH
HEIGHT
PACKING
WIDTH
DIMENSION
DEPTH
UNIT WEIGHT
TYPE
QUANTITY
AIR QUALITY FILTER RAIL
LENGTH
SIZE
WIDTH
THICKNESS
MATERIAL
CASING
INSULATION / THICKNESS

l/s / CFM
Pa / in.wg.
mm / in

mm/in
mm/in

V/Ph/Hz
W
A
W

mm/in
m/ ft

l/s / CFM
dBA

mm / in

V/Ph/Hz
W
A
W

cm/ fl.oz
V/Ph/Hz
F
W
A
A
mm / in
m/ ft

mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/Ib
pc
mm/in
mm/in
mm/in

UAT150CY1X
145,500
42,644
13,070
24.8
11.1
R22 / TXV
2x 4.6 / 2 x 10.1
380- 415 / 3 / 50
DUCTED
AUTOTRANSFORMER
2173 / 4600
125 / 0.5
25.40 / 1
CENTRIFUGAL
1
GALVANISED STEEL
BELT DRIVE
305 / 12
305 / 12
THREE PHASE SQUIRREL CAGE
INDUCTION MOTOR
1
IP22
B
380-415 / 3 / 50
1700
3.7
2200
4
S.I.G.C
9.52 / 0.38
ALUMINIUM
0.57 / 6.14
3
16
4673 / 9900
66
PROPELLER
2
PLASTIC
DIRECT DRIVE
610 / 24
THREE PHASE INDUCTION MOTOR
2
IP55
F
380 - 415 / 3 / 50
1040
2.30
360
6
SCROLL
2
MINERAL OIL
2514 / 83.8
F
380 - 415 / 3 / 50
N/A
10320
9.8
100
S.I.G.C
9.52 / 3/8
ALUMINIUM
1.30 / 14.0
2
16
1390 / 54.7
1965 / 77.4
1630 / 64.2
1540 / 60.6
2150 / 84.6
1935 / 76.2
600 / 1322.8
FILTER (OPTIONAL)
2
895 / 35.2
685 / 27.0
50.8 / 2
GALVANISED STEEL
PE / 10mm

UAT180CY1X
188,600
55,275
16,920
31.3
11.1
R22 / TXV
2 x 6 / 2 x 13.2
380- 415 / 3 / 50
DUCTED
AUTOTRANSFORMER
3068 / 6500
150 / 0.6
25.40 / 1
CENTRIFUGAL
1
GALVANISED STEEL
BELT DRIVE
305 / 12
305 / 12
THREE PHASE SQUIRREL CAGE
INDUCTION MOTOR
1
IP22
B
380-415 / 3 / 50
2100
4.3
3700
4
S.I.G.C
9.52 / 0.38
ALUMINIUM
0.65 / 7.00
3
16
6514 / 13800
68
PROPELLER
2
PLASTIC
DIRECT DRIVE
681 / 26.8
THREE PHASE INDUCTION MOTOR
2
IP55
F
380 - 415 / 3 / 50
1600
3.50
580
6
SCROLL
2
MINERAL OIL
3253 / 108.4
F
380 - 415 / 3 / 50
N/A
13220
12.6
111
S.I.G.C
9.52 / 3/8
ALUMINIUM
1.44 / 15.5
2
16
1390 / 54.7
1965 / 77.4
1630 / 64.2
1540 / 60.6
2150 / 84.6
1935 / 76.2
650 / 1433
FILTER (OPTIONAL)
2
895 / 35.2
685 / 27.0
50.8 / 2
GALVANISED STEEL
PE / 10mm

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
2) ALL UNITS ARE BEING TESTED AND COMPLY TO IS0 13253
3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING -27C DB/ 19C WB INDOOR AND 35C DB / 24C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE MEASURED IN SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.
5) S.I.G.C - SEAMLESS INNER GROOVED COPPER

MODEL
Btu/hr
W
W
A
Btu/hr / W

COOLING CAPACITY
TOTAL INPUT POWER
TOTAL RUNNING CURRENT
EER
REFRIGERANT TYPE / CONTROL
REFRIGERANT CHARGE
POWER SOURCE
CONTROL

kg / Ib
V/Ph/Hz
AIR DISCHARGE
OPERATION

AIR FLOW
EXTERNAL STATIC PRESSURE
CONDENSATE DRAIN SIZE
TYPE
QUANTITY
MATERIAL
FAN
DRIVE
DIAMETER
LENGTH
TYPE
EVAPORATOR
FAN MOTOR

COIL

QUANTITY
INDEX OF PROTECTION (IP)
INSULATION GRADE
POWER SOURCE
RATED INPUT POWER
RATED RUNNING CURRENT
MOTOR OUTPUT
POLES
MATERIAL
TUBE
DIAMETER
MATERIAL
FACE AREA
FIN
ROW
FIN PER INCH

AIR FLOW
SOUND PRESSURE LEVEL
TYPE
QUANTITY
FAN
MATERIAL
DRIVE
DIAMETER
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
INSULATION GRADE
FAN MOTOR
POWER SOURCE
RATED INPUT POWER
RATED RUNNING CURRENT
MOTOR OUTPUT
POLES
CONDENSER
TYPE
QUANTITY
OIL TYPE
OIL AMOUNT
INSULATION GRADE
COMPRESSOR
POWER SOURCE
CAPACITOR
RATED INPUT POWER
RATED RUNNING CURRENT
LOCKED ROTOR AMP.
MATERIAL
TUBE
DIAMETER
MATERIAL
COIL
FACE AREA
FIN
ROW
FIN PER INCH
HEIGHT
UNIT
WIDTH
DIMENSION
DEPTH
HEIGHT
PACKING
WIDTH
DIMENSION
DEPTH
UNIT WEIGHT
TYPE
QUANTITY
AIR QUALITY FILTER RAIL
LENGTH
SIZE
WIDTH
THICKNESS
MATERIAL
CASING
INSULATION / THICKNESS

l/s / CFM
Pa / in.wg.
mm / in

mm/in
mm/in

V/Ph/Hz
W
A
W

mm/in
m/ ft

l/s / CFM
dBA

mm / in

V/Ph/Hz
W
A
W

cm/ fl.oz
V/Ph/Hz
F
W
A
A
mm / in
m/ ft

mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/Ib
pc
mm/in
mm/in
mm/in

UAT240CY1X
252,300
73,945
23,000
40.0
11.0
R22 / TXV
2 x 8 / 2x 17.6
380- 415 / 3 / 50
DUCTED
AUTOTRANSFORMER
3729 / 7900
200 / 0.8
25.40 / 1
CENTRIFUGAL
1
GALVANISED STEEL
BELT DRIVE
457 / 18
457 / 18
THREE PHASE SQUIRREL CAGE
INDUCTION MOTOR
1
IP22
B
380-415 / 3 / 50
2920
5.6
3700
4
S.I.G.C
9.52 / 0.38
ALUMINIUM
0.89 / 9.58
4
16
5773 / 12230
68
PROPELLER
2
PLASTIC
DIRECT DRIVE
681 / 26.8
THREE PHASE INDUCTION MOTOR
2
IP55
F
380 - 415 / 3 / 50
1740
3.80
680
6
SCROLL
2
MINERAL OIL
3253 / 108.4
F
380 - 415 / 3 / 50
N/A
18340
16.1
118
S.I.G.C
9.52 / 3/8
ALUMINIUM
1.64 / 17.7
3
16
1690 / 66.5
1965 / 77.4
1905 / 75
1865 / 73.4
2150 / 84.6
2220 / 87.4
850 / 1874
FILTER (OPTIONAL)
2
834 / 32.8
760 / 29.9
50.8 / 2
GALVANISED STEEL
PE / 10mm

UAT300CY1X
306,400
89,801
28,360
53.2
10.8
R22 / TXV
2 x 10.6 / 2 x 23.4
380- 415 / 3 / 50
DUCTED
AUTOTRANSFORMER
4101 / 8700
250 / 1.0
25.40 / 1
CENTRIFUGAL
1
GALVANISED STEEL
BELT DRIVE
381 / 15
381 / 15
THREE PHASE SQUIRREL CAGE
INDUCTION MOTOR
1
IP22
B
380-415 / 3 / 50
4200
7.9
5500
4
S.I.G.C
9.52 / 0.38
ALUMINIUM
1.14 / 12.3
4
16
10148 / 21500
73
PROPELLER
2
PLASTIC
DIRECT DRIVE
800 / 31.5
THREE PHASE INDUCTION MOTOR
2
IP55
F
380 - 415 / 3 / 50
300
2.70
1,200
6
SCROLL
2
MINERAL OIL
3253 / 108.4
F
380 - 415 / 3 / 50
N/A
23360
22.5
174
S.I.G.C
9.52 / 3/8
ALUMINIUM
2.13 / 22.9
3
16
1650 / 65.0
2410 / 94.9
2030 / 80.0
1875 / 73.8
2590 / 102.0
2270 / 89.4
980 / 2161
FILTER (OPTIONAL)
2
1040 / 40.9
750 / 29.5
50.8 / 2
GALVANISED STEEL
PE / 10mm

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
2) ALL UNITS ARE BEING TESTED AND COMPLY TO IS0 13253
3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING -27C DB/ 19C WB INDOOR AND 35C DB / 24C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE MEASURED IN SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.
5) S.I.G.C - SEAMLESS INNER GROOVED COPPER

TM-UAT-1114-B

General Data - Cooling Only (R22)

General Data - Cooling Only (R22)


MODEL
Btu/hr
W
W
A
Btu/hr / W

COOLING CAPACITY
TOTAL INPUT POWER
TOTAL RUNNING CURRENT
EER
REFRIGERANT TYPE / CONTROL
REFRIGERANT CHARGE
POWER SOURCE

kg / Ib
V/Ph/Hz

AIR DISCHARGE
OPERATION
AIR FLOW
EXTERNAL STATIC PRESSURE
CONDENSATE DRAIN SIZE
TYPE
QUANTITY
MATERIAL
FAN
DRIVE
DIAMETER
LENGTH
TYPE

CONTROL

EVAPORATOR
FAN MOTOR

TM-UAT-1114-B

COIL

QUANTITY
INDEX OF PROTECTION (IP)
INSULATION GRADE
POWER SOURCE
RATED INPUT POWER
RATED RUNNING CURRENT
MOTOR OUTPUT
POLES
MATERIAL
TUBE
DIAMETER
MATERIAL
FACE AREA
FIN
ROW
FIN PER INCH

AIR FLOW
SOUND PRESSURE LEVEL
TYPE
QUANTITY
FAN
MATERIAL
DRIVE
DIAMETER
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
INSULATION GRADE
FAN MOTOR
POWER SOURCE
RATED INPUT POWER
RATED RUNNING CURRENT
MOTOR OUTPUT
POLES
CONDENSER
TYPE
QUANTITY
OIL TYPE
OIL AMOUNT
INSULATION GRADE
COMPRESSOR
POWER SOURCE
CAPACITOR
RATED INPUT POWER
RATED RUNNING CURRENT
LOCKED ROTOR AMP.
MATERIAL
TUBE
DIAMETER
MATERIAL
COIL
FACE AREA
FIN
ROW
FIN PER INCH
HEIGHT
UNIT
WIDTH
DIMENSION
DEPTH
HEIGHT
PACKING
WIDTH
DIMENSION
DEPTH
UNIT WEIGHT
TYPE
QUANTITY
AIR QUALITY FILTER RAIL
LENGTH
SIZE
WIDTH
THICKNESS
MATERIAL
CASING
INSULATION / THICKNESS

l/s / CFM
Pa / in.wg.
mm / in

mm/in
mm/in

V/Ph/Hz
W
A
W

mm/in
m/ ft

l/s / CFM
dBA

mm / in

V/Ph/Hz
W
A
W

cm/ fl.oz
V/Ph/Hz
F
W
A
A
mm / in
m/ ft

mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/Ib
pc
mm/in
mm/in
mm/in

UAT360AY1X
329,000
96,424
39,870
67.2
8.3
R22 / TXV
16.5 / 36.4 & 19.5 / 43.0
380- 415 / 3 / 50
DUCTED
AUTOTRANSFORMER
5191 / 11000
300 / 1.2
25.4 / 1
CENTRIFUGAL
1
GALVANISED STEEL
BELT DRIVE
560 / 22
457 / 18
THREE PHASE SQUIRREL CAGE
INDUCTION MOTOR
1
IP22
F
380-415 / 3 / 50
5870
11.3
5107
4
S.I.G.C
9.52 / 3/8
ALUMINIUM
3.02 / 32.5
3&4
14 & 13
9439 / 20000
70
PROPELLER
2
GALVANISED STEEL
DIRECT DRIVE
812.8 / 32.0
THREE PHASE INDUCTION MOTOR
2
IP55
F
380 - 415 / 3 / 50
4500
8.40
3465
6
SCROLL
2
160P & 320SZ
6600 / 220 & 8000 / 266.7
N/A
380 - 415 / 3 / 50
N/A
29500
47.5
175 & 215
S.I.G.C
9.52 / 3/8
ALUMINIUM
3.50 / 37.7
2&3
14 & 13
1974 / 77.7
2252 / 88.7
3100 / 122.0
2150 / 84.5
2300 / 90.5
3250 / 128.0
1600 / 3527
FILTER (OPTIONAL)
2&4
860 / 33.86
505/ 19.88 & 600/ 23.62
50.8 / 2
ELECTRO GALVANISED MILD STEEL
PE / 10 mm

UAT420AY1X
404,000
118,406
46,800
72.8
8.6
R22 / TXV
2 x 19.5 / 2 x 43.0
380- 415 / 3 / 50
DUCTED
AUTOTRANSFORMER
5899 / 12500
300 / 1.2
25.4 / 1
CENTRIFUGAL
1
GALVANISED STEEL
BELT DRIVE
560 / 22
457 / 18
THREE PHASE SQUIRREL CAGE
INDUCTION MOTOR
1
IP22
F
380-415 / 3 / 50
7500
13.3
6525
4
S.I.G.C
9.52 / 3/8
ALUMINIUM
3.02 / 32.5
4
13
9439 / 20000
70
PROPELLER
2
GALVANISED STEEL
DIRECT DRIVE
812.8 / 32.0
THREE PHASE INDUCTION MOTOR
2
IP55
F
380 - 415 / 3 / 50
4500
8.40
3465
6
SCROLL
2
320SZ
8000 / 266.7
N/A
380 - 415 / 3 / 50
N/A
34800
51.1
215
S.I.G.C
9.52 / 3/8
ALUMINIUM
3.50 / 37.7
3
13
1974 / 77.7
2252 / 88.7
3100 / 122.0
2150 / 84.5
2300 / 90.5
3250 / 128.0
1600 / 3527
FILTER (OPTIONAL)
2&4
860 / 33.86
505/ 19.88 & 600/ 23.62
50.8 / 2
ELECTRO GALVANISED MILD STEEL
PE / 10 mm

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
2) ALL UNITS ARE BEING TESTED AND COMPLY TO IS0 13253
3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING -27C DB/ 19C WB INDOOR AND 35C DB / 24C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE MEASURED IN SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.
5) S.I.G.C - SEAMLESS INNER GROOVED COPPER

MODEL

Btu/hr
W
W
A
Btu/hr / W

COOLING CAPACITY
TOTAL INPUT POWER
TOTAL RUNNING CURRENT
EER
REFRIGERANT TYPE / CONTROL
REFRIGERANT CHARGE
POWER SOURCE
CONTROL

kg / Ib
V/Ph/Hz
AIR DISCHARGE
OPERATION

AIR FLOW
EXTERNAL STATIC PRESSURE
CONDENSATE DRAIN SIZE
TYPE
QUANTITY
MATERIAL
FAN
DRIVE
DIAMETER
LENGTH

l/s / CFM
Pa / in.wg.
mm / in

mm/in
mm/in

TYPE
EVAPORATOR
FAN MOTOR

COIL

QUANTITY
INDEX OF PROTECTION (IP)
INSULATION GRADE
POWER SOURCE
RATED INPUT POWER
RATED RUNNING CURRENT
MOTOR OUTPUT
POLES
MATERIAL
TUBE
DIAMETER
THICKNESS
MATERIAL
THICKNESS
FIN
FACE AREA
ROW
FIN PER INCH

AIR FLOW
SOUND PRESSURE LEVEL
TYPE
QUANTITY
FAN
MATERIAL
DRIVE
DIAMETER
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
INSULATION GRADE
POWER SOURCE
FAN MOTOR
RATED INPUT POWER
RATED RUNNING CURRENT
MOTOR OUTPUT
POLES
TYPE
CONDENSER
QUANTITY
OIL TYPE
OIL AMOUNT
INSULATION GRADE
COMPRESSOR
POWER SOURCE
CAPACITOR
RATED INPUT POWER
RATED RUNNING CURRENT
LOCKED ROTOR AMP.
MATERIAL
TUBE
DIAMETER
THICKNESS
MATERIAL
COIL
THICKNESS
FIN
FACE AREA
ROW
FIN PER INCH
HEIGHT
UNIT DIMENSION
WIDTH
DEPTH
HEIGHT
PACKING DIMENSION WIDTH
DEPTH
UNIT WEIGHT
TYPE
QUANTITY
LENGTH
AIR QUALITY
FILTER RAIL
WIDTH
SIZE
THICKNESS
MATERIAL
CASING
INSULATION / THICKNESS

V/Ph/Hz
W
A
W
mm/in
mm/in
mm/in
m2/ ft2

l/s / CFM
dBA

mm / in

V/Ph/Hz
W
A
W

cm3 / fl.oz
V/Ph/Hz
F
W
A
A
mm / in
mm / in
mm/ in
m2/ ft2
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/Ib
pc
mm/in
mm/in
mm/in

UATP60AY1X
UATP80AY1X
59,000
72,000
17,292
21,102
5,890
8,700
10.9
16.3
10.0
8.3
R407C / TXV
R407C / CAPILLARY TUBE
4.6 / 10.1
4.6 / 10.1
380 - 415 / 3 / 50
380 - 415 / 3 / 50
DUCTED
DUCTED
AUTOTRANSFORMER
AUTOTRANSFORMER
850 / 1800
1334 / 2826
100 / 0.4
100 / 0.4
25.4 / 1.0
25.4 / 1.0
CENTRIFUGAL
CENTRIFUGAL
2
2
PLASTIC
GALVANISED STEEL
BELT DRIVE
BELT DRIVE
254 /10
254 /10
254 /10
254 / 10 & 203.2 / 8.0
THREE PHASE SQUIRREL CAGE THREE PHASE SQUIRREL CAGE
INDUCTION MOTOR
INDUCTION MOTOR
1
1
IP22
IP22
B
B
380-415 / 3 / 50
380-415 / 3 / 50
580
1200
1.60
2.10
750
1100
4
4
S.I.G.C
SEAMLESS COPPER
9.52 / 3/8
9.52 / 3/8
0.33 / 0.013
0.33 / 0.013
ALUMINIUM
ALUMINIUM
0.11 / 0.004
0.11 / 0.004
0.53 / 5.70
0.65 / 6.96
3
3
16
15
2124 / 4500
2667 / 5650
63
65
PROPELLER
PROPELLER
1
1
GALVANISED STEEL
GALVANISED STEEL
DIRECT DRIVE
DIRECT DRIVE
609.6 / 24.0
660.4 / 26.0
INDUCTION MOTOR
INDUCTION MOTOR
1
1
IP54
IP44
F
F
220-240 / 1 / 50
220-240 / 1 / 50
600
670
2.52
1.30
400
550
6
6
SCROLL
SCROLL
1
1
POE
POE
1770 / 62.3
2510 / 88.3
F
F
380 - 415 / 3 / 50
380 - 415 / 3 / 50
N/A
N/A
4820
6830
8.5
12.9
74
95
S.I.G.C
S.I.G.C
9.52 / 3/8
9.52 / 3/8
0.33 / 0.013
0.33 / 0.013
ALUMINIUM
ALUMINIUM
0.11 / 0.004
0.11 / 0.004
1.41 / 15.17
1.41 / 15.17
2
2
16
16
1000 / 39.4
1000 / 39.4
1100 / 43.3
1300 / 51.2
1530 / 60.2
1530 / 60.2
1090 / 42.9
1090 / 42.9
1250 / 49.2
1450 / 57.1
1680 / 66.1
1680 / 66.1
295 / 650
370 / 816
FILTER (OPTIONAL)
FILTER (OPTIONAL)
1
1
820 / 32.3
1020 / 40.2
615 / 24.2
615 / 24.2
25.4 / 1
25.4 / 1
ELECTRO GALVANISED STEEL
ELECTRO GALVANISED STEEL
PE / 10mm
PE / 10mm

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
2) ALL UNITS ARE BEING TESTED AND COMPLY TO IS0 13253
3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING -27C DB/ 19C WB INDOOR AND 35C DB / 24C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE MEASURED IN SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.
5) S.I.G.C - SEAMLESS INNER GROOVED COPPER

TM-UAT-1114-B

General Data - Cooling Only (R407C)

General Data - Cooling Only (R407C)


MODEL

Btu/hr
W
W
A
Btu/hr / W

COOLING CAPACITY
TOTAL INPUT POWER
TOTAL RUNNING CURRENT
EER
REFRIGERANT TYPE / CONTROL
REFRIGERANT CHARGE
POWER SOURCE
CONTROL

kg / Ib
V/Ph/Hz
AIR DISCHARGE
OPERATION

AIR FLOW
EXTERNAL STATIC PRESSURE
CONDENSATE DRAIN SIZE
TYPE
QUANTITY
MATERIAL
FAN
DRIVE
DIAMETER
LENGTH

l/s / CFM
Pa / in.wg.
mm / in

mm/in
mm/in

TYPE
EVAPORATOR
FAN MOTOR

TM-UAT-1114-B

COIL

QUANTITY
INDEX OF PROTECTION (IP)
INSULATION GRADE
POWER SOURCE
RATED INPUT POWER
RATED RUNNING CURRENT
MOTOR OUTPUT
POLES
MATERIAL
DIAMETER
TUBE
THICKNESS
MATERIAL
THICKNESS
FACE AREA
FIN
ROW
FIN PER INCH

AIR FLOW
SOUND PRESSURE LEVEL
TYPE
QUANTITY
FAN
MATERIAL
DRIVE
DIAMETER
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
INSULATION GRADE
FAN MOTOR
POWER SOURCE
RATED INPUT POWER
RATED RUNNING CURRENT
MOTOR OUTPUT
POLES
TYPE
CONDENSER
QUANTITY
OIL TYPE
OIL AMOUNT
INSULATION GRADE
COMPRESSOR
POWER SOURCE
CAPACITOR
RATED INPUT POWER
RATED RUNNING CURRENT
LOCKED ROTOR AMP.
MATERIAL
TUBE
DIAMETER
THICKNESS
MATERIAL
COIL
THICKNESS
FIN
FACE AREA
ROW
FIN PER INCH
HEIGHT
UNIT DIMENSION
WIDTH
DEPTH
HEIGHT
PACKING DIMENSION WIDTH
DEPTH
UNIT WEIGHT
TYPE
QUANTITY
AIR QUALITY
FILTER RAIL
LENGTH
SIZE
WIDTH
THICKNESS
MATERIAL
CASING
INSULATION / THICKNESS

V/Ph/Hz
W
A
W
mm/in
mm/in
mm/in
m2/ ft2

l/s / CFM
dBA

mm / in

V/Ph/Hz
W
A
W

cm3 / fl.oz
V/Ph/Hz
F
W
A
A
mm / in
mm / in
mm/ in
m2/ ft2
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/Ib
pc
mm/in
mm/in
mm/in

UATP100AY1X
95,000
27,843
11,600
20.2
8.2
R407C / CAPILLARY TUBE
5.9 / 13
380 - 415 / 3 / 50
DUCTED
AUTOTRANSFORMER
1667 / 3532
100 / 0.4
25.4 / 1.0
CENTRIFUGAL
2
GALVANISED STEEL
BELT DRIVE
254 /10
254 / 10 & 203.2 / 8.0
THREE PHASE SQUIRREL CAGE
INDUCTION MOTOR
1
IP22
B
380-415 / 3 / 50
1900
2.70
1500
4
SEAMLESS COPPER
9.52 / 3/8
0.33 / 0.013
ALUMINIUM
0.11 / 0.004
0.65 / 6.96
4
15
2667 / 5650
66
PROPELLER
1
GALVANISED STEEL
DIRECT DRIVE
660.4 / 26.0
THREE PHASE INDUCTION MOTOR
1
IP22
F
380-415 / 3 / 50
670
1.30
550
6
SCROLL
1
POE
3250 / 114.4
F
380 - 415 / 3 / 50
N/A
9030
16.2
125
S.I.G.C
9.52 / 3/8
0.33 / 0.013
ALUMINIUM
0.11 / 0.004
1.42 / 15.28
3
16
1000 / 39.4
1300 / 51.2
1530 / 60.2
1090 / 42.9
1450 / 57.1
1680 / 66.1
400 / 882
FILTER (OPTIONAL)
1
1020 / 40.2
615 / 24.2
25.4 / 1
ELECTRO GALVANISED STEEL
PE / 10mm

UATP120AY1X
110,000
32,239
12,180
22.8
9.0
R407C / TXV
5.6 / 12.3
380 - 415 / 3 / 50
DUCTED
AUTOTRANSFORMER
1699 / 3600
100 / 0.4
25.4 / 1.0
CENTRIFUGAL
2
GALVANISED STEEL
BELT DRIVE
254 /10
254 / 10 & 203.2 / 8.0
THREE PHASE SQUIRREL CAGE
INDUCTION MOTOR
1
IP22
B
380-415 / 3 / 50
1340
2.59
1500
4
S.I.G.C
9.52 / 3/8
0.33 / 0.013
ALUMINIUM
0.11 / 0.004
0.65 / 6.96
4
14
3776 / 8000
68
PROPELLER
1
GALVANISED STEEL
DIRECT DRIVE
762 / 30
THREE PHASE INDUCTION MOTOR
1
IP44
E
380-415 / 3 / 50
960
2.40
580
8
SCROLL
1
POE
3250 / 114.4
F
380 - 415 / 3 / 50
N/A
10220
17.8
125
S.I.G.C
9.52 / 3/8
0.33 / 0.013
ALUMINIUM
0.11 / 0.004
1.42 / 15.28
3
14
1000 / 39.4
1300 / 51.2
1530 / 60.2
1090 / 42.9
1450 / 57.1
1680 / 66.1
425 / 937
FILTER (OPTIONAL)
1
1020 / 40.2
615 / 24.2
25.4 / 1
ELECTRO GALVANISED STEEL
PE / 10mm

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
2) ALL UNITS ARE BEING TESTED AND COMPLY TO IS0 13253
3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING -27C DB/ 19C WB INDOOR AND 35C DB / 24C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE MEASURED IN SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.
5) S.I.G.C - SEAMLESS INNER GROOVED COPPER

MODEL

Btu/hr
W
W
A
Btu/hr / W

COOLING CAPACITY
TOTAL INPUT POWER
TOTAL RUNNING CURRENT
EER
REFRIGERANT TYPE / CONTROL
REFRIGERANT CHARGE
POWER SOURCE
CONTROL

kg / Ib
V/Ph/Hz
AIR DISCHARGE
OPERATION

AIR FLOW
EXTERNAL STATIC PRESSURE
CONDENSATE DRAIN SIZE
TYPE
QUANTITY
MATERIAL
FAN
DRIVE
DIAMETER
LENGTH

l/s / CFM
Pa / in.wg.
mm / in

mm/in
mm/in

TYPE
EVAPORATOR
FAN MOTOR

COIL

QUANTITY
INDEX OF PROTECTION (IP)
INSULATION GRADE
POWER SOURCE
RATED INPUT POWER
RATED RUNNING CURRENT
MOTOR OUTPUT
POLES
MATERIAL
DIAMETER
TUBE
THICKNESS
MATERIAL
THICKNESS
FACE AREA
FIN
ROW
FIN PER INCH

AIR FLOW
SOUND PRESSURE LEVEL
TYPE
QUANTITY
FAN
MATERIAL
DRIVE
DIAMETER
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
INSULATION GRADE
FAN MOTOR
POWER SOURCE
RATED INPUT POWER
RATED RUNNING CURRENT
MOTOR OUTPUT
POLES
TYPE
CONDENSER
QUANTITY
OIL TYPE
OIL AMOUNT
INSULATION GRADE
COMPRESSOR
POWER SOURCE
CAPACITOR
RATED INPUT POWER
RATED RUNNING CURRENT
LOCKED ROTOR AMP.
MATERIAL
TUBE
DIAMETER
THICKNESS
MATERIAL
COIL
THICKNESS
FIN
FACE AREA
ROW
FIN PER INCH
HEIGHT
UNIT DIMENSION
WIDTH
DEPTH
HEIGHT
PACKING DIMENSION WIDTH
DEPTH
UNIT WEIGHT
TYPE
QUANTITY
AIR QUALITY
FILTER RAIL
LENGTH
SIZE
WIDTH
THICKNESS
MATERIAL
CASING
INSULATION / THICKNESS

V/Ph/Hz
W
A
W
mm/in
mm/in
mm/in
m2/ ft2

l/s / CFM
dBA

mm / in

V/Ph/Hz
W
A
W

cm3 / fl.oz
V/Ph/Hz
F
W
A
A
mm / in
mm / in
mm/ in
m2/ ft2
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/Ib
pc
mm/in
mm/in
mm/in

UATP150AY1X
140,000
41,032
17,200
32.1
8.1
R407C / CAPILLARY TUBE
2 x 3.9 / 2 x 8.6
380 - 415 / 3 / 50
DUCTED
AUTOTRANSFORMER
2667 / 5651
200 / 0.8
25.4 / 1.0
CENTRIFUGAL
2
PLASTIC
BELT DRIVE
384.5 / 15.1
374.0 / 14.7
THREE PHASE SQUIRREL CAGE
INDUCTION MOTOR
1
IP22
B
380-415 / 3 / 50
2200
3.80
2200
4
S.I.G.C
9.52 / 3/8
0.33 / 0.013
ALUMINIUM
0.11 / 0.004
2 x 0.57 / 2 x 6.12
3
15
5333 / 11300
70
PROPELLER
2
GALVANISED STEEL
DIRECT DRIVE
660.4 / 26.0
THREE PHASE INDUCTION MOTOR
2
IP44
F
380-415 / 3 / 50
1280
2.70
550
6
SCROLL
2
POE
2510 / 88.3
F
380 - 415 / 3 / 50
N/A
13720
25.6
95
S.I.G.C
9.52 / 3/8
0.33 / 0.013
ALUMINIUM
0.11 / 0.004
2 x 1.25 / 2 x 13.44
2
16
1200 / 47.2
1990 / 78.3
1670 / 65.7
1320 / 52.0
2100 / 82.7
1810 / 71.3
665 / 1466
FILTER (OPTINAL)
2
840 / 33.1
667 / 26.3
25.4 / 1
ELECTRO GALVANISED STEEL
PE / 10mm

UATP200AY1X
190,000
55,686
25,100
43.8
7.6
R407C / CAPILLARY TUBE
2 x 4.2 / 2 x 9.3
380 - 415 / 3 / 50
DUCTED
AUTOTRANSFORMER
3167 / 6710
200 / 0.8
25.4 / 1.0
CENTRIFUGAL
2
PLASTIC
BELT DRIVE
384.5 / 15.1
374.0 / 14.7
THREE PHASE SQUIRREL CAGE
INDUCTION MOTOR
1
IP22
B
380-415 / 3 / 50
3500
4.90
3700
4
S.I.G.C
9.52 / 3/8
0.33 / 0.013
ALUMINIUM
0.11 / 0.004
2 x 0.57 / 2 x 6.12
4
15
5333 / 11300
70
PROPELLER
2
GALVANISED STEEL
DIRECT DRIVE
660.4 / 26.0
THREE PHASE INDUCTION MOTOR
2
IP44
F
380-415 / 3 / 50
1280
2.70
550
6
SCROLL
2
POE
3250 / 114.4
F
380 - 415 / 3 / 50
N/A
20320
36.2
125
S.I.G.C
9.52 / 3/8
0.33 / 0.013
ALUMINIUM
0.11 / 0.004
2 x 1.25 / 2 x 13.44
3
16
1200 / 47.2
1990 / 78.3
1670 / 65.7
1320 / 52.0
2100 / 82.7
1810 / 71.3
765 / 1687
FILTER (OPTINAL)
2
840 / 33.1
667 / 26.3
25.4 / 1
ELECTRO GALVANISED STEEL
PE / 10mm

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
2) ALL UNITS ARE BEING TESTED AND COMPLY TO IS0 13253
3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING -27C DB/ 19C WB INDOOR AND 35C DB / 24C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE MEASURED IN SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.
5) S.I.G.C - SEAMLESS INNER GROOVED COPPER

TM-UAT-1114-B

General Data - Cooling Only (R407C)

10

General Data - Cooling Only (R407C)


MODEL

Btu/hr
W
W
A
Btu/hr / W

COOLING CAPACITY
TOTAL INPUT POWER
TOTAL RUNNING CURRENT
EER
REFRIGERANT TYPE / CONTROL
REFRIGERANT CHARGE
POWER SOURCE

kg / Ib
V/Ph/Hz

AIR DISCHARGE
CONTROL
OPERATION
AIR FLOW
EXTERNAL STATIC PRESSURE
CONDENSATE DRAIN SIZE
TYPE
QUANTITY
MATERIAL
FAN
DRIVE
DIAMETER
LENGTH

l/s / CFM
Pa / in.wg.
mm / in

mm/in
mm/in

TYPE
EVAPORATOR
FAN MOTOR

TM-UAT-1114-B

COIL

11

QUANTITY
INDEX OF PROTECTION (IP)
INSULATION GRADE
POWER SOURCE
RATED INPUT POWER
RATED RUNNING CURRENT
MOTOR OUTPUT
POLES
MATERIAL
DIAMETER
TUBE
THICKNESS
MATERIAL
THICKNESS
FACE AREA
FIN
ROW
FIN PER INCH

AIR FLOW
SOUND PRESSURE LEVEL
TYPE
QUANTITY
FAN
MATERIAL
DRIVE
DIAMETER
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
INSULATION GRADE
FAN MOTOR
POWER SOURCE
RATED INPUT POWER
RATED RUNNING CURRENT
MOTOR OUTPUT
POLES
TYPE
CONDENSER
QUANTITY
OIL TYPE
OIL AMOUNT
INSULATION GRADE
COMPRESSOR
POWER SOURCE
CAPACITOR
RATED INPUT POWER
RATED RUNNING CURRENT
LOCKED ROTOR AMP.
MATERIAL
TUBE
DIAMETER
THICKNESS
MATERIAL
COIL
THICKNESS
FIN
FACE AREA
ROW
FIN PER INCH
HEIGHT
UNIT DIMENSION
WIDTH
DEPTH
HEIGHT
PACKING DIMENSION WIDTH
DEPTH
UNIT WEIGHT
TYPE
QUANTITY
AIR QUALITY
FILTER RAIL
LENGTH
SIZE
WIDTH
THICKNESS
MATERIAL
CASING
INSULATION / THICKNESS

V/Ph/Hz
W
A
W
mm/in
mm/in
mm/in
m2/ ft2

l/s / CFM
dBA

mm / in

V/Ph/Hz
W
A
W

cm3 / fl.oz
V/Ph/Hz
F
W
A
A
mm / in
mm / in
mm/ in
m2/ ft2
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/Ib
pc
mm/in
mm/in
mm/in

UATP250AY1X
230,000
67,409
28,700
53.0
8.0
R407C / TXV
2 x 9.6 / 2 x 21.2
380 - 415 / 3 / 50
DUCTED
AUTOTRANSFORMER
3776 / 8000
300 / 1.2
25.4 / 1.0
CENTRIFUGAL
1
GALVANISED STEEL
BELT DRIVE
457.2 / 18
480 / 18.9
THREE PHASE SQUIRRE
CAGE INDUCTION MOTOR
1
IP54
F
380-415 / 3 / 50
4700
9.10
5500
4
SEAMLESS COPPER
9.52 / 3/8
0.33 / 0.013
ALUMINIUM
0.11 / 0.004
2 x 0.91 / 2 x 9.84
4
14
9439 / 20000
74
PROPELLER
2
GALVANISED STEEL
DIRECT DRIVE
812.8 / 32.0
THREE PHASE INDUCTION MOTOR
2
IP54
F
380-415 / 3 / 50
4200
7.2
1500
6
SCROLL
2
POE
3250 / 114.4
F
380 - 415 / 3 / 50
N/A
19800
36.7
125
SEAMLESS COPPER
9.52 / 3/8
0.33 / 0.013
ALUMINIUM
0.11 / 0.004
2 x 3.0 / 2 x 32.44
2
14
1735 / 68.3
2200 / 86.6
2720 /107.1
1900 / 75
2250 / 88.5
2900 / 114
1200 / 2646
FILTER (OPTIONAL)
2
1370 / 53.9
735 / 28.9
50.8 /2
ELECTRO GALVANISED STEEL
PE / 10mm

UATP300AY1X
283,000
82,943
40,160
68.5
7.0
R407C / TXV
2 x 10.4 / 2 x 22.9
380 - 415 / 3 / 50
DUCTED
AUTOTRANSFORMER
4389 / 9300
300 / 1.2
25.4 / 1.0
CENTRIFUGAL
1
GALVANISED STEEL
BELT DRIVE
457.2 / 18
480 / 18.9
THREE PHASE SQUIRRE
CAGE INDUCTION MOTOR
1
IP54
F
380-415 / 3 / 50
6700
11.70
7500
4
S.I.G.C
9.52 / 3/8
0.33 / 0.013
ALUMINIUM
0.11 / 0.004
2 x 0.91 / 2 x 9.84
4
14
9439 / 20000
74
PROPELLER
2
GALVANISED STEEL
DIRECT DRIVE
812.8 / 32.0
THREE PHASE INDUCTION MOTOR
2
IP54
F
380-415 / 3 / 50
4200
7.2
1500
6
SCROLL
2
POE
4140 / 145.7
F
380 - 415 / 3 / 50
N/A
29260
49.6
198
S.I.G.C
9.52 / 3/8
0.33 / 0.013
ALUMINIUM
0.11 / 0.004
2 x 3.0 / 2 x 32.44
2
14
1735 / 68.3
2200 / 86.6
2720 /107.1
1900 / 75
2250 / 88.5
2900 / 114
1350 / 2976
FILTER (OPTIONAL)
2
1370 / 53.9
735 / 28.9
50.8 /2
ELECTRO GALVANISED STEEL
PE / 10mm

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
2) ALL UNITS ARE BEING TESTED AND COMPLY TO IS0 13253
3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING -27C DB/ 19C WB INDOOR AND 35C DB / 24C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE MEASURED IN SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.
5) S.I.G.C - SEAMLESS INNER GROOVED COPPER

MODEL

Btu/hr
W
W
A
Btu/hr / W

COOLING CAPACITY
TOTAL INPUT POWER
TOTAL RUNNING CURRENT
EER
REFRIGERANT TYPE / CONTROL
REFRIGERANT CHARGE
POWER SOURCE

kg / Ib
V/Ph/Hz

AIR DISCHARGE
CONTROL
OPERATION
AIR FLOW
EXTERNAL STATIC PRESSURE
CONDENSATE DRAIN SIZE
TYPE
QUANTITY
MATERIAL
FAN
DRIVE
DIAMETER
LENGTH

l/s / CFM
Pa / in.wg.
mm / in

mm/in
mm/in

TYPE
EVAPORATOR
FAN MOTOR

COIL

QUANTITY
INDEX OF PROTECTION (IP)
INSULATION GRADE
POWER SOURCE
RATED INPUT POWER
RATED RUNNING CURRENT
MOTOR OUTPUT
POLES
MATERIAL
DIAMETER
TUBE
THICKNESS
MATERIAL
THICKNESS
FACE AREA
FIN
ROW
FIN PER INCH

AIR FLOW
SOUND PRESSURE LEVEL
TYPE
QUANTITY
FAN
MATERIAL
DRIVE
DIAMETER
TYPE
QUANTITY
INDEX OF PROTECTION (IP)
INSULATION GRADE
FAN MOTOR
POWER SOURCE
RATED INPUT POWER
RATED RUNNING CURRENT
MOTOR OUTPUT
POLES
TYPE
CONDENSER
QUANTITY
OIL TYPE
OIL AMOUNT
INSULATION GRADE
COMPRESSOR
POWER SOURCE
CAPACITOR
RATED INPUT POWER
RATED RUNNING CURRENT
LOCKED ROTOR AMP.
MATERIAL
TUBE
DIAMETER
THICKNESS
MATERIAL
COIL
THICKNESS
FIN
FACE AREA
ROW
FIN PER INCH
HEIGHT
UNIT DIMENSION
WIDTH
DEPTH
HEIGHT
PACKING DIMENSION WIDTH
DEPTH
UNIT WEIGHT
TYPE
QUANTITY
AIR QUALITY
FILTER RAIL
LENGTH
SIZE
WIDTH
THICKNESS
MATERIAL
CASING
INSULATION / THICKNESS

V/Ph/Hz
W
A
W
mm/in
mm/in
mm/in
m2/ ft2

l/s / CFM
dBA

mm / in

V/Ph/Hz
W
A
W

cm3 / fl.oz
V/Ph/Hz
F
W
A
A
mm / in
mm / in
mm/ in
m2/ ft2
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/Ib
pc
mm/in
mm/in
mm/in

UATP360AY1X
331,000
97,011
41,870
74.2
7.9
R407C / TXV
14.5 / 32.0 & 18.0 / 39.7
380 - 415 / 3 / 50
DUCTED
AUTOTRANSFORMER
5191 / 11000
300 / 1.2
25.4 / 1.0
CENTRIFUGAL
1
GALVANISED STEEL
BELT DRIVE
560 / 22
457 / 18
THREE PHASE SQUIRREL
CAGE INDUCTION MOTOR
1
IP44
F
380-415 / 3 / 50
5870
11.30
5107
4
S.I.G.C
9.52 / 3/8
0.33 / 0.013
ALUMINIUM
0.11 / 0.004
3.02 / 32.5
3&4
14 & 13
9439 / 20000
70
PROPELLER
2
GALVANISED STEEL
DIRECT DRIVE
812.8 / 32.0
THREE PHASE INDUCTION MOTOR
2
IP54
F
380-415 / 3 / 50
4500
8.4
3465
6
SCROLL
2
160 SZ & 300 SZ
6600 / 232.3 & 8000 / 281.6
N/A
380 - 415 / 3 / 50
N/A
31500
54.5
175 & 215
S.I.G.C
9.52 / 3/8
0.33 / 0.013
ALUMINIUM
0.11 / 0.004
3.50 / 37.7
2&3
14 & 13
1974 / 77.7
2252 / 88.7
3100 / 122.0
2150 / 84.5
2300 / 90.5
3250 / 128.0
1600 / 3527
FILTER (OPTIONAL)
2&4
860 / 33.86
505 / 19.88 & 600 / 23.62
50.8 /2
ELECTRO GALVANISED STEEL
PE / 10mm

UATP420AY1X
415,000
121,630
48,800
83.7
8.5
R407C / TXV
2 x 18.0 / 2 x 39.7
380 - 415 / 3 / 50
DUCTED
AUTOTRANSFORMER
5899 / 12500
300 / 1.2
25.4 / 1.0
CENTRIFUGAL
1
GALVANISED STEEL
BELT DRIVE
560 / 22
457 / 18
THREE PHASE SQUIRREL
CAGE INDUCTION MOTOR
1
IP44
F
380-415 / 3 / 50
7500
13.30
6525
4
S.I.G.C
7.0 / 0.28
0.28 / 0.011
ALUMINIUM
0.11 / 0.004
3.02 / 32.5
4
13
9439 / 20000
70
PROPELLER
2
GALVANISED STEEL
DIRECT DRIVE
812.8 / 32.0
THREE PHASE INDUCTION MOTOR
2
IP54
F
380-415 / 3 / 50
4500
8.4
3465
6
SCROLL
2
320 SZ
8000 / 281.6
N/A
380 - 415 / 3 / 50
N/A
36800
62.0
215
S.I.G.C
9.52 / 3/8
0.33 / 0.013
ALUMINIUM
0.11 / 0.004
3.50 / 37.7
3
13
1974 / 77.7
2252 / 88.7
3100 / 122.0
2150 / 84.5
2300 / 90.5
3250 / 128.0
1600 / 3527
FILTER (OPTIONAL)
2&4
860 / 33.86
505 / 19.88 & 600 / 23.62
50.8 /2
ELECTRO GALVANISED STEEL
PE / 10mm

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
2) ALL UNITS ARE BEING TESTED AND COMPLY TO IS0 13253
3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING -27C DB/ 19C WB INDOOR AND 35C DB / 24C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE MEASURED IN SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.
5) S.I.G.C - SEAMLESS INNER GROOVED COPPER

TM-UAT-1114-B

General Data - Cooling Only (R407C)

12

Safety Devices (R22)


MODEL

UAT60AY1X
TYPE
HIGH PRESSURE SWITCH

SAFETY
DEVICE

NC

OPEN

kPa/psi

3241 / 470

CLOSE

kPa/psi

2648 / 384

TYPE
LOW PRESSURE SWITCH

N/A

OPEN

kPa/psi

CLOSE

kPa/psi

N/A
N/A
YES

PHASE SEQUENCER
DISCHARGE THERMOSTAT SETTING

125 / 257

C / F

MODEL

UAT100AY1X
TYPE
HIGH PRESSURE SWITCH

SAFETY
DEVICE

NC
kPa/psi

3241 / 470

CLOSE

kPa/psi

2648 / 384

TYPE
LOW PRESSURE SWITCH

N/A

OPEN

kPa/psi

N/A

CLOSE

kPa/psi

N/A

PHASE SEQUENCER

YES
C / F

MODEL

125 / 257

UAT150CY1X
TYPE
HIGH PRESSURE SWITCH

NC
kPa/psi

3241 / 470

CLOSE

kPa/psi

2648 / 384

OPEN

kPa/psi

48/7

CLOSE

kPa/psi

152/22

C / F

YES
125/257

TYPE
LOW PRESSURE SWITCH

DISCHARGE THERMOSTAT SETTING

NC

MODEL

UAT240CY1X
TYPE
HIGH PRESSURE SWITCH

NC
kPa/psi

3241 / 470

CLOSE

kPa/psi

2648 / 384

OPEN

kPa/psi

48/7

CLOSE

kPa/psi

152/22

C / F

125/257

TYPE
LOW PRESSURE SWITCH

NC

YES

DISCHARGE THERMOSTAT SETTING

MODEL

UAT360AY1X
TYPE
HIGH PRESSURE SWITCH

TM-UAT-1114-B

13

UAT300CY1X

OPEN

PHASE SEQUENCER

SAFETY
DEVICE

UAT180CY1X

OPEN

PHASE SEQUENCER

SAFETY
DEVICE

UAT120AY1X

OPEN

DISCHARGE THERMOSTAT SETTING

SAFETY
DEVICE

UAT80AY1X

NC

OPEN

kPa/psi

2937 / 426

CLOSE

kPa/psi

2413 / 350

TYPE
LOW PRESSURE SWITCH

UAT420AY1X

N/A

OPEN

kPa/psi

CLOSE

kPa/psi

PHASE SEQUENCER
DISCHARGE THERMOSTAT SETTING

N/A
N/A
YES

C / F

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

N/A

Safety Devices (R407C)


MODEL

UATP60AY1X
TYPE

SAFETY
DEVICE

NC

OPEN

kPa/psi

3241 / 470

CLOSE

kPa/psi

2648 / 384

TYPE
LOW PRESSURE SWITCH

N/A

OPEN

kPa/psi

N/A

CLOSE

kPa/psi

N/A

PHASE SEQUENCER
DISCHARGE THERMOSTAT SETTING

N/A
125 / 257

C / F

MODEL

UATP100AY1X
TYPE
HIGH PRESSURE SWITCH

SAFETY
DEVICE

NC

OPEN

kPa/psi

3241 / 470

CLOSE

kPa/psi

2648 / 384

TYPE
LOW PRESSURE SWITCH

N/A

OPEN

kPa/psi

N/A

CLOSE

kPa/psi

N/A

PHASE SEQUENCER
DISCHARGE THERMOSTAT SETTING

N/A
125 / 257

C / F

MODEL

UATP150AY1X
TYPE
HIGH PRESSURE SWITCH

SAFETY
DEVICE

NC
kPa/psi

3241 / 470

CLOSE

kPa/psi

2648 / 384

TYPE
LOW PRESSURE SWITCH

N/A

OPEN

kPa/psi

CLOSE

kPa/psi

N/A

C / F

YES
N/A

DISCHARGE THERMOSTAT SETTING

MODEL

N/A

UATP250AY1X
TYPE
HIGH PRESSURE SWITCH

NC
kPa/psi

3241 / 470

CLOSE

kPa/psi

2648 / 384

TYPE
LOW PRESSURE SWITCH

UATP300AY1X

OPEN

N/A

OPEN

kPa/psi

CLOSE

kPa/psi

N/A
N/A

PHASE SEQUENCER

YES

DISCHARGE THERMOSTAT SETTING

N/A

C / F

MODEL

UATP360AY1X
TYPE
HIGH PRESSURE SWITCH OPEN
CLOSE

SAFETY
DEVICE

UATP200AY1X

OPEN

PHASE SEQUENCER

SAFETY
DEVICE

UATP120AY1X

NC
kPa/psi

3241 / 470

kPa/psi

2648 / 384

TYPE
LOW PRESSURE SWITCH

N/A

OPEN

kPa/psi

CLOSE

kPa/psi

PHASE SEQUENCER
DISCHARGE THERMOSTAT SETTING

UATP420AY1X

N/A
N/A
YES

C / F

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

N/A

TM-UAT-1114-B

HIGH PRESSURE SWITCH

UATP80AY1X

14

4. Selection Process
The following are the design requirements for UAT100A unit:
Model:
UAT100A
Supply Air Quantity
=
3800
CFM
External Static Pressure
=
150
Pa
Step 1:

From the blower curve (at 3800 CFM),


Standard operating system;
Internal Static Pressure =

160

Pa

Step 2:

Therefore at 3800 CFM and 150 Pa external static pressure,


Total Static Pressure =
150 + 160
Pa
=
310
Pa

Step 3:

From the blower curve, the design requirement calls for RPM about 1380 RPM.
From the table:
Motor pulley =
Blower pulley =
Motor RPM
=

106
125
1420

mm
mm

In order to obtain 1380 RPM, we calculate the new blower pulley as:
(while maintaining the motor pulley)
Db
=
106 x (1420/1380)
=
109.07mm
Let us take close approximation of 110 mm diameter pulley size
Recheck, with Db = 110 mm
Blow pulley =
=

1420 x (106/110)
1368.4 RPM

We thus need to change the blower pulley from 125 mm to 110 mm in order to obtain the
higher operating static pressure.
Step 3:

When the pulley is changed, the V-belt length must be rechecked. We have for horizontal
air throw configuration:
V-belt length, L =
2C + 1.57 (Db + Dm)
=
(2 x 174) + 1.57(110 + 106)
=
687.12
We thus can use a belt with a length of 687 mm.
where, C
Db
Dm

Step 4:

TM-UAT-1114-B

distance between the centres of the two pulleys


diameter of blower pulley
diameter of motor pulley

From the blower curve, we can also notice that the motor power input has maintained
within the current operating range of the standard unit's motor.
Summary:
i) Fan motor kW
ii) Blower pulley diameter
iii) V-belt size

15

=
=
=

=
=
=

2.2
110
687

kW
mm
mm

Note: Factory supplied rooftop is only with standard drive package.


All other changes are only given as example and need to be field supply.

The following table summarizes the pulley data, motor size used for the UAT/UATP series, as manufactured:
Blower Pulley,Db
Type
Diameter (mm)

Motor Pulley, Dm
Type
Diameter (mm)

V-belt length , L
Type
Length (mm)

UAT(P)60AY1X

SPZ 1

125

SPZ 1

95

SPZ

750

UAT(P)80AY1X

SPZ 1

140

SPZ 1

100

SPZ

737

UAT(P)100AY1X

SPZ 1

125

SPZ 1

106

SPZ

710

UAT(P)120AY1X

SPZ 1

125

SPZ 1

106

SPZ

710

UAT150CY1X

SPZ 2
SPA 2

132
160

SPZ 2
SPA 2

75
90

SPZ
SPA

737
782

SPZ 2
SPA 2

160
170

SPZ 2
SPA 2

106
100

SPZ
SPA

812
757

SPZ 2
SPZ 2

200
224

SPZ 2
SPZ 2

95
125

SPZ
SPZ

887
1662

UATP300AY1X

SPZ 3
SPZ 2

150
224

SPZ 3
SPZ 2

95
140

SPZ
SPZ

900
1700

UAT(P)360AY1X

SPA

280

VPT

139

SPA

2132

UAT(P)420AY1X

SPA

250

VPT

139

SPA

2060

UATP150AY1X
UAT180CY1X
UATP200AY1X
UAT240CY1X
UATP250AY1X
UAT300CY1X

Model

Pulley Centre Distance, C (mm)


Nominal
Minimum
Maximum

Motor (kW)

Motor (RPM)

UAT(P)60AY1X

203

203

245

0.75

1420

UAT(P)80AY1X

180

175

190

1.1

1420

UAT(P)100AY1X

174

170

185

1.5

1420

UAT(P)120AY1X

174

170

185

1.5

1420

UAT150CY1X

191

175

205

2.2

1420

UATP150AY1X

195
191

190
191

205
210

2.2
3

1430
1420

UAT240CY1X

167
205

165
195

180
215

3.7
3.7

1430
1430

UATP250AY1X

558

558

572

5.5

1440

UAT300CY1X

256
565

210
558

280
572

5.5
7.5

1430
1440

UAT180CY1X
UATP200AY1X

UATP300AY1X
UAT(P)360AY1X

748

730

763

7.5

1440

UAT(P)420AY1X

739

730

763

7.5

1440

TM-UAT-1114-B

Model

16

UAT(P)60AY1X
RPM

300

0.75 kW

250

0.55 kW

Total Static Pressure (Pa)

1050

Standard
Point

200

1000

150

900
800

100

Internal Static
Pressure

TM-UAT-1114-B

50

17

0
1500

1600

1700

1800

1900

2000

710

760

800

850

900

950

2055-044

Air Flow

2100 CFM

1000

L/S

RPM

UAT(P)80AY1X

1.5 kW
300

1300

1.1 kW

200

Standard
Point

1100

1000
100

900

0
2300
1090

2400

2500

2600
1200

2700

2800
1300

Internal Static
Pressure

2900

3000
1400

3100

3200
1500

3300 CFM
1560

L/s

Air Flow
2055-0

TM-UAT-1114-B

Total Static Pressure (Pa)

1200

18

400

RPM

UAT(P)100AY1X

2.2 kW
1.5 kW

350

300

1.1 kW

1400

Total Static Pressure (Pa)

250

Standard
Point

1300

200

1200
150

1100

Internal
Static
Pressure

1000

100

50

0
2800

TM-UAT-1114-B

1320

19

3000

3200

1450

3400

3600

1590

1720

Air Flow

3800

4000

1850

4200

1980

CFM
L/S

400

RPM

UAT(P)120AY1X

2.2 kW
1.5 kW

350

300

1.1 kW

1400

Standard
Point

1300

200

1200
150

1100

Internal
Static
Pressure

1000

100

50

0
2800

1320

3000

3200

1450

3400

3600

1590

1720

Air Flow

3800

4000

1850

4200

1980

CFM
L/S

TM-UAT-1114-B

Total Static Pressure (Pa)

250

20

TM-UAT-1114-B

UAT150CY1X

21

RPM

UATP150AY1X
500

1000

3.0 kW
450

400

900

2.2 kW

350

Standard
Point

300

250

700

1.5 kW

200

150

600
Internal
Static
Pressure

100

50

0
4500

5000

5500

6000

6500

6800

2120

2360

2600

2830

3070

3200

Air Flow
2055-052

CFM
L/S

TM-UAT-1114-B

Total Static Pressure (Pa)

800

22

TM-UAT-1114-B

UAT180CY1X

23

At 6400cfm: 182+500 = 682cfm

RPM

UATP200AY1X
650

1200

600

1100

550

3.7 kW

1000

500

400

Standard
Point

3.0 kW

900

350

800
300

250

700
200

Internal
Static
Pressure

150

100
5400

5900

6400

6900

7400

7900

2550

2780

3020

3260

3490

3730

Air Flow
2055-053

CFM
L/S

TM-UAT-1114-B

Total Static Pressure (Pa)

450

24

TM-UAT-1114-B

UAT240CY1X

25

UATP250AY1X

RPM

800

5.5 kW
750

1000

700

650

900
600

4.0 kW
Standard
Point

Total Static Pressure (Pa)

550

500

800

450

400

350

700

300

600

250

Internal
Static
Pressure

200

150

3020

2055-045

6900

3010

7400

3450

7900

3670

8400

3880

Air Flow

8900

4100

9400

4300

CFM
4530 L/S

TM-UAT-1114-B

100
6400

26

TM-UAT-1114-B

UAT300CY1X

27

UATP300AY1X

RPM

900

7.5 kW
850

800

5.0 kW
750

1000
700

650

900
550

500

450

4.0kW
400

800
350

700

300

Internal
Static
Pressure

250

200

150

100
7700

8200

8700

9200

9700

10200

10700

11200 CFM

3640

3870

4110

4340

4580

4820

5050

5290

2055-046

Air Flow

L/S

TM-UAT-1114-B

Total Static Pressure (Pa)

600

28

UAT(P)360AY1X

RPM

900

850

800

750

7.5 kW

800

700

650

Total Static Pressure (Pa)

600

550

700
5.5 kW
Standard
Point

500

4.0kW
450

600
400

350

300

500
250

Internal Static
Pressure

200

150

TM-UAT-1114-B

100
8800

29

4160

2055-047

9300

4440

9800

10300

4750

10800

5050

11300

5340

Air Flow

11800

5620

12300

12800

5780

CFM
6280 L/S

1000

RPM

UAT(P)420AY1X

11.0 kW

950
900
850
800
750

800
7.5 kW

650

Standard
Point

600
550

700

5.5kW

500
450
400

600

350
300

500

250

Internal Static
Pressure

200
150
100
10000

4720

10500

5060

11000

11500

5390

12000

12500

5720

13000

6070

Air Flow
2055-048

13500

6400

14000

14500

6730

15000 CFM

7080

L/S

TM-UAT-1114-B

Total Static Pressure (Pa)

700

30

5. Application Information
Ensure the operating temperature is in allowable range.

Cooling (R22) - C Series


Outdoor DB temperature (C)

Cooling (R22) - A Series

Outdoor temp. (C DB)

52
50
40
30
20
10
0

54
52

19

14

10

15

20

24 25

30

19.4

23

Indoor temp. (C WB)

Indoor temp. (C WB)

Cooling (R407C)

Outdoor temp. (C DB)

50
46
40

Caution :

30

The use of your air conditioner


outside the range of working
temperature and humidity can
result in serious failure.

20
10
0

10

15

20

24 25

TM-UAT-1114-B

Indoor temp. (C WB)

31

30

Refrigerant Circuit Diagaram

TM-UAT-1114-B

Model : UAT(P)60AY1X

32

TM-UAT-1114-B

Model : UAT(P)80/100AY1X

33

TM-UAT-1114-B

Model : UAT(P)120AY1X

34

TM-UAT-1114-B

Model : UATP150/200AY1X

35

TM-UAT-1114-B

Model : UATP250/300AY1X

36

Model : UAT(P)360/420AY1X

TM-UAT-1114-B

COMP1

37

Model : UAT150/180/240/300CY1X

HEADER
IN

HEADER

HEADER
OUT

DISTRIBUTOR
Thermal Expansion
Valve Sensor Bulb

TM-UAT-1114-B

Note: YRT150/180/240/300C consists of 2 circuits in the system.

38

6. Installations
Before installing the air conditioner unit, please read the following safety precautions carefully.

WARNING

Installation and maintenance should be performed by qualified persons who are familiar
with local code and regulation, and experienced with this type of appliance.
All field wiring must be installed in accordance with the national wiring regulation.
Ensure that the rated voltage of the unit corresponds to that of the name plate before
commencing wiring work
According to the wiring diagram.
The unit must be GROUNDED to prevent possible hazard due to insulation failure.
All electrical wiring must not touch the refrigerant piping, compressor and any moving parts
of the fan motors.
Confirm that the unit has been switched OFF before installing or servicing the unit.
Before installing the air conditioner unit, please read the following safety precautions carefully.

CAUTION

TM-UAT-1114-B

Please take note of the following important points when installing

39

Do not install the unit where leakage of flammable gas may occur

If gas leaks and accumulates around the unit, it may cause fire ignition.

Confirm drainage piping is connected properly

If the drainage piping is not connected perfectly, it may cause water leakage which will
dampen the furniture.

Do not overcharge the unit

This unit is factory pre-charged. Over charge will cause over current or damage to the
compressor.

Ensure that the unit panel is closed after service or installation.


Unsecured panel will cause unit to operate noisily.

Installation
All series of air conditioners are designed for outdoor installations and are to be placed on a slab or
rooftop. However, if the air conditioner is to be installed in a plant room, please contact your equipment
supplier prior to installation for further advise.
Access to the compressors, control wiring, and fans for service and installation purpose must be provided.
Please see item 1: Space Required Around Units for recommendations.

1. Location For Installation















- Install the unit in such way that air distributed by the unit cannot be drawn in again (as in the case
of short circuit of discharge air). Allow sufficient space for maintenance around the unit.
- When two or more units are installaed in a location, they must be positioned such that one unit will
not be traking the discharge air from another unit.
- Ensure that there is no obstruction of air flow into or out of the unit. Remove obstacles which block
air intake or air discharge.
- The location must be well ventilated, so that the unit can draw and distribute plenty of air.
- The unit is recommended to install in: A place capable of bearing the weight of the unit and isolating noise and vibration.
A place where has adequate drainage.
A place where the unit will not be buried in snow.
A place where air outlet port is not exposed to strong wind.
A place where the air discharge and operating sound level will not annoy the neighbours.
The location where it is not accesible by general public.

2. Space Required Around Units.

(1) Care must be taken to prevent recirculation of air. To stabilize compressor and condensing
pressure, it is recommended that wherever possible the condenser air inlet side should be
faced away from prevailing winds. Please see diagrams below.
(2) For rooftop installation, the type of mounting base depends on the construction of the roof.
A built-up roof may not support the weight of the unit. Hence, it may be necessary to support the
unit by adding structural members below it.

TM-UAT-1114-B

(3) The units are equipped with hoisting hangers for rigging and hoisting of the unit. Please see
item 3: Lifting method for further information.
The hoisting plates are located on the top of the unit. When hoisting the unit with a crane, spreader
bars must be used to prevent damage to side panels by the supporting cables.

40

UATP150/200AY1X

300

Evaporator
coil, air filter
service

(min clearance)
Condenser
inlet
300
500

Condenser
inlet

1000

300

UAT(P)60/80/100/120AY1X

300

Condenser
outlet

(unit : mm)

(min clearance)

condenser outlet

(unit : mm)

500

1000

(min clearance)
Condenser
inlet
500

Evaporator coil,
motor service

1000

UAT(P)360/420AY1X
2000

UATP250/300AY1X
Evaporator coil,
motor service
(min clearance)

Condenser
inlet

1500

Evaporator
coil, air filter
service

1000

Electrical
control circuit
& compressor
service

1500

1000

Evaporator coil,
air filter service

700

Electrical
control circuit
& compressor
service

700

(min clearance)
Condenser
inlet
1000

Electrical
control circuit
& compressor
service

1000

Electrical
control circuit
& compressor
service

1500

(min clearance)

1000
Condenser
inlet

TM-UAT-1114-B

41

condenser outlet

(unit : mm)

3000

2000

1000

500

500
Condenser
inlet

condenser outlet

(unit : mm)

Condenser
air inlet

1200

Condenser
air inlet

3000

Evaporator coil
& motor service,
Air filter service

1200

UAT150/180/240/300CY1X
Condenser
air outlet

Electrical
control circuit
service &
compressor
service

Evaporator coil,
air filter service

1200

Condenser
air inlet
Condenser
air inlet

3. Duct Construction.
(1) UAT(P) series side flow units are equipped with horizontal
supply and return air openings. Duct connection to the unit
should be made with duct flanges and secured directly to the
air openings with flexible duct connectors to avoid normal
noise transmission.

Duct connection with


a vertical air plenum
at UAT(P) side flow unit
UAT side flow unit

(2) For vertical air supply, a field supply plenum should be


used. The figure shows the recommended method for duct
connection.
(3) To prevent air leakage, all duct seams should be taped.
Duct runs in air spaces that are not air-conditioned must be
insulated and provided with a vapor barrier.

Ducts exposed outdoors must be weather proofed. For quiet
operation, we recommend that the insulation on the supply
duct be placed inside, lining the duct.
(4) Where ducts from outdoors enter a building, the duct openings
in the building should be sealed with weather stripping to
prevent rain, dirt, sand, etc. from entering the building.
(5) Correctly sized filters must be fitted. There is no provision
within the unit for the placement of filter. However, the filters
may be installed in the return air chamber.

TM-UAT-1114-B

(6) Duct earth wiring must be connected. Please refer to the


section Outlines and dimensions for the correct position.

42

4. Lifting Method

When the unit is to be lifted and moved, attach ropes to the hoisting
hangers (4 pieces) provided on the top corners of the unit.
When the unit is lifted, its center of gravity tends to shift the unit to
one side. Imbalance such as that in the figure should be attained.
The angles at which the ropes suspend the unit should be at least
60 at the compressor end and at least 45 at the condenser end.
Care should be taken to avoid contact with the unit while it is
being lifted.

Hook (as directly aligned


over the center of gravity
as possible)

The drain piping should have a drain trap.

5. Drain Piping

(1) The condensate drain fitting (R1) is provided. The drain pipe
can be led out at the right or left side. Please see Chapter 10:
Outlines & Dimensions for further details.
(2) The drain pipe must be provided with a trap on the outside of
the unit and also installed at an incline for proper drainage,
as shown below.
(3) To prevent condensate formation and leakage, provide the drain
pipe with insulation to safeguard against sweating.
(4) Upon completion of the piping work, check that there is no
leakage and that the water drains off properly.

6. Refrigerant Charge

An additional charge is unnecessary.


The table below shows the amount of the charge when the unit is shipped from the factory.
UAT60AY1X
Refrigerant charge
per circuit (kg)
Refrigerant charge
per circuit (kg)

Refrigerant charge
per circuit (kg)

TM-UAT-1114-B

Refrigerant charge
per circuit (kg)

43

5.2

UAT80AY1X
4.0

UAT180CY1X

UAT240CY1X

2 x 6.0

2 x 8.0

UATP60AY1X

UAT100AY1X
5.9
UAT300CY1X

UAT120AY1X
6.2

UAT150CY1X
2 x 4.6

UAT360AY1X

UAT420AY1X

2 x 10.6

16.5 , 19.5

2 x 19.5

UATP80AY1X

UATP100AY1X

UATP120AY1X

UATP150AY1X

4.6

4.6

5.9

5.6

2 x 3.9

UATP200AY1X

UATP250AY1X

UATP300AY1X

UATP360AY1X

UATP420AY1X

2 x 4.2

2 x 9.6

2 x 10.4

14.5 , 18.0

2 x 18.0

7. Special Precautions When Dealing With Refrigerant R407C Unit


(1) What Is New Refrigerant R407C?
R407C is a zeotropic refrigerant mixture which has Zero Ozone Depletion Potential (ODP = 0)
and thus, conforms to the Montreal Protocol regulation. It requires Polyol-ester (POE) oil for
its compressors lubricant. Its refrigerant capacity and performance are about the same as the
refrigerant R22.
(2) Components
Mixture of composition by weight: R32(23%), R125(25%), R134a(52%)
(3) Characteristic
R407C liquid and vapor components have different compositions when the fluid evaporates
or condenses. Hence, when a leak occurs and only vapor leaks out, the composition of the
refrigerant mixture left in the system will change and subsequently affect the system performance.
DO NOT add new refrigerant to a leaked system. It is recommended that the system should
be evacuated thoroughly before recharging with R407C.
When refrigerant R407C is used, the composition will differ depending on whether it is in gaseous
or liquid phase. Hence when charging R407C, ensure that only liquid is being withdrawn
from the cylinder or can. This is to make certain that only original composition of R407C is
being charged into the system.
POE oil is used as a lubricant for R407C compressor, which is different from the mineral oil used
for R22 compressor. Extra precaution must be taken to avoid exposing the R407C system to
moist air.
(4) Check List Before Installation/servicing
Tubing
Refrigerant R407C is more easily affected by dust of moisture compared with R22, make sure
to temporarily cover the ends of the tubing prior to installation
Compressor oil
No additional charge of compressor oil is permitted.
Refrigerant
No other refrigerant other that R407C
Tools
Tools specifically for R407C only (must not be used for R22 or other refrigerant)
i) Gauge manifold and charging hose
ii) Gas leak detector
iii) Refrigerant cylinder/charging cylinder
iv) Vacuum pump c/w adapter
v) Flare tools
vi) Refrigerant recovery machine

(a) Filter-dryer must be installed along the liquid line for all R407C air conditioners. This is to
minimise the contamination of moisture and dirt in the refrigerant system. Filter-dryer must be
of molecular sieve type. For a heat-pump system, install a two-way flow filter dryer along the
liquid line.
(b) During installation or servicing, avoid prolong exposure of the internal part of the refrigerant
system to moist air. Residual POE oil in the piping and components can absorb moisture from
the air.

TM-UAT-1114-B

(5) Handling And Installation Guidelines


Like R22 systems, the handling and installation of R407C systems are closely similar. All
precautionary measures; such as ensuring no moisture, no dirt or chips in the system, clean brazing
using nitrogen, and thorough leak check and vacuuming are equally important requirements.
However, due to the zeotropic nature of R407C and its hydroscopic POE oil, additional precautions
must be taken to ensure optimum and trouble-free system operation.

44

c) Ensure that the compressor is not exposed to open air for more than the recommended time
specified by its manufacturer (typically less than 10 minutes). Remove the seal-plugs only when
the compressor is about to be brazed.
d) The system should be thoroughly vacuumed to 1.0 Pa (-700mmHg) or lower. This vacuuming
level is more stringent than R22 system so as to ensure no incompressible gas and moisture in
the system.
e) When charging R407C, ensure that only liquid is being withdrawn from the cylinder or can.
This is to ensure that only the original composition of R407C is being delivered into the system.
The liquid composition can be different from the vapor composition.

R32/R125/R134
33% / 33% / 34%
23% / 25% / 52%

Composition of R407C in vapour phase


is different from liquid phase.

f) Normally, the R407C cylinder or can is being equipped with a dip-pipe for liquid withdrawal.
However, if the dip -pipe is not available, invert the cylinder or can so as to withdraw liquid from
the valve at the bottom.

Dip-pipe

Invert cylinder
without dip-pipe

Liquid
withdrawal

TM-UAT-1114-B


g) When servicing leaks, the top-up method, commonly practiced for R22 system, is not
recommended for R407C systems. Unlike R22 where the refrigerant is of a single component,
the composition of R407C (which is made-up of three different components) may have changed
during the leak. Consequently, atop-up may not ensure that the R407C in the system is of
the original composition. This composition shift may adversely affect the system performance.
It is recommended that the system be evacuated thoroughly before recharging with R407C.

45

8. Electric Wiring
Construct The Earth Connection.
All electrical work must be carried out by a suitable qualified electrical trades-person and in accordance
with local supply authority requirements and associated regulators.
The unit is to be wired directly from an electrical distribution board either by a circuit breaker (preferred)
or HRC fuse.
Fix power source wiring to control box by using buffer bushing for sensible force (PG connection or
the like). Connect control wiring to control terminal block through the knockout hole of control box
using ordinary bushing.
NOTE : Earth wiring must be connected.
Arrangement such as terminal block in control box.
Method For Connecting Electric Wire
Please carry out the wiring after consulting with local electric power company on local regulations.
(I) The entire wiring diagram of unit.

a.
b.
c.
d.
e

Power supply
Main switch/fuse (field supply)
Power supply wiring for unit
Unit

Earth

(II) Electrical wiring


Remove the panel on the right side of UAT(P)60-120AY1X or the rear side of UAT150-300CY1X,
UATP150-300AY1X and UAT(P)360-420A, and connect the units power supply wiring to the proper
terminals in the control box.
Connect the wires by following the wiring diagram.
(III) Wiring example and selection of earth leakage breaker

380~415V, 50Hz, 3
Power cable
2
(mm )

Breaker capacity
(A)

UAT(P)60AY1X

40

40

8 over

UAT(P)80AY1X

14

50

50

14 over

UAT(P)100AY1X

14

50

50

14 over

UAT(P)120AY1X

14

50

50

14 over

UAT150CY1X

16

48

63

16 over

UATP150AY1X

22

100

100

22 over

UAT180CY1X

25

57

63

25 over

UATP200AY1X

22

100

100

22 over

UAT240CY1X

35

72.5

80

35 over

UATP250AY1X

38

125

125

38 over

UAT300CY1X

35

85

100

35 over

UATP300AY1X

38

125

125

38 over

UAT(P)360AY1X

38

125

125

22 over

UAT(P)420AY1X

38

125

125

22 over

Over current
protection switch (A)

Earth cable
2
(mm )

The grounding wire must be of the same diameter as the power cable wires. The table above is an
example. The selection of other capacities should be determined in accordance with the relevant local
standards, in the country of installation.
Note: All electrical wiring must comply with local electrical authority regulations.

TM-UAT-1114-B

Model

46

Control Module UAT(P)60AY1X

47

TB4
N

TB3
N

L1

L2

L3

TB2

TB1

Terminal Block for


power supply wires

Control Module UAT80/100/120AY1X

TM-UAT-1114-B

Terminal Block for


power supply wires

47

Control Module UATP80/100/120AY1X

Terminal Block for


power supply wires

TM-UAT-1114-B

Control Module UAT150CY1X

48

Control Module UAT180/240CY1X

Control Module UATP150/200AY1X

TB8
N

TB7
N

N
N

47
N

Terminal Block for


power supply wires

TB1
L1

L2

L3

TB3
N

TM-UAT-1114-B

TB5

TB4

49

Control Module UATP250AY1X

Terminal Block for


power supply wires

TM-UAT-1114-B

Control Module UAT300CY1X

50

Control Module UATP300AY1X

Terminal Block for


power supply wires

TM-UAT-1114-B

Control Module UAT(P)360/420AY1X

51

Terminal Block for


power supply wires

9. The Putting Condition Of The Belt


1. Set the parallel angle of the fan and the motor pulley as shown in table 1 and figure 1.
2. Set the tension of one belt when the flexion load is within the range as shown in figure 2 and table
2 at the proper flexion. (A=0.016xC mm)
3. Adjust the suitable tension after the belt sit properly across the pulley (after working for 24-28 hours).
When a new belt is used, adjust the suitable tension about 1.3 times the maximum value of the
flexion load.
4. Readjust the belt every 2,000 hours after the first adjustment.
Exchange the belt when the belts surroundings length has expanded by 2% including the first
expansion (about 1%) of the belt (after approximately 8,000 hours converted working time).
Table 1
Pulley

Parallel angle

Pulley

K(i)
10 or less

Note
Gap of 3mm every 1 m

Table 2
Size of Pulley Motor
mm
inch
60-80
2.5-3.0
81-90
3.5
91-105
4
106-above
4.5-above

Flexion load
W(kgf)
1.1-1.4
1.3-1.7
1.6-2.0
1.9-2.9

10.Before Starting The Trial Run


After having installed the unit, check that :
(1) The unit is fixed securely.
(2) The unit is installed properly.
(3) The drain pipe is provided with a drain trap.
(4) The electrical wiring has been connected correctly and the terminal screws have been properly
tightened.
(5) The duct work has been performed correctly.

After the unit is turned on:


(1) Check that the fans are rotating in the proper direction.
(2) Check to see whether there are refrigerant leakage, and slack in power or transmission cable.
(3) Check the operation of high-pressure switch.
If the two lead wires of the outdoor unit fan motor are disconnected from the contactor and cooling
is performed, the high-pressure switch should function and stop the unit after 5 to 10 minutes.
Perform trial operation after completion of above items.

TM-UAT-1114-B

Before turning the unit on:


(1) Measure the resistance between the terminals of the electrical parts and ground to ensure that
the value is at least 1.0M ohm.
If the measured value is below 1.0M ohm, do not operate the unit.
(2) The unit is using a phase protector.
If wiring phase of power supply is mistaken, the unit does not run.
Please reconfirm and modify wiring phase.

52

11. Before Operating The Unit


1. Check points for operation


Check the following points before you operate your air conditioner.

(1) Check that there is nothing blocking the flow of air from the air outlet into the air inlet.

Indoor Side
Outlet grille

Inlet grille


Ceiling

Obstacle blocking air outlet

Ceiling

Obstacle blocking air inlet

(2) Make sure the air conditioner is properly grounded by checking the ground terminal.

Ground

TM-UAT-1114-B

53

2.






Caution for use


Keep the following points in mind to safeguard against failures and breakdowns.
For safety, confirm that the earth terminal has been connected to the earth wire correctly.
Never block or cover the units intakes or outlets.
It will reduce the units efficiency.
To start the unit again after it is stopped, ensure 3 minutes has elapsed before turning
the unit ON. Repeated stopping and starting within 3 minutes gives improper force to the
machine. This can cause the fuse or power source to trip.

7. Wiring Diagram
UAT(P)60AY1X

TM-UAT-1114-B

ROOPTOP UNIT MODEL: UAT(P)60AY1X

54

UAT(P)80/100/120AY1X

TM-UAT-1114-B

ROOFTOP UNIT MODEL: UAT(P)80/100/120AY1X

55

UATP150/200AY1X

TM-UAT-1114-B

ROOFTOP UNIT MODEL: UATP150/200AY1X

56

UAT150/180/240/300CY1X

TM-UAT-1114-B

ROOFTOP UNIT MODEL: UAT150/180/240/300CY1X

57

UATP250/300AY1X, UAT(P)360/420AY1X

ROOFTOP UNIT MODEL: UATP250/300AY1X


UAT(P)360/420AY1X

TM-UAT-1114-B

**AVAILABLE IN UATP300AY1X

58

8. Servicing and Maintenance


1.


For Superior Performance And Lasting


Durability, Please Do Not Forget To
Conduct Proper And Regular
Maintenance.

Warning

1.Do not wash the unit with water.


If washed with water, electrical shock may be caused.
2.Turn off power source.
For safety, turn the power source off before service work
to avoid electronical shock.


1.1 Cleaning The Air Filter

If using an air filter which is special order or field supplied, please refer to filter supplier for
maintenance and care instructions.

Clean more regularly if the air filter gets very dirty. If the filter gets blocked, air will not be sucked in
properly, and the cooling effect will deteriorate. Failure to clean the air filter may result in equipment
breakdown or malfunction.

1. Removing the air filter.


The air filter is mounted in the service panel.
(in front of the heat exchanger.)

2. The air filter is cleaned with cleaner or washed in clear water.


Please wash the dirty air filter in lukewarm water with neutral detergent.
Please do not use hot water of 50C or more, as it can deform the filter.
Do not scrub or wring dry the filter as this can damage the filter.
Rinse thoroughly and ensure there is no detergent remaining.
3. When the filter is washed in clear water, dry it under the shade.
Please do not dry under direct sunshine and direct fire.

Pull out the filter

Remove the service panel


4. The air filter is installed as before.

1.2





Cleaning Of Panel
Clean dirt off panel as follows.
Use a household neutral cleanser such as dishwashing
liquid. Moisten a soft cloth with the cleanser, then wipe lightly.
Next, wipe three or four times with another soft cloth moisten
with water.
Finally, wipe off all the remaining cleanser with a soft cloth.

Moisten a soft cloth with the alcohol, then wipe off lightly.
Isopropyl alcohol is sold at stores as reagents in small quantities.

Fingermarks
Grease
Adhesive
Paste

Note:
Alcohol is highly combustible. Take extreme care when
handing. Also, do not use paint or adhesive thinner.

TM-UAT-1114-B

1.3 Cleaning The Outdoor Heat Exchanger



If you use your air conditioner for prolonged periods, the outdoor
heat exchanger will become dirty, impairing its function and reducing the

air conditioners performance. Consult your equipment supplier or air

conditioning contractor on how to clean the heat exchanger.

59

1.4







Starting The Air Conditioner After Service Works


Please turn on the power supply after checking is done and no abnormality is found.
Please do the following work.
It is confirmed that air inlet and outlet are not blocked.
It is confirmed that the earth connection line does not come off.
The earth connection line is firmly installed in the unit.
It is confirmed that there is neither lifting, blocking, nor bending of the drain-hose.
1. The controller is in the OFF position.

2. The power supply switch is turned on.

Neutral
Cleanser

Isopropyl
alcohol

1.5







When The Air Conditioner Is Not To Be Used For A Long Time


If the air conditioner is not to be used for a long time due to seasonal change, etc.,
Please do the following work.
1. The power supply switch is turned off.
If the power supply is kept on, several watts or several tends of watts will be wasted.
The accumulation of dust, etc., can result in fire.
2. Filter, and drain pan must be cleaned. Pay attention to clean dust in the drain.
3. Run it for 4-5 hours with the air blowing until the inside is completely dry.
Failing to do so can result in the growth of unhygienic, unhealthy mold in scattered areas
throughout the room.

1.6






In Case Of Failure
(1) Never remodel the air conditioner by yourself. Consult your dealer for any repair service.
Improper repair work can result in water leakage, electric shock, fire, etc.
(2) If the power breaker is frequently activated, get in touch with your dealer.
Leaving the unit as it is under such conditions can result in fire or failure.
(3) If refrigerant gas blows out or leaks, stop the operation of the air conditioner.
Thoroughly ventilate the room, and contact your dealer.
Leaving the unit as it is can result in accidents due to oxygen deficiency.

2.1






Transfer Of Installation
(1) When removing and reinstalling the air conditioner, consult with your dealer in advance
to ascertain the cost of the professional engineering work required for transferring the
installation.
(2) Please do not use refrigerant other than the specified refrigerant when you top-up/
recharge the refrigerant at the new installation site .
(3) When moving or reinstalling the air conditioner, consult with your dealer.
Defective installation can result in electric shock, fire, etc.

2.2












Place For Installation


Please do not use the unit in the following places.
(1) Places with a lot of oil, moisture, and dust.
(2) Places with high salinities such as seaside.
(3) Places where sulfur gas, volatile gas, and corroded gas are filled.
(4) Places where acid solution is frequently used.
(5) Places where special spray is frequently used.
(6) Hot spring zones.
(7) Near to machines that generate high cycles (High cycle welding machine etc.).
(8) Places where ventilation entrance of unit is closed by snowfall.
(9) The unit must be installed on stable, level surface.
The consequence of using a unit in the places mentioned above is the main body might
corrode, the refrigerant might leak, the performance of the unit might decrease remarkably,
and it might cause damage of parts in the unit.

2.3








Regarding Electric Work


(1) The electrical work must be undertaken by a person who is qualified as an electrical
technician with respect to local governing laws.
(2) Please install the earth connection for the electric shock prevention.
(3) Never connect the grounding wire to a gas pipe, water pipe, arrestor, or telephone
grounding wires. For details, consult with your dealer.
(4) In some types of installation sites, the installation of an earth leakage breaker is

mandatory.
For details, consult with your dealer.
(5) The breaker and the fuse must be of correct capacity.

TM-UAT-1114-B

2. Transferring Work And Construction

60

TM-UAT-1114-B

61

2.4









Consideration Of The Noise


(1) Take sufficient measures against noise when installing the air conditioners at hospitals or
communications related businesses.
(2) If the air conditioner is used in any of the above-mentioned environments, frequent
operational failure can be expected. It is advisable to avoid these type of installation sites.
For further details, consult with your dealer.
(3) Choose a place where cool air and noise from the outdoor air outlet of the air conditioner
do not inconvenience the neighbors.
(4) Obstacles placed near the air outlet of the unit can decrease performance and increase
noise. Avoid placing any obstacles adjacent to the air outlet.
(5) If the air conditioner produces any abnormal sound, consult your dealer.

2.5



Disposing Of The Unit


When you need to dispose of the unit, consult your dealer.
If pipes are removed incorrectly, refrigerant (fluorocarbon gas) may blow out and come into
contact with your skin, causing injury. Releasing refrigerant into the atmosphere also
damages the environments.

2.6



Maintenance And Inspection


(1) If the air conditioner is used throughout several seasons, the inside can get dirty and
eventually reduce the performance.
(2) Depending upon the conditions of usage, foul odors can be generated and drainage can
deteriorate due to dust, dirt, etc.

9. Troubleshooting

No

Fault conditions

Possible causes / corrective actions

The air conditioner unit will not resume after


power failure.

The auto restart function is not functioning. Please


turn on the unit with the wireless / wired controller.

The compressor does not operate 3 minutes


after the air conditioner unit is started.

Protection against frequent starting.


Wait for 3 or 4 minutes for the compressor to start
operating by it self.

The airflow is too slow or room cannot be


cooled sufficiently.

The air filter is dirty.


The doors and windows are opened.
The air suction and discharge of both indoor and
outdoor units are clogged or blocked.
The regulated temperature or temperature setting
is not low enough.

Discharge airflow has bad odor.

Cigarettes, smoke particles, perfume and others,


which might have adhered onto the coil, may
cause odor.
Contact your nearest dealer.

Condensation on the front air grille of the indoor


unit.

This is caused by air humidity after an extended


period of operation.
The set temperature is too low. Increase the
temperature setting and operate the unit at high
fan speed.

Water flowing out from the air conditioner.

Switch off the unit and contact your nearest


dealer. This might be due to tilted installation.

Hissing airflow sound from the air conditioner


unit during operation.

Liquid refrigerant flowing into the evaporator coil.

The wireless controller display is dim.

The batteries are discharged.


The batteries are not correctly inserted.
The assembly is not good.

Compressor operates continuously.

Dirty air filter. Clean the air filter.


Temperature setting too low (cooling). Use higher
temperature setting.

10

No cool air comes out during cooling cycle.

Temperature setting too high (cooling). Use lower


temperature setting.

TM-UAT-1114-B

When a malfunction of the air conditioner unit is detected, immediately switch off the main power supply
before proceeding with the following troubleshooting procedures.
The following are common fault conditions and simple troubleshooting tips. If any other fault conditions which
are not listed occur, contact your nearest local dealer. DO NOT attempt to troubleshoot the unit by yourself.

62

Diagnostic Guidelines
By means of pressure reading :

High side
Low side

High side
Low side
High side
Low side

High side
Low side

TM-UAT-1114-B

High side
Low side

63

Probable cause

Too high

Normal

A little low

Circuit

Too low

Data

A little high

Pressure

1.
2.
3.
4.

1. Poor compression / no compression (compressor


defective)
2. Reversing valve leaking.
1.
2.
3.
4.

Overcharged with refrigerant.


Non-condensable gases in refrigerant circuit (e.g. air)
Obstructed air-intake / discharge.
Hot air short circuiting in outdoor unit.

Undercharged with refrigerant.


Refrigerant leakage.
Air filter clogged / dirty (indoor unit).
Indoor fan locked / seized.

1. Outdoor fan blocked (cooling).


2. Outdoor coil dirty (cooling).
3. Non-condensable gases in refrigerant circuit (e.g. air)
1. Air intake temperature of indoor unit too high.

By Means Of Diagnostic Flow Chart:

Generally, there are two kinds of problems, i.e. starting failure and insufficient cooling. Starting
failure is caused by electrical defect while improper application or defects in refrigerant circuit causes
Insufficient cooling .

The most common causes of air conditioner failure to start are :


a)Voltage not within 10% of rated voltage.
b)Power supply interrupted.
c)Improper control settings.
d)Air conditioner is disconnected from main power source.
e)Fuse blown or circuit breaker off.

TM-UAT-1114-B

i) Diagnosis of Electric Circuit

64

ii ) Diagnosis Of Refrigerant Circuit / Application


There might be some causes where the unit starts running but does not perform satisfactorily, i.e.
insufficient cooling. Judgement could be made by measuring temperature difference of indoor units
intake and discharge air as well as running current.

TM-UAT-1114-B

Satisfactory operation with temperature difference of air intake & discharge


of indoor unit 8C to 13C. *
( * value is for reference only )

65

10. Dimensional Data


UAT(P) - A Series
UAT(P)60AY1X
(unit : mm)

10

Except : Drain size. (unit : inch)


25
46

51

150 150 150 150

34

34

49
36
170

25

15

(1342)

25

B Detail

25

Hanger (4 places)

A Detail

230

31

360

15

265

(1342)

1000

25

265

46

51

25

540

16- 3 Holes

36

16- 3 Holes

4-15X25 Mtg. holes

200

170

Return air duct flange

1192

1100

1142

668

15 100 100 15

1100

10

1020

Supply air duct flange

10

49

20

232

125 125 125 125

20

200

10

668

Supply air
668

Control box

192

232

Supply
air

412

1000

200

Return
air

Condenser
Air inlet

Drain R 1

135

Return air

71

437

Wiring hole

50

1530

UAT(P)80/100/120AY1X
(unit : mm)
10

107

51

25
46

Except : Drain size. (unit : inch)

150 150 150 150 150 150

10

60

36

Hanger (4 places)

173

25
(1342)

15

25
A Detail

UAT(P)
80/100AY1X
ONLY

Control box
Return
air

Drain R 1

Condenser
Air inlet

437

50

Wiring hole
1530

TM-UAT-1114-B

Return air

71

173

412

1020

1000

107

Supply
air

135

Supply air

192

230

31

1020

170
36

B Detail

20- 3 Holes

(1342)

B
265

25

1000

46

4-15X25 Mtg. holes

25

25
15

20- 3 Holes

265

107

170

1392

1300

1342

Return air duct flange

51

15 100 100 15

1020

Supply air duct flange

10

10

1020

60

173

150 150 150 150 150 150

49

49
1300

60

60

1020

66

25

UATP150/200AY1X
1200

15

25

25

(2032)

123

X
UATP-A 1670

46

51

10

Detail A

72

200

200

200

200

200

200

200 200

72
49

1744

428

2082

2032

1990

1990

1744

Except : Drain size. (unit : inch)

Supply air & Return air


Duct flange

15

Detail B

25

25

46

B
235

(2032)

123
51

4-15X25 Mtg. holes

123

Hanger (4 places)

1744

Return air

123

428

123

1200

Supply air

Supply
air
Control box

169

428

51

1744

10

26- 3 Holes

25

235
123

34 120 120 120 34

(unit : mm)

Condenser
Air inlet

Condenser
Air inlet

Return
air

77

124

Return air

Condenser
Air inlet

483
50

UATP150/200AY1X ONLY

Drain R 1

Wiring hole

10

80

UATP250/300AY1X
43 120 120 120 120 43
566

383

Supply
air

22.5

20- 3

144

144

Except : Drain size. (unit : inch)

640
80 120 120 120 120 80

25

(unit : mm)

Supply air
duct Flange

10

25
144

144

23

Return air
duct flange

2850

2200
165

2768

566

758

100

80

50

2720

67

Condenser
air inlet

Condenser
air inlet

control
box

28- 3

10

Condenser
air inlet

320

510

TM-UAT-1114-B

640

Return
air

1302
1735

Supply air

10

80

383

51

Return
air

Detail A

80 150 150 150 150 80


758

1302
51 150 150 150 150 150 150 150 150

1146

2200
1912

27.5 15

80

Drain R1

wiring hole

UAT(P)360/420AY1X
(unit : mm)

Except : Drain size. (unit : inch)

TM-UAT-1114-B

3148

68

UAT - C Series
UAT150CY1X
142.0

652.0

994.0

684.0

652.0

855.0

1630.0

48.0.0

82.5

1800.0

82.5

94.0

1800.0

94.0

1988.0

1251.0

125.0

150.0

165.0

1390.0

CONTROL
BOX

700.0

350.0

50.0

1965.0

497.0

1748.0

UAT180CY1X
412.0

652.0

994.0

684.0

652.0

830.0

CONTROL
BOX

1988.0

150.0

1390.0

TM-UAT-1114-B

69

48.0

1251.0
1748.0

497.0

125.0

1630.0

1965.0

165 350.0 50.0

1710.0
82.5

1800.0

82.5

94.0

1800.0

94.0

UAT240CY1X
1045.0

456.0

994.0

1076.0

456.0

158.0

1981.0
1965.0

48.0

147.0

1672.0

147.0

158.0

1672.0

158.0

170 484.0

CONTROL
BOX

1988.0

150.0

200

768.0

1690.0

61.0

1905.0

1251.0
2021.0

770.0

UAT300CY1X
160.0

677.0

1215.0

1076.0

677.0

1000.0

2104.0

2030.0

48.0

151.0

2110.0

162.0

2110.0

149.0

2430.0

1371.0

770.0
2141.0

158.0

TM-UAT-1114-B

150.0

245.0

768.0

1650.0

CONTROL
BOX

407.0

138.0

88.0

2410.0

70

11. Exploded View & Part List


Model : UAT(P)60AY1X

34
35
29
4

33

22
30
31
38

32

6
42

20
21

28

15
8

16
26
19
23
27

41

43

40

14

36

TM-UAT-1114-B

13

71

12

11
3

10

17
18

25

24

37

39

44

NO

DESCRIPTION

NO

DESCRIPTION

1
2
3
4
5
6
7
8
9
10
11
12
13

ASSY, BASE PAN


STRUCTURE BASE RIGHT
STRUCTURE BASE LEFT
ASSY, PARTITION
LEG CASING (NO DOWM FLOW)
ASSY, PILLAR INDOOR 2
ASSY, PILLAR INDOOR 1
ASSY, COIL OUTDOOR
ASSY, DRAIN PAN
ASSY, COIL INDOOR
PLATE, BAFFLE RIGHT
PLATE, BAFFLE LEFT
ASSY, FRONT BEAM

14
15
16
17
18
19
20
21

RAIN, FILTER BOTTOM


ASSY, MOTOR BASE
ASSY, FAN FRAME
SUPPORT, MOTOR BASE
MOTOR
ASSY, FRONT PANEL
ASSY, BLOWER HOUSING
ASSY DRIVE PACKAGE
PULLEY, BLOWER B1*6*20MM
BELT, V B30 BANDO
PULLEY, NBK B1X4 BORE 19MM
SUPPORT, PARTITION
PARTITION, TUBING

22
23

Model : UAT(P)60AY1X

NO

DESCRIPTION

NO

DESCRIPTION

24
25
26
27
28
29
30
31
32
33
34

SUPPORT, ACCUMULATOR
ACCUMULATOR, PA5083-11-7-C
COMPRESSOR, ASSY
HEATER, CRANKCASE 70W 240V 018-0057-00
COVER, PARTITION TUBING
ASSY, PILLAR OD LEFT
ASSY, TOP PANEL REAR
ORIFICE (BELL MOUTH)
ASSY, MOTOR BRACKET (OUTDOOR)
MOTOR, H220-240/50-2 HONGLU
FAN GUARD

35
36
37
38
39
40
41
42
43
44

PANEL, TOP (INDOOR)


AIR FILTER
COVER, FILTER RIGHT
PANEL, SIDE LEFT
PANEL, SIDE RIGHT
ASSY, DUCT INTAKE
ASSY, DUCT DISCHARGE
ASSY, CONTROL BOX
PANEL, SERVICE
HANDLING HANDLES

TM-UAT-1114-B

1. ALL SPECIFICATION ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

72

Model : UAT(P)80/100AY1X

TM-UAT-1114-B

NO
1
2
3
4
5
6
7
8
9
10

73

DESCRIPTION
ASSY., BASE INDOOR
ASSY., BASE OUTDOOR
STRUCTURE BASE RIGHT
STRUCTURE BASE LEFT
ASSY., PARTITION
ASSY, DRAIN PAN
ASSY, COMPRESSOR BASE
ASSY., COMPRESSOR SUPPORT
ACCUMULATOR, P734972X02 TC399637-1 MIT
COMPRESSOR, ASSY

NO
11
12
13
14
15
16
17
18
19
20

DESCRIPTION
COMPRESSOR ITACHI
ASSY., COIL OUTDOORITACHI
ASSY., COIL OUTDOOR
COVER, COIL LEFT
ASSY., PILLAR OUTDOOR 1
ASSY., PILLAR OUTDOOR 2
ASSY., PILLAR INDOOR 1
ASSY., PILLAR INDOOR 2
ASSY., PANEL FRONT
ASSY., BEAM FRONT

Model : UAT(P)80/100AY1X

NO.
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45

DESCRIPTION
ASSY., COIL INDOOR
ASSY., COIL INDOOR
PLATE, BAFFIE RIGHT
PLATE, BAFFIE
PLATE, BAFFIE LEFT
FILTER RAIL, BOTTOM
ASSY., FAN FRAME
ASSY., MOTOR BASE
SUPPORT BASE
MOTOR, 1.1kW 50Hz R P714595x02 HITACHI
MOTOR, 1.1kW 50Hz R P714567x02 H
FAN BASE
ASSY., BLOWER HOUSING A
ASSY., BLOWER HOUSING B
FAN SIROCCO, D286 x L274
FAN SIROCCO, D286 x L184
SHAFT, FAN
SHEET, RUBBER 38 x 165mm
BEARING, ID20 x OD47 x t27
RUBBER , MOUNT B26 D 121
BEAM, ASSY
CASE
PULLEY, B1 x 4 x 24mm NBK
PULLEY, B1 x 4.5 x 24mm NBK
PULLEY, BLOWER
BELT, V

46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69

DESCRIPTION
BELT, V
SUPPORT, PARTITION
ASSY., PANEL REAR TOP
ASSY., REAR TOP PANEL
ASSY., ORIFICE
ASSY., MOTOR BRACKET
MOTOR
FAN PROPELLER, 26 SFZ660 SINGCHANG
FAN GUARD, SQUARE PRG8~20 W636557G02
ASSY., OD PARTITION
COVER, OD PARTITION
ASSY. CONTROL BOX UAT(P)80AY1X
ASSY. CONTROL BOX UAT(P)100AY1X
ASSY., TERMINAL COVER
TOP PLATE (INDOOR)
AIR FILTER, 1020mm x 615mm
PANEL, SIDE LEFT
PANEL, SIDE RIGHT
COVER, FILTER RIGHT
ASSY., INTAKE DUCT
ASSY., DISCHARGE DUCT
PANEL, SERVICE 1
PANEL, SERVICE 2
HANDLING HANDLES
BRACKET, FITTING W881464G03

TM-UAT-1114-B

1. ALL SPECIFICATION ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

74

Model : UAT(P)120AY1X

40 39 38 37 44 45

15

43

31

59

54
53
49

42 41

51 52

18

50

35

48

33
34
36
61
20

55

46

57

32

56
47

21
65

69

58

64

22 26

NO
1
2
3
4
5
6
7
8
9

TM-UAT-1114-B

10

75

23 24

60

25

27

DESCRIPTION
ASSY., BASE INDOOR
ASSY., BASE OUTDOOR
STRUCTURE BASE RIGHT
STRUCTURE BASE LEFT
ASSY., PARTITION
ASSY., SUPPLY AIR
ASSY., DRAIN PAN
COVER, LOW IN HALE
ASSY., COMPRESSOR BASE
COMPRESSOR, ASSY.
ZR144KC-TFD-522 COPELAND

28

29

30

19

NO
11
12
13
14
15
16
17
18
19
20

63

62 67 68

66

DESCRIPTION
COMPRESSOR, ASSY.
ZR144KCE-TFD-522 COPELAND
ASSY., COIL OUTDOOR
ASSY., COIL OUTDOOR
ASSY., COIL OUTDOOR
PLATE, BAFFLE
ASSY., PILLAR OUTDOOR 1
ASSY., PILLAR OUTDOOR 2
ASSY., COVER BLOWER
ASSY., PILLAR INDOOR 1
ASSY., PILLAR INDOOR 2

Model : UAT(P)120AY1X

NO
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45

DESCRIPTION
ASSY., PANEL FRONT
ASSY., BEAM FRONT
ASSY., COIL INDOOR
ASSY., COIL INDOOR
PLATE, BAFFLE RIGHT
PLATE, BAFFLE LEFT
FILTER RAIL, BOTTOM
ASSY., FAN FRAME
ASSY., MOTOR BASE
SUPPORT BASE
MOTOR, 1.5kW 50Hz R P714567X02 HITACHI
FAN BASE
ASSY., BLOWER HOUSING A
ASSY., BLOWER HOUSING B
FAN SIROCCO, D286 x L274
FAN SIROCCO, D286 x L184
SHAFT, FAN
SHEET, RUBBER 38 x 165 mm
BEARING, ID20 x OD47 x t27
RUBBER, MOUNT B26 D121
BEAM, ASSY.
CASE
PULLEY, B1 x 4.5 x 24mm NBK
PULLEY, BLOWER B1*5.5 20mm/7mm
BELT, V B30 BANDO

NO
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69

DESCRIPTION
SUPPORT, PARTITION
ASSY., OD PARTITION
ASSY., PANEL REAR TOP
ASSY., ORIFICE 30"
FAN MOTOR BRACKET 30"A01024023059
MOTOR, HAT081 HEADLINE
MOTOR, HAT051 HEADLINE
FAN PROPELLER, 30" TFL750 SINGCHANG
FAN GUARD, SQUARE PRG8~20 W636557G02
HEATER, CRANKCASE 90W 240V 018-0047-01
ASSY. CONTROL BOX
COVER, OD PARTITION
COVER, BOX C35
TOP PLATE (INDOOR)
AIR FILTER, 1020mm x 615mm
PANEL, SIDE LEFT
PANEL, SIDE RIGHT
COVER, FILTER RIGHT
ASSY., INTAKE DUCT
ASSY., DISCHARGE DUCT
PANEL, SERVICE 1
PANEL, SERVICE 2
HANDLING HANDLE
BRACKET, FITTING W881464G03

TM-UAT-1114-B

1. ALL SPECIFICATION ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

76

Model : UATP150/200AY1X

88

83
87

76 74

84

73 71 69 67
81 82
86
80
79

91 92

94 95

53
85

51

54

52

78
61 62 63 64
75 77
65
66 68 70 72
56
58 59 60
57
93

55
48 49 50

TM-UAT-1114-B

NO
1
2
3
5
6
8
9
12
13
14
15

77

DESCRIPTION
ASSY., BASE PAN OD
ASSY., BASE FRAME REAR
ASSY., BASE PAN ID
ASSY., SEPARATOR
ASSY., DRAIN PAN
ASSY., PILLAR INDOOR L
ASSY., PILLAR INDOOR R
ASSY., COIL INDOOR L
ASSY., COIL INDOOR R
ASSY., COIL INDOOR L
ASSY., COIL INDOOR R

NO
20
21
24
25
26
28
30
32
33
35

DESCRIPTION
PLATE, BAFFLE L
PLATE, BAFFLE R
PLATE, BAFFLE C
ASSY., ATTACHMENT SEPARATOR
ASSY., BEAM
ASSY., FRONT PANEL LOW
ASSY., FRONT PANEL UPPER
ASSY., DUCT FLANGE
ASSY., DUCT FLANGE
ASSY., TOP PANEL
ASSY., FAN BASE FLANGE

Model : UATP150/200AY1X

NO
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
58

NO
DESCRIPTION
ASSY., FRAME MOTOR
61
62
ASSY., MOTOR BASE
WASHER, MOTOR BASE
MOTOR, 2.2kW 50Hz R P714568X03 HITACHI 63
MOTOR, 3.7kW 50Hz R P714569X03 HITACHI 64
65
PULLEY, B2*5 28mm
66
BELT, V B42 BANDO
67
PULLEY, B2 x 6 x 28mm NBK
68
BELT, V B43 BANDO
69
PULLEY, BLOWER B2*10*28mm
BLOWER WHEEL, D384.5X374 PLSTC W125160G04 74
SHAFT, FAN PW/PA20 1365MML VR310G419H05 76
BEARING, t28XID30XOD62 B58D071H04 78
RUBBER MOUNT, T21XID45XOD74*B31H223H01 79
BEARING CASE, t10.5XID33XOD108*B02R192H0 80
CUT OFF, L479mm R02C755H05
81
BEAM ASSY. *W493249G01PW20D
83
ASSY., BLOWER HOUSING LEFT
84
ASSY., BLOWER HOUSING RIGHT
85
AIR FILTER, SARANET 667x840mm
86
HEATER, CRANKCASE 90W 240V 018-0047-01 87
ASSY., COMPRESSOR BASE
88

DESCRIPTION
COMPRESSOR, ASSY. ZR94KC-TFD-522 COPELAND
COMPRESSOR, JH521YEB MITSUBISHI
COMPRESSOR, ASSY. ZR94KCE-TFD-522
COMPRESSOR, ASSY. ZR125KC-TFD-522 COPELAND
COMPRESSOR, ASSY. ZR125KCE-TFD-522
ASSY., TOP PANEL BEAM
ASSY., COIL OUTDOOR L
ASSY., COIL OUTDOOR R
ASSY., COIL OUTDOOR L
ASSY., COIL OUTDOOR R
ASSY., PILLAR R COND PRG15,20*W876857G03
ASSY., PILLAR L COND PRG15,20*W876857G04
ASSY., PILLAR L O/D PRG-15,20MYA
ASSY., PILLAR RIGHT O/D PRG-15,20MYA
ASSY., PANEL BEAM REAR TOP
ASSY., PANEL REAR TOP
ORIFICE PLATE (BELLMOUTH)*W634967G03
MOTOR, 0.55kW P714879X01 HITACHI
BRACKET, FITTING W881464G03
ASSY., MOTOR BRACKET
FAN PROPELLER, 26" SFZ660-135 SINGCHANG
FAN GUARD, SQUARE PRG8~20 W636557G02

TM-UAT-1114-B

1. ALL SPECIFICATION ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

78

Model : UATP250/300AY1X

45 47 49 51

67

33

23

34
66

60
61
65
62 64
55
57
68
54
39 40
69

56

31

38
59

30
29

41 42
58

63

44 46 48 50

24
25

28

19

69

27
53
52
35
21

TM-UAT-1114-B

NO
1
2
3
4
5
6
7
8
9
10

79

22

32 26

20

DESCRIPTION
ASSY., BASE FRAME REAR
ASSY., BASE FRAME FRONT
PLATE, BASE
FIXTURE
ASSY., RIGHT BASE PANEL (INS)
ASSY., LEFT BASE PANEL (INS)
ASSY., PARTITION L (INS)
ASSY., PARTITION R (INS)
ASSY., SIDE PILLAR L (INS)
ASSY., SIDE PILLAR R

37 43

NO
11
12
13
14
15
17
19
20
21
22

36

DESCRIPTION
ASSY., COIL SUPPORT (INS)
ASSY., DRAIN PAN (INS)
PAN, DRIP
ASSY., COIL INDOOR
ASSY., COIL INDOOR
ASSY., COIL INDOOR
ASSY., FRONT PILLAR L (INS)
ASSY., FRONT PILLAR R (INS)
ASSY., FRONT PANEL L (INS)
ASSY., CENTER PILLAR (INS)

Model : UATP250/300AY1X

NO
23
24
25
26
27
28
29
39
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45

DESCRIPTION
ASSY., TOP PANEL SUPPORT (INS)
HOLDER, BLOWER 1
HOLDER, BLOWER 2
ASSY., FRONT PANEL R (INS)
ASSY., DISCHARGE DUCT FLANGE
ASSY., SIDE PANEL HOLDER (INS)
BEAM, PANEL HOLDER
ASSY., FILTER RAIL CENTER
RAIL FITER 2
ASSY., FILTER COVER (INS)
ASSY., PANEL FRONT TOP L (INS)
ASSY., PANEL FRONT TOP R (INS)
SUPPORT,TUBE
SUPPORT ACCUMULATOR
ACCUMULATOR,A-AS62011 ALCO
SUPPORT, COIL BASE
ASSY., COMPRESSOR SUPPORT UATP250AY1X
ASSY., COMPRESSOR SUPPORT UATP300AY1X
COMPRESSOR,ASSY.
COMPRESSOR,ASSY.
ASSY., SEPARATOR 1
ASSY., COIL OUTDOOR L
ASSY., COIL OUTDOOR R

NO
46
47
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69

DESCRIPTION
ASSY., COIL OUTDOOR L
ASSY., COIL OUTDOOR R
ASSY., COIL OUTDOOR L
ASSY., COIL OUTDOOR R
PLATE, BOTTOM 1
PLATE, BOTTOM 2
ASSY., PILLAR REAR CENTER L
ASSY., PILLAR REAR CENTER R
ASSY., PILLAR OUTDOOR L
ASSY., PILLAR OUTDOOR R
PANEL, SEPARATOR 3
ASSY., SEPARATOR 2
ASSY., REAR TOP PANEL
ORIFICE, 32"
MOTOR, AEFPAL 6P-2.1HP,415V/3P/50HzTECO
BRACKET, FITTING W881464G03
BRACKET, FAN MOTOR 32"
FAN PROPELLER, 32" TFL800 SINGCHANG
GUARD, FAN UATP250/300AY1X
ASSY., SIDE PANEL (INS)
PANEL, SERVICE
SUPPORT, PIPE

TM-UAT-1114-B

1. ALL SPECIFICATION ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

80

TM-UAT-1114-B

Model : UAT(P)360/420AY1X

81

NO
1
2
3
4
5
6
7
8
9
10
11

DESCRIPTION
ASSY, LOWER SIDE PANEL (INS)
ASSY, UPPER SIDE PANEL (INS)
HANDLING HANDLE
PANEL,SERVICE LOWER
PANEL,SERVICE UPPER
ASSY., SIDE PILLAR L (INS)
ASSY., SIDE PILLAR R
ASSY., DISCHARGE DUCT FLANGE
ASSY., FRONT PANEL L (INS)
ASSY., FRONT PANEL R (INS)
ASSY, FILTER COVER (INS)

NO
16
17
18
19
20
21
22
23
24
25

DESCRIPTION
BLOWER, CPLT FDA 560 CMV L/H KRUGER CCW
MOTOR, 7.5KW 50HZ L P714597X02 HITACHI
SHEET, RUBBER t5x48x218mm 18
PULLEY, BUSH 2517/40 19 1 1
PULLEY, A2 VPT139 REPTECH 20
PULLEY, BUSH 1615-38/10mm
PULLEY, 2 SPA 280/2517
PULLEY, 2 SPA 250/2517
BELT, V SPA 2132
MOTOR, AEFPAL 6P-2.1HP,415V/
BRACKET, FAN MOTOR 32" RT250

12
13

ASSY, FRONT TOP PANEL L (INS)


ASSY, FRONT TOP PANEL R (INS)

26

FAN PROPELLER, 32" TFL800 SINGCHANG

14
15

ORIFICE, 32"
ASSY., REAR TOP PANEL

28
29
30

GUARD, FAN RT250/300 28 2 2


FILTER, SARANET TOP L860 x W
FILTER, SARANET L860

Model : UAT150CY1X

12
13
14
15
16

DESCRIPTION
ASSY, TUBING (MAIN)
ASSY, BASE PAN MAIN (GUIDE)
ASSY, INS. DRAIN PAN
ASSY, INS. PILLAR FRONT LEFT
ASSY, INS. PILLAR FRONT RIGHT
ASSY, ID COIL L/R GUIDE
ASSY, INS. SEPARATOR 1
ASSY, INS. SEPARATOR 2
ASSY., INS. SEPARATOR CENTRE
SUPPORT, TOP PANEL
ASSY, INS. FRONT PANEL
ASSY, COMP. ZR84KC-TFD-522 COPELAND

NO

ASSY, PILLAR REAR LEFT


ASSY, PILLAR REAR RIGHT
ASSY, PILLAR CENTER LEFT

27
28

ASSY, PILLAR CENTER RIGHT

17
18
19
20
21
22
23
24
25
26

29
30

DESCRIPTION
ASSY, OD COIL R
ASSY, OD COIL R (GOLD FIN)
ASSY, OD COIL L
ASSY, OD COIL L (GOLD FIN)
SUPPORT, PILLAR LEFT
SUPPORT, PILLAR RIGHT
ASSY, PARTITION OD BIG
ASSY, PARTITION OD SMALL
ASSY, INS. ATTACHMENT PILLAR BACK L/R
ASSY, INS. ID TOP CHANNEL LEFT
ASSY, INS ID TOP CHANNEL RIGHT
ASSY, BRACKET VALVE
SUPPORT, PIPE
PLATE, PIPE SUPPORT
ASSY, FRAME ID MOTOR
ASSY, ID MOTOR BASE

TM-UAT-1114-B

NO
1
2
3
4
5
6
7
8
9
10
11

82

Model : UAT150CY1X

NO
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56

DESCRIPTION
PULLEY, 2 SPZ 132/1610
PULLEY, BUSH 1610/25
FRONT BLOWER MOUNT
ASSY, INS. FLANGE CASING
MOTOR, 2.2KW 50HZ L P714607X02
PULLEY, 2 SPZ 75/1210
PULLEY, BUSH 1210/28
ASSY, FLANGE OUTLET
ASSY, INS. FLANGE INLET
ASSY, INS. FILTER COVER
ASSY, INS. SIDE PANEL LEFT
ASSY, INS. SIDE PANEL RIGHT
ASSY, CONTROL BOX
ASSY, CONTROL BOX (SEQ)
PANEL, SERVICE COMP.
ASSY, INS. CTR SVC PANEL
ASSY, INS. ID TOP PANEL
ASSY, INS. REAR TOP PANEL
ORIFICE
ASSY, MOTOR BRACKET
MOTOR, 360W 1PH 230V
FAN PROPELLER, 24
FAN GUARD
ASSY, INS. COVER SEPARATOR LEFT
ASSY, INS. COVER SEPARATOR RIGHT
COVER, COIL SIDE L/R

NO
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81

DESCRIPTION
COVER, COIL REAR L/R
HANDLING HANDLE
FIXTURE
FILTER, SARANET 895x685MM
BELT, V SPZ 737
SHEET, RUBBER MTG t5.0X38X180MM R331F133H02
CAP, S655002H03
NUT, HEX. M10 (R.P)
NUT, HEX H.T M16
NUT, HEX 1/2
WASHER, SPRING OD22XID13Xt1.5MMS561121H08
NUT, C/W FLANGE (M8XDIA 24.0)
SCREW, HEX. TAP M5X12 P-WASHER 4P223591-12
SCREW, HEX. TAP M5X12 4SA01118-12
WASHER, FLAT M8 T1.6X8.5X18MM (R.PL)
BOLT, HEX PAN HEAD M8X40MM (R.PL) M
WASHER, SPRING OD15XOD8.5Xt1.2MM S561121H06
WASHER, FLAT OD25X10.5XT1.0MM
SCREW, WOOD M12 X 65MM S519112H04
WASHER, FLAT OD33.5 X ID13.5XT1.2MM
SCREW, HEX. TAP M5X16 P. WASHER 4SA1112-16
BOLT, HEX PAN HEAD M10X40MM
WASHER, SPRING OD22XID10XT1.0MM
COIL GUARD, SIDE L/R
COIL GUARD, FRONT

TM-UAT-1114-B

1. ALL SPECIFICATION ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

83

Model : UAT180CY1X

12
13
14
15
16

DESCRIPTION
ASSY, OD COIL R
ASSY, OD COIL R (GOLD FIN)
ASSY, OD COIL L
ASSY, OD COIL L (GOLD FIN)
SUPPORT, PILLAR LEFT
SUPPORT, PILLAR RIGHT
ASSY, PARTITION OD BIG
ASSY, PARTITION OD SMALL
ASSY, INS. ATTACHEMENT PILLAR L/R
ASSY, INS. ID TOP CHANNEL LEFT
ASSY, INS. ID TOP CHANNEL RIGHT

DESCRIPTION
ASSY, TUBING (MAIN)
ASSY, BASE PAN MAIN (GUIDE)
ASSY, INS. DRAIN PAN
ASSY, INS. PILLAR FRONT LEFT
ASSY, INS. PILLAR FRONT RIGHT
ASSY, ID COIL L/R GUIDE
ASSY, INS. SEPARATOR 1
ASSY, INS. SEPARATOR 2
ASSY., INS. SEPARATOR CENTRE
SUPPORT, TOP PANEL
ASSY, INS. FRONT PANEL TOP
ASSY, COMPRESSOR (ZZR108KC-TFD)

NO

ASSY, PILLAR REAR LEFT

27
28

SUPPORT PIPE
PLATE, PIPE SUPPORT

29
30

ASSY, FRAME ID MOTOR


ASSY, ID MOTOR BASE

ASSY, PILLAR REAR RIGHT


ASSY, PILLAR REAR CENTER LEFT
ASSY, PILLAR REAR CENTER RIGHT

17
18
19
20
21
22
23
24
25
26

ASSY, BRACKET VALVE

TM-UAT-1114-B

NO
1
2
3
4
5
6
7
8
9
10
11

84

Model : UAT180CY1X

NO
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55

DESCRIPTION
BLOWER, AT12-12 G2L
PULLEY, 2 SPZ 160/2012
BLOWER, PULLEY BUSH 2012/25
FRONT BLOWER MOUNT
ASSY, INS. FLANGE CASING
MOTOR, 3.0KW 50HZ L 4HTD00885
PULLEY, 2 SPZ 106/1610
MOTOR, PULLEY BUSH 1610/28
ASSY, FLANGE OUTLET
ASSY, INS. FLANGE INLET
ASSY, INS. FILTER COVER
ASSY, INS. SIDE PANEL LEFT
ASSY, INS. SIDE PANEL RIGHT
ASSY, CONTROL BOX
ASSY, CONTROL BOX (SEQ)
PANEL, SERVICE COMP.
ASSY, INS PANEL SERVICE CONTROL BOX
ASSY, INS. ID TOP PANEL
ASSY, INS. REAR TOP PANEL
ORIFICE, 681MM FAN
ASSY, MOTOR BRACKET OD (681MM)
MOTOR, 5016P 580W
FAN PROPELLER, 681MM P68L115
FAN GUARD
ASSY, INS. COVER SEPARTATOR LEFT
ASSY, INS. COVER SEPARATOR RIGHT

NO
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81

DESCRIPTION
COVER, COIL SIDE L/R
COVER, COIL REAR L/R
HANDLING HANDLE
FIXTURE
FILTER, SARANET 895X685MM
BELT, V SPZ 812
SHEET, RUBBER MTG T5.0X38X180MM R331F133H02
CAP, S655002H03
NUT, HEX M10 (R.P)
NUT, HEX H.T M16
NUT, HEX 1/2
WASHER, SPRING OD22XID13Xt1.5MMS561121H08
NUT, C/W FLANGE (M8XDIA24.0)
SCREW, HEX. TAP M5X12 P-WASHER 4P223591-12
SCREW, HEX. TAP M5X12 4SA01118-12
WASHER, FLAT M8 T1.6X8.5X18MM
BOLT, HEX. PAN HEAD M8X20MM
WASHER, SPRING OD15XID8.5X1.2MMS561121H06
WASHER, FLAT 0D25XID10.5XT1.0MM
SCREW, WOOD M12X65MM S519112H04
WASHER, FLAT OD33.5 X ID13.5 X T1.2MM
SCREW, HEX. TAP M5 X 16 P.WASHER 4SA01112-16
BOLT, HEX PAN HEAD M10X40MM
WASHER, SPRING OD22XID10XT1.0MM
COIL GUARD, SIDE L/R
COIL GUARD, FRONT

TM-UAT-1114-B

1. ALL SPECIFICATION ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

85

NO
1
2
3
4
5
6
7
8
9
10
11

DESCRIPTION
ASSY, TUBING (MAIN)
ASSY, BASE PAN MAIN (GUIDE)
ASSY, INS. DRAIN PAN
ASSY, INS. ID COIL BASE SUPPORT
ASSY, INS. PILLAR FRONT LEFT
ASSY, INS. PILLAR FRONT RIGHT
ASSY, ID COIL L/R GUIDE
ASSY, INS. SEPARATOR 1
ASSY, INS. SEPARATOR 2
ASSY., INS. SEPARATOR CENTRE
ASSY, COMPRESSOR ZR144KC-TFD-522

NO

12
13

ASSY, PILLAR REAR LEFT

27

DESCRIPTION
ASSY, OD COIL L
ASSY, OD COIL L (GOLD FIN)
SUPPORT, PILLAR CENTER LEFT
SUPPORT, PILLAR CENTER RIGHT
ASSY, PARTITION OD BIG
ASSY, PARTITION OD SMALL
ASSY, INS COVER SEPARATOR RIGHT
ASSY, INS COVER SEPARATOR LEFT
ASSY, BRACKET VALVE
SUPPORT PIPE
PLATE, PIPE SUPPORT
ASSY, INS. ATTACHEMENT PILLAR BACK L/R

ASSY, PILLAR REAR RIGHT

28

ASSY, INS. ID TOP CHANNEL L

14
15

ASSY, PILLAR REAR CENTER LEFT


ASSY, PILLAR REAR CENTER RIGHT
ASSY, OD COIL R
ASSY, OD COIL R (GOLD FIN)

29
30
31
32

ASSY, INS. ID TOP CHANNEL RIGHT


ASSY, FRAME ID FRAME
LEG (CASING)
ASSY, MOTOR BASE

16

17
18
19
20
21
22
23
24
25
26

TM-UAT-1114-B

Model : UAT240CY1X

86

Model : UAT240CY1X

NO
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59

DESCRIPTION
BLOWER, AT18/18
PULLEY, 2 SPZ 200/2012
PULLEY, BUSH 2012/25
SUPPORT, BLOWER RIGHT
ATTACHMENT
ASSY, INS. FLANGE CASING
MOTOR, 3.7KW 50HZ L P714608X03
PULLEY, 2 SPZ 95/1610
PULLEY, BUSH 1610/28
ASSY, INS. FRONT PANEL TOP
ASSY, INS. FRONT PANEL BOTTOM
ASSY, FLANGE OUTLET
ASSY, INS. FLANGE INLET
ASSY, INS. SIDE PANEL LEFT
ASSY, INS. SIDE PANEL LEFT
ASSY, CONTROL BOX
ASSY, CONTROL BOX (SEQ)
PANEL, SERVICE COMP.
ASSY, INS. CONTROL BOX SERVICE PANEL
ASSY, INS. ID TOP PANEL
ASSY, INS. REAR TOP PANEL
ORIFICE, 681MM FAN
ASSY, MOTOR BRACKET OD (681MM)
MOTOR, 5016P 580W
FAN PROPELLER, 681MM P68L11S KOHBUNSHI
FAN GUARD
ASSY, INS. FILTER COVER
COVER, COIL SIDE L/R

NO
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87

DESCRIPTION
COVER, COIL REAR L/R
HANDLING HANDLE
FIXTURE
FILTER, SARANET
BELT, V SPZ 887
SHEET, RUBBER MTG t5.0X38X180MM
SCREW, HEX. TAP M5X12 P-WASHER 4P223591-12
SCREW, HEX. TAP M5X12 4SA01118-12
WASHER, FLAT M8 T1.6X8.5X18MM (R.PL)
BOLT, HEX. PAN HEAD M8X20MM
WASHER, SPRING OD15XID8.5X1.2MMS561121H07
WASHER, FLAT OD25XID10.5XT1.0MM
SCREW, WOOD M12X65MM S519112H04
WASHER, FLAT OD33.5 X ID13.5XT1.2MM
SCREW, HEX. TAP M5X16 P.WASHER 4SA01112-16
CAP, S655002H03
NUT, HEX. M8 S562112H01
ADJUSTING SCREW AHU
WASHER, FLAT OD25X109.0XT1.0MM
BOLT, HEX PAN HEAD M8X40MM (R.PL) M
NUT, HEX 1/2
WASHER, SPRING OD22XID13Xt1.5MMS561121H08
BOLT, HEX PAN HEAD M10X40MM
WASHER, SPRING OD22XOD10Xt1.0MM
NUT, C/W FLANGE (M8XDIA 24.0)
COIL GUARD, SIDE L/R
COIL GUARD, FRONT
LEG, (CASING) RIGHT

TM-UAT-1114-B

1. ALL SPECIFICATION ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

87

Model : UAT300CY1X

12
13
14
15
16

DESCRIPTION
ASSY, TUBING (MAIN)
ASSY, BASE PAN MAIN (GUIDE)
ASSY, INS. DRAIN PAN
SUPPORT, ID COIL
ASSY, INS. PILLAR FRONT LEFT
ASSY, INS. PILLAR FRONT RIGHT
ASSY, ID COIL L/R GUIDE
ASSY, INS. SEPARATOR 1
ASSY, INS. SEPARATOR 2
ASSY., INS. SEPARATOR CENTER
ASSY, COMP. ZR190KC COPELAND
ASSY, COMP. ZR160KC COPELAND

NO
17
18
19
20
21
22
23
24
25
26

DESCRIPTION
ASSY, OD COIL R
ASSY, OD COIL R (GOLD FIN)
ASSY, OD COIL L
ASSY, OD COIL L (GOLD FIN)
SUPPORT, PILLAR CENTER LEFT
SUPPORT, PILLAR CENTER RIGHT
ASSY, PARTITION OD BIG
ASSY, PARTITION OD SMALL
ATTACHMENT, PARTITION
ASSY, INS COVER SEPARATOR RIGHT
ASSY, INS COVER SEPARATOR LEFT
ASSY, BRACKET VALVE

ASSY, PILLAR REAR LEFT

27

ASSY, PILLAR REAR RIGHT


ASSY, PILLAR REAR CENTER LEFT
ASSY, PILLAR REAR CENTER RIGHT

28
29

SUPPORT PIPE
PLATE, PIPE SUPPORT
ASSY, INS. ATTACHEMENT PILLAR BACK L/R

30

ASSY, INS. ID TOP CHANNEL LEFT

TM-UAT-1114-B

NO
1
2
3
4
5
6
7
8
9
10
11

88

Model : UAT300CY1X

NO
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60

DESCRIPTION
ASSY, INS ID TOP CHANNEL RIGHT
ASSY, INDOOR FAN FRAME
LEG, BLOWER 2
ASSY, MOTOR BASE
BLOWER, AT15/15 G2L NICOTRA STD
PULLEY, 3 SPZ 150/2012
PULLEY, BUSH 2012/25
SUPPORT, BLOWER RIGHT
ATTACHMENT
ASSY, INS. FLANGE CASING
MOTOR, 5.5KW 50HZ L P714609X02 HITACHI
PULLEY, 3 SPZ 95/1610
PULLEY, BUSH 1610/38
ASSY, INS. FRONT PANEL TOP
LEG, BLOWER
SUPPORT, TOP PANEL
ASSY, FLANGE OUTLET
ASSY, INS. FLANGE INLET
ASSY, INS. SIDE PANEL LEFT
ASSY, INS. SIDE PANEL RIGHT
ASSY, CONTROL BOX
ASSY, CONTROL BOX (SEQ)
PANEL, SERVICE COMP.
ASSY, INS. CONTROL BOX SERVICE PANEL
ASSY, INS. ID TOP PANEL
ASSY, INS. TOP PANEL OD
ORIFICE, FAN 800MM
BRACKET, MOTOR
MOTOR, 5016P 1200W
FAN PROPELLER, 800MM P68L11S KOHBUNSHI
FAN GUARD

NO
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91

DESCRIPTION
ASSY, INS. FILTER COVER
COVER, COIL SIDE L/R
COVER, COIL REAR L/R
HANDLING HANDLE
FIXTURE
FILTER, SARANET
BELT, V SPZ 887
SHEET, RUBBER MTG t5.0X38X180MM
SCREW, HEX. TAP M5X12 P-WASHER 4P223591-12
SCREW, HEX. TAP M5X12 4SA01118-12
WASHER, FLAT M8 T1.6X8.5X18MM (R.PL)
BOLT, HEX. PAN HEAD M8X20MM
WASHER, SPRING OD15XID8.5X1.2MMS561121H07
WASHER, FLAT OD25XID10.5XT1.0MM
SCREW, WOOD M12X65MM S519112H04
WASHER, FLAT OD33.5 X ID13.5XT1.2MM
SCREW, HEX. TAP M5X16 P.WASHER 4SA01112-16
CAP, S655002H03
BOLT, HEX PAN HEAD M10X40MM
WASHER, SPRING OD22XOD10Xt1.0MM
WASHER, FLAT OD25X109.0XT1.0MM
BOLT, HEX PAN HEAD M8X40MM (R.PL) M
NUT, HEX 1/2
WASHER, SPRING OD22XID13Xt1.5MMS561121H08
NUT, C/W FLANGE (M8XDIA 24.0)
NUT, HEX. M8 S562112H01
NUT, HEX H.T. M16
WASHER FLAT T3.0X16.0X32.0MM
WASHER SPRING T3.7X16.0X27.0MM
COIL GUARD, SIDE L/R
COIL GUARD, FRONT

TM-UAT-1114-B

1. ALL SPECIFICATION ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

89

GROUP ASSOCIATED (C&L) SDN BHD (109719-M)


Branches:

Penang
Pahang
Melaka
Sarawak
Kedah

Tel: 04-331 1670


Tel: 09-567 6778
Tel: 06-288 1133
Tel: 082-333 299
Tel: 04-733 0235

Johor
Tel: 07-557 7788
Perak
Tel: 05-548 2307
Sabah
Tel: 088-722 194
Negeri Sembilan Tel: 06-768 8969
Kelantan Tel: 09-747 4678