شرح تهوية غرفة المحولات

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 2

Qs =vxcp x T

Qs: Heat dissepation in the transformer room

V :fan capcity cfm


jal/kg.c

Cp= 1. 08

V :fan capcity cfm


V=Qs/CPXT

T
38 100.4
" 45 115
T
CP =1.08
QS

Transformers
150 kVA and smaller : 50 Watts/kVA
150 - 500 kVA : 30 Watts/kVA
500 - 1000 kVA : 25 Watts/kVA
1000 - 2500 kVA : 20 Watts/kVA
larger than 2500 kVA : 15 Watts/kVA

1 = 3.4112

2500 Kva

=Qs= 20 watt x2500=50000 watt


=3.4112x50000=170550 btu/hr

T =115-100.4=14.6 f
CP =1.08

V :fan capcity cfm


V=Qs/CPXT= 170550/14.5x1.08= 10890 cfm

You might also like