Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 7

Noise Calculation Procedure

1- Calculate the Fan sound power (SWL) from this


correlation
SWL = 40+10 log10 Q+20 log10 P s
Q = air flow rate, m3/s & Ps is the static pressure, Pa

2- Make spectrum corrections according the following


table

3- Calculate the attenuation db caused by the straight


duct and the fittings from Tables 2 to 5

4- Calculate the attenuation db caused by Outlet


reflection from Table 6
5- Calculate attenuated SWL = SWL attenuation
caused by steps 3 and 4
6- Calculate the difference between the attenuated
SWL and room SPL through calculation of the room
factor and using the chart

9- Using the following table according the required NC

10 Calculated the required insertion loss by subtract


combined SPL from the required NC to select the
silencer if there is loss

Fan duty
m3/s @
Pa
Type
In-duct sound power
Duct/Be Siz Leng Typ
nd
e
th
e

Outlet reflection
Total duct attenuation
Attenuated SWL
SWL SPL
Criterion
NC
Required insertion loss
+ 3db

Octave center frequency, Hz


6 12 25 50 1 2 4 8
3 5
0
0
K K K K