LAMPIRAN 1

PERHITUNGAN
Tabel 4.1 Data Hasil Pengamatan Cooling Tower
Q(kW)

Mv(g/s)

Temperatur

X
(mm

H2O

T1

T2

T3

T4

T5

T6

20

20

30,0

28,2

36,2

34,5

41,0

31,0

0,5

30
40
20

20
20
20

31,2
30,2
30,2

28,2
28,7
29,4

36,9
37,3
38,7

35,3
36,2
35,7

41,0
41,0
50,0

31,5
30,5
35,5

1,0

30
40

20
20

31,9
30,7

28,3
28,4

38,9
39,2

36,3
36,5

50,0
50,0

34,2
34,3

Keterangan
T 1 = Temperatur dry bulb masuk
T 2 = Temperatur wet bulb masuk
T 3 = Temperature dry bulb keluar
T 4 = Temperature wet bulb keluar
T 5 = Temperature air masuk
T 6 = Temperatur air keluar

Diketahui :
1. Orifice Constant
Rumus :
ma

= 0,137

x
Vb

Keterangan :
ma
x

= Dry air mass flowrate (kg/s)


= Orifice differential (mm

Vb

H2O

)
3

= Specific volume of steam and air mixture leaving top of column ( m /kg )

2. Water Capacity of System

= 3,0 liter (excluding make up tank )

3. Dimensions of Column

= 0,15 m x 0,15 m x 1 m (High)

4. Packing Data

= B-200 m

Number of decks

=8

Number of plates per deck

= 18

2
Total surface area of packing m

= 2,16

Height of packing, m

= 0,48

Packing density

area
m1
volume ,

= 200

Untuk Cooling Load Q = 0,5 kW, laju Alir 20 gr/s


H2O

Untuk Orifice Diffrential (x)

= 20 mm

Temperatur wet bulb udara masuk )

= 28,2

Temperatur air keluar (


Approach to wet bulb

T6

= 31,0
= (31,0 28,2)
= 2,8

1) Perhitungan Kecepatan Udara dan Approach To wet Bulb

Spesifikasi

volumetric udara keluar dengan menggunakan cara plot

Temperatur dry bulb udara keluar (


T4

T3

) dan temperature wet bulb keluar (

) pada physcometric chart, maka diperoleh

Air mass flowrate (m)

Vb

= 0,137

= 0,137

3
= 0,92 ( m /kg )

x
Vb
20
0,92

= 0,204 kg/s
Air Volume flowrate (V)

Cross selectional area of empty tower (A)

= m.

Vb

= 0,204

kg
s

= 0,018

m3
s

m2

V
A

m3
0,018
s
0,0225m 2

0,8 m/s

2) Perhitungan Laju Pendinginan dan Cooling Range


Laju Pendinginan

x 0,92

= 0,15 m. 0,15 m
= 0,0225

Kecepatan udara

Q
T 5T 6

m
kg

0,5
41,031,0

= 0,05 kW/
T 5 T 6
=

Cooling Range

= 41,0 31,0
= 10
Dry Bulb

=(

T 6 T 2

= 31,0 28,2
= 7,5
Untuk Cooling Load Q = 0,5 kW, laju Alir 30 gr/s
H2O

Untuk Orifice Diffrential (x)

= 20 mm

Temperatur wet bulb udara masuk )

= 28,2

Temperatur air keluar (

T6

= 31,5

= (31,5 28,2)
= 3,3

Approach to wet bulb

3) Perhitungan Kecepatan Udara dan Approach To wet Bulb


Spesifikasi
volumetric udara keluar dengan menggunakan cara plot
Temperatur dry bulb udara keluar (
T4

T3

) dan temperature wet bulb keluar (

) pada physcometric chart, maka diperoleh

Air mass flowrate (m)

Vb

= 0,137

= 0,137

= 0,923 ( m /kg )

x
Vb
20
0,923

= 0,6377 kg/s
Air Volume flowrate (V)

Vb

= m.

= 0,6377

kg
s

= 0,0184

m
s

x 0,923
3

Cross selectional area of empty tower (A)

= 0,15 m. 0,15 m
= 0,0225

Kecepatan udara

V
A

m3
s
2
0,0225 m

0,0184

=
=

0,8177 m/s

4) Perhitungan Laju Pendinginan dan Cooling Range


Laju Pendinginan

Cooling Range

Q
T 5T 6

0,5
41,031,5

= 0,052 kW/
T 5 T 6
=
= 41,0 31,5
= 9,5

Dry Bulb

=(

T 6 T 2

= 31,5 28,2
= 3,3

m3
kg

Untuk Cooling Load Q = 0,5 kW, laju Alir 40 gr/s


H2O

Untuk Orifice Diffrential (x)

= 20mm

Temperatur wet bulb udara masuk )

= 28,7

Temperatur air keluar (

T6

= 30,5

= (30,5 28,7)
= 1,8

Approach to wet bulb

5) Perhitungan Kecepatan Udara dan Approach To wet Bulb


Spesifikasi
volumetric udara keluar dengan menggunakan cara plot
Temperatur dry bulb udara keluar (
T4

T3

) dan temperature wet bulb keluar (

) pada physcometric chart, maka diperoleh

Air mass flowrate (m)

Vb

= 0,137

= 0,137

3
= 0,93 ( m /kg )

x
Vb

20
0,93

= 0,635 kg/s
Air Volume flowrate (V)

= m.

Vb

= 0,635

= 0,590
Cross selectional area of empty tower (A)

kg
s

x 0,93

m3
s

= 0,15 m. 0,15 m

m3
kg

m2

= 0,0225
Kecepatan udara

V
A

m3
s
0,0225m 2

0,590

26,24 m/s

6) Perhitungan Laju Pendinginan dan Cooling Range


Laju Pendinginan

Q
T 5T 6

0,5
41,030,5

= 0,0476 kW/
T 5 T 6
=

Cooling Range

= 41,0 30,5
= 10,5
Dry Bulb

=(

T 6 T 2

= 30,5 28,7
= 1,8
Untuk Cooling Load Q = 1,0 kW, laju Alir 20 gr/s
H2O

Untuk Orifice Diffrential (x)

= 20 mm

Temperatur wet bulb udara masuk )

= 29,4

Temperatur air keluar (


Approach to wet bulb

T6

= 35,5
= (35,5 29,4)
= 6,1

7) Perhitungan Kecepatan Udara dan Approach To wet Bulb


Spesifikasi
volumetric udara keluar dengan menggunakan cara plot
Temperatur dry bulb udara keluar (
T4

T3

) dan temperature wet bulb keluar (

) pada physcometric chart, maka diperoleh

Air mass flowrate (m)

Vb

= 0,137

= 0,137

3
= 0,928 ( m /kg )

x
Vb
20
0,928

= 0,6353 kg/s
Air Volume flowrate (V)

= m.

Vb

= 0,6353

= 0,5895
Cross selectional area of empty tower (A)

x 0,928

m3
s

m2

V
A

m3
0,5895
s
0,0225 m 2

26,20 m/s

8) Perhitungan Laju Pendinginan dan Cooling Range


Laju Pendinginan

= 0,15 m. 0,15 m
= 0,0225

Kecepatan udara

kg
s

Q
T 5T 6

m
kg

1,0
50,035,5

= 0,06 kW/
T 5 T 6
=

Cooling Range

= 50,0 35,5
=14,5
Dry Bulb

=(

T 6 T 2

= 35,5 29,4
= 6,1

Untuk Cooling Load Q = 1,0 kW, laju Alir 30 gr/s


H2O

Untuk Orifice Diffrential (x)

= 20 mm

Temperatur wet bulb udara masuk )

= 28,3

Temperatur air keluar (

T6

= 34,2

= (34,2 28,3)
= 5,9

Approach to wet bulb

9) Perhitungan Kecepatan Udara dan Approach To wet Bulb


Spesifikasi
volumetric udara keluar dengan menggunakan cara plot
Temperatur dry bulb udara keluar (
T4

T3

) dan temperature wet bulb keluar (

) pada physcometric chart, maka diperoleh

Air mass flowrate (m)

Vb

= 0,137

= 0,137

3
= 0,93 ( m /kg )

x
Vb
20
0,93

= 0,6353 kg/s
Air Volume flowrate (V)

Vb

= m.

= 0,6353

kg
s

= 0,5908

m
s

x 0,93
3

Cross selectional area of empty tower (A)

= 0,15 m. 0,15 m
= 0,0225

Kecepatan udara

V
A

m3
s
2
0,0225 m

0,5908

=
=

26,25 m/s

10) Perhitungan Laju Pendinginan dan Cooling Range


Laju Pendinginan

Cooling Range

Q
T 5T 6

1,0
50,034,2

= 0,063 kW/
T 5 T 6
=
= 50,0 34,2
= 15,8

Dry Bulb

=(

T 6 T 2

= 34,2 28,3
= 5,9
Untuk Cooling Load Q = 1,0 kW, laju Alir 40 gr/s

m3
kg

H2O

Untuk Orifice Diffrential (x)

= 2o mm

Temperatur wet bulb udara masuk )

= 28,4

Temperatur air keluar (

T6

= 34,3

= (34,3 28,4)
= 5,9

Approach to wet bulb

11) Perhitungan Kecepatan Udara dan Approach To wet Bulb


Spesifikasi
volumetric udara keluar dengan menggunakan cara plot
Temperatur dry bulb udara keluar (
T4

T3

) dan temperature wet bulb keluar (

) pada physcometric chart, maka diperoleh

Air mass flowrate (m)

Vb

= 0,137

= 0,137

= 0,94 ( m /kg )

x
Vb

20
0,94

= 0,6319 kg/s
Air Volume flowrate (V)

= m.

Vb

= 0,6319

= 0,5940
Cross selectional area of empty tower (A)

kg
s

x 0,94

m3
s

= 0,15 m. 0,15 m
= 0,0225

m2

m3
kg

Kecepatan udara

V
A

m
s
0,0225 m2

0,5940

=
=

26,40 m/s

12) Perhitungan Laju Pendinginan dan Cooling Range


Laju Pendinginan

Cooling Range

Q
T 5T 6

1,0
50,034,3

= 0,06 kW/
T 5 T 6
=
= 50,0 34,3
=15,7

Dry Bulb

=(

T 6 T 2

= 34,3 28,4
= 5,9