VARIABLE AIR VOLUME

RAV

PRODUCT DESCRIPTION
RABIE VAV terminal boxes type RAV were developed for the control of air flow,
especially in variable volume systems.
They come in different models:

RAVBS VAV Terminal Box

RAVBP VAV Terminal Box with Bypass

RAVBC CAV Terminal Box


Factory fitted control package, ensures the most accurate setup of required flow
rates. The flow rate control is a closed circuit system with external power supply.
RAV boxes can be supplied with control components from any reputable manufacturer to suit the project specification.
RAV contains an differential pressure sensor for air flow measurement (not for
Bypass type), a control damper and an integral sound attenuator for reducing the
air regenerated noise.
The control damper blade with seal insures best air tightness when closed.
RAV has a circular spigot connection up to 200 (8) size and Oval connection for
larger sizes on the fan side (high pressure end) & a rectangular flange connection
on the room side (low pressure end).
RTF Reserves The Right of Alternation

20-1

VARIABLE AIR VOLUME


RAV

RAVB(S, E or C)

RAVBP (By-Pass Type)

RTF Reserves The Right of Alternation

20-2

VARIABLE AIR VOLUME


RAV

RAV Principle of Operation


Room temperature controller
In VAV systems, the room temperature control
takes the form of a cascade control. The primary
controlled variable is the room temperature. The
output signal of the room temperature controller
is not fed directly to the supply air control
damper but alters the setpoint value of the supply
air flow rate control circuit.
The flow rate control also generates minimum
and maximum limits for the air flow which has
benefits in keeping the room temperature constant and for the functioning of the overall room
air conditioning system.
Flow rate measurement
A sensor is necessary for the positive measurement of air flows, this is achieved by pressure
measurement at several points distributed over
the cross-section and provision of the resulting
average value. The differential pressure sensor is
an optimum solution in terms of economics and
product technology.
This sensor delivers exact results for most room
air conditioning applications based on normal
upstream flow conditions.
Volume flow control
The control of the flow rate takes place in a
closed control circuit, i.e. measurement comparison control.
A pressure transducer converts the pressure differential into an electrical signal, which is interpreted as the actual value by the controller. In
most applications, the setpoint value comes from
a room temperature controller.
The controller compares the actual value with the
setpoint value and from the difference between
these two alters the control signal to the damper
actuator.

Supply/extract air tracking control


In individual rooms and closed-off office areas,
where the balance between supply and extract air
flow rate has to be maintained. Otherwise, annoying whistling noises can occur at door gaps,
and the doors can be difficult to open. For this
reason, the extract air should also have variable
control in a VAV system.
The actual value of the supply air is fed as an input signal to the extract air controller (slave controller). In this way, the extract air flow rate automatically follows the supply air flow rate, even in
the case where this has not reached its setpoint
value.
Bypass VAV
Bypass VAV is usually installed in a pressure dependent system (application) where there is no
variable speed control of the supply fan and so
back pressure should be avoided. For this reason
a bypass VAV requires a pressure relief damper
(or bypass damper) to avoid exceeding the maximum pressure of the system. Flow measurement
is not possible for Bypass type and so the Bypass
VAV comes without flow sensor. The control of
Bypass VAV shall be directly from the setpoint
of the room Temperature Controller OR BMS.
CAV Terminal Boxes
CAV Terminal Boxes are principally the same as
VAV Terminal Boxes but the concept of function is different. The CAV is intended to keep
preset constant air volume inter the duct branch
afterword the box. To do so, the compact controller will receive a signal of the preset volume
flow required and the actuator will act to keep
the flow constant depending on differential pressure measurement taken (corresponding to air
speed).

RTF Reserves The Right of Alternation

20-3

VARIABLE AIR VOLUME


RAV

RAV CONSTRUCTION & CHARACTERISTICS


Casing in galvanized sheet steel Gauge 22
Lining in the sound attenuator section of 25mm thickness
Control damper blade in galvanized sheet steel of Gauge 16 with suitable seal
Sensor tubes in aluminum with plastic pipes to the actuator
Plastic plain bearings
Controller fitted to the control damper made by Belimo or Siemens. Optionally
we can use any other controller if requested
Flow rate range is 1:10 (according to selected controller accuracy)
Flow range is setup and programmed in the factory as required by end-user, based
on data extracted from the calibration test rig
An optional Air Heater can be supplied with RAV on request

1)
1.1)
2)
3)
4)
4.1)
5)
6)
7)

Control Blade
Bypass Blade (only for bypass model RAVBP)
Controller
Differential Pressure Sensor
VAV Main Casing Box
Bypass Casing Box (only for bypass model RAVBP)
Inlet Spigot
Acoustic Liner
DP Sensor plastic pipes

RTF Reserves The Right of Alternation

20-4

VARIABLE AIR VOLUME


RAV

DIMENSIONS

* Only for By-Pass Type

Nominal Size
D
125 mm 5 inch
150 mm 6 inch
175 mm 7 inch
200 mm 8 inch
225 mm 9 inch
250 mm 10 inch
300 mm 12 inch
350 mm 14 inch
400 mm 16 inch
450 mm 18 inch
500 mm 20 inch
550 mm 22 inch
600 mm 24 inch

Inlet
Dx
Shape (mm)
Round
125
Round
150
Round
175
Round
200
Flat Oval 250
Flat Oval 300
Flat Oval 400
Flat Oval 450
Flat Oval 550
Flat Oval 600
Flat Oval 750
Flat Oval 750
Flat Oval 900

Dy
(mm)
125
150
175
200
200
200
200
250
250
300
300
350
350

A
(mm)
150
150
150
150
150
150
150
150
150
200
200
200
200

B
(mm)
300
300
300
300
350
400
500
550
650
700
850
850
1000

L
(mm)
600
600
700
700
700
700
700
800
800
900
900
1000
1000

H
(mm)
250
250
300
300
300
300
300
350
350
400
400
450
450

F
(mm)
200
200
250
250
250
250
250
300
300
350
350
400
400

G
(mm)
250
250
250
250
300
350
450
500
600
650
800
800
950

J
(mm)
230
230
280
280
280
280
280
330
330
380
380
430
430

K
(mm)
280
280
280
280
330
380
480
530
630
680
830
830
980

RTF Reserves The Right of Alternation

20-5

VARIABLE AIR VOLUME


RAV

PERFORMANCE DATA
RAV for flow control on Supply Air Application

Volumetric Flow Range and minimum differential pressure for each size
For Types RAVBS, RAVBC and RAVBP (fully Open)
Nominal Size
D
125 mm

5 inch

150 mm

6 inch

175 mm

7 inch

200 mm

8 inch

225 mm

9 inch

250 mm

10 inch

300 mm

12 inch

350 mm

14 inch

Volumetric Flow Rate


l/s
m/hr
CFM
30
110
65
60
220
125
120
430
255
250
900
530
45
160
95
100
360
210
190
680
405
350
1260
740
60
220
125
130
470
275
260
940
550
450
1620
955
80
290
170
170
610
360
330
1190
700
650
2340
1375
105
380
220
220
790
465
425
1530
900
900
3240
1905
130
470
275
260
940
550
520
1870
1100
1150
4140
2435
185
670
390
390
1400
825
775
2790
1640
1600
5760
3390
255
920
540
500
1800
1060
990
3560
2100
2200
7920
4660

Minimum Differential Pressure (Pa)


Static
Dynamic
Total
20
3
23
20
6
26
35
24
59
55
106
161
20
3
23
20
17
37
30
61
91
50
207
257
20
3
23
20
15
35
35
60
95
50
180
230
20
3
23
20
13
33
20
50
70
40
193
233
20
3
23
20
12
32
30
44
74
45
198
243
20
3
23
20
10
30
30
40
70
35
197
232
20
2
22
20
11
31
25
42
67
35
181
216
20
2
22
20
9
29
20
34
54
30
167
197

RTF Reserves The Right of Alternation

20-6

VARIABLE AIR VOLUME


RAV

Volumetric Flow Range and minimum differential pressure for each size
For Types RAVBS, RAVBC and RAVBP (fully Open)
Nominal Size
D
400 mm

16 inch

450 mm

18 inch

500 mm

20 inch

550 mm

22 inch

600 mm

24 inch

Volumetric Flow Rate


l/s
m/hr
CFM
320
1150
680
670
2410
1420
1330
4790
2820
2750
9900
5825
415
1490
880
830
2990
1760
1650
5940
3495
3600
12960
7630
530
1910
1125
1050
3780
2225
2100
7560
4450
4600
16560
9745
610
2200
1295
1250
4500
2650
2500
9000
5295
5250
18900
11125
745
2680
1580
1500
5400
3180
3000
10800
6355
6450
23220
13665

Minimum Differential Pressure (Pa)


Static
Dynamic
Total
20
2
22
20
9
29
20
36
56
30
155
185
20
2
22
20
8
28
20
32
52
20
152
172
20
2
22
20
7
27
20
29
49
20
139
159
20
2
22
20
8
28
20
31
51
20
135
155
20
2
22
20
7
27
20
28
48
20
127
147

RTF Reserves The Right of Alternation

20-7

VARIABLE AIR VOLUME


RAV

Discharge Sound Power Level


For Types RAVBS, RAVBC and RAVBP (fully Open)

NC

dBA

4000

2000

1000

500

250

125

NC

dBA

4000

2000

1000

500

14
inch

250

350
mm

12
inch

125

300
mm

10
inch

NC

250
mm

9 inch

45 31 27 16 19 15

dBA

225
mm

8 inch

4000

200
mm

7 inch

2000

175
mm

6 inch

1000

150
mm

5 inch

65
125
255
530
95
210
405
740
125
275
550
955
170
360
700
1375
220
465
900
1905
275
550
1100
2435
390
825
1640
3390
540
1060

500

125
mm

30
60
120
250
45
100
190
350
60
130
260
450
80
170
330
650
105
220
425
900
130
260
520
1150
185
390
775
1600
255
500

250

125

Volumetric Discharge Sound Power Level Discharge Sound Power Level Discharge Sound Power Level
(dB) at Pst=100Pa
(dB) at Pst=200Pa
(dB) at Pst=500Pa
Nominal Size Flow Rate
D
l/s CFM
6 <20 39 38 35 24 27 25

2 <20 48 47 45 34 37 34 11 <20

50 36 32 21 24 20 11 <20 44 43 40 29 32 30

7 <20 53 52 50 39 42 39 16 <20

55 46 45 26 26 22 17 <20 56 53 48 34 34 32 19 <20 65 62 58 44 44 41 28

21

62 56 50 35 34 24 24 <20 66 63 58 43 42 34 29 22 75 72 68 53 52 43 38

33

47 33 35 19 21 17

8 <20 41 40 37 27 29 27

4 <20 50 49 47 37 39 36 13 <20

50 37 40 22 24 20 11 <20 46 44 40 30 32 30

9 <20 55 53 50 40 42 39 18 <20

55 53 47 33 31 24 18 <20 63 60 55 41 39 34 26 <20 72 69 65 51 49 43 35

30

61 61 56 41 40 29 25 <20 71 68 64 49 48 39 34 29 73 70 66 53 50 44 36

31

43 34 30 21 23 18

5 <20 42 41 38 29 31 28

6 <20 51 50 48 39 41 37 15 <20

48 38 47 33 31 24 10 <20 46 45 58 45 41 37 13 <20 55 54 73 60 54 48 27 <20


51 40 48 34 32 31 13 <20 48 47 59 46 42 47 15 <20 57 56 74 61 55 60 28 <20
55 55 51 35 34 32 19 <20 51 64 62 47 44 48 26 <20 60 76 77 62 57 61 38
51 34 31 21 23 18 12 <20 42 41 39 29 31 28

27

6 <20 51 50 49 39 41 37 15 <20

53 45 51 38 36 35 15 <20 43 54 64 52 48 53 20 <20 52 65 80 69 63 69 34 <20


60 54 56 40 38 36 22 <20 48 64 70 54 50 54 27 <20 58 77 87 71 65 70 42

29

65 62 61 48 45 42 28 21 52 73 76 64 59 63 35 23 62 79 87 84 76 81 44

31

51 34 35 25 26 21 12 <20 44 43 41 33 34 31

8 <20 53 52 51 43 44 40 17 <20

52 45 52 40 38 35 14 <20 44 57 61 52 49 51 20 <20 53 68 75 67 63 65 32 <20


59 51 57 45 42 39 21 <20 49 64 66 58 54 56 26 <20 59 70 81 74 69 71 36

22

62 60 61 52 50 45 25 <20 51 75 70 67 64 64 36 25 70 70 82 75 70 72 38

28

51 36 32 25 26 21 12 <20 44 43 40 33 34 31

8 <20 53 52 50 43 44 40 17 <20

53 45 54 45 44 42 15 <20 45 53 67 59 57 62 23 <20 54 64 83 77 73 80 39

20

58 52 56 50 47 43 20 <20 49 61 69 65 60 63 26 <20 58 73 85 84 76 81 41

26

64 61 63 55 52 50 27 20 54 71 77 71 66 73 35 21 63 84 89 91 83 93 51

37

53 39 34 27 28 23 14 <20 49 46 42 35 36 33 12 <20 58 55 52 45 46 42 21 <20


58 49 50 42 40 38 20 <20 54 57 61 54 51 54 21 <20 63 68 75 69 65 68 33

21

61 57 52 50 50 49 24 <20 56 66 63 64 63 69 29 <20 65 78 77 81 80 86 43

30

65 63 58 55 51 50 28 21 59 72 70 70 64 70 34 22 68 85 85 88 81 87 48

38

51 53 35 28 29 24 16 <20 51 48 43 36 37 34 14 <20 60 57 53 46 47 43 23 <20


58 59 50 40 40 39 23 <20 58 52 61 51 51 54 21 <20 68 61 75 65 64 68 33

25

990 2100 63 66 54 50 48 45 29 20 63 58 65 63 61 62 27 <20 73 68 79 80 76 78 38 31


2200 4660 68 73 63 60 55 53 35 27 68 64 75 75 69 73 34 25 78 75 91 95 85 91 49 38

RTF Reserves The Right of Alternation

20-8

VARIABLE AIR VOLUME


RAV

Discharge Sound Power Level


For Types RAVBS, RAVBC and RAVBP (fully Open)
Discharge Sound Power
Level (dB) at Pst=500Pa

880

830

1760 58 59 53 43 42 41 23 <20 62 56 65 52 52 55 25 <20 71 66 74 65 64 63 34 29

1650

3495 67 65 61 53 51 50 30 24 71 61 74 64 63 67 34 28 72 67 74 65 65 62 35 30

3600

7630 75 74 70 62 61 60 39 34 79 69 84 74 75 80 43 38 73 66 72 66 67 62 35 31

530

1125 56 53 35 36 33 29 19 <20 59 51 43 44 41 39 21 <20 68 60 53 54 51 48 30 25

1050

2225 64 60 51 46 45 44 26 20 67 57 62 56 55 59 29 23 77 67 76 68 68 72 39 36

2100

4450 71 68 61 55 53 52 34 29 74 64 74 66 64 69 36 32 79 75 80 80 79 84 44 38

4600

9745 75 75 70 65 64 63 39 34 78 70 84 78 77 83 43 37 83 82 82 81 80 82 47 43

610

1295 63 56 36 38 36 30 25 <20 61 52 44 46 44 40 22 <20 70 61 54 56 54 49 31 27

1250

2650 66 62 51 46 45 45 28 22 63 57 62 55 54 59 26 <20 72 66 76 66 66 72 36 30

2500

5295 76 69 62 56 54 53 38 34 72 63 75 66 64 69 35 30 82 72 91 79 78 84 47 42

NC

415

dBA

5825 70 72 66 61 60 55 35 28 74 67 80 76 74 75 38 32 79 75 77 72 70 72 42 38

4000

2750

2000
1000
500

2820 64 65 60 51 50 46 29 21 68 61 73 64 62 63 32 25 78 71 76 69 65 68 40 37

250

1330

125

1420 58 57 50 42 41 39 22 <20 62 54 61 53 51 54 24 <20 72 63 75 67 64 67 35 30

NC

670

dBA
4000

51 52 35 29 30 25 16 <20 55 50 43 37 38 35 17 <20 64 59 53 47 48 44 26 20

2000
1000
500
250

22
inch

680

125

550
mm

20
inch

320

NC

500
mm

18
inch

CFM

dBA
4000
2000

450
mm

16
inch

l/s

1000

400
mm

Discharge Sound Power Level Discharge Sound Power Level


(dB) at Pst=100Pa
(dB) at Pst=200Pa
500
250
125

Nominal Size
D

Volumetric
Flow Rate

53 53 34 36 33 29 17 <20 57 50 42 44 41 39 19 <20 66 59 52 54 51 48 28 22

5250 11125 79 75 70 64 62 61 42 38 74 68 84 75 73 79 41 33 84 77 95 82 80 80 50 45
600
mm

24
inch

745

1580 64 59 37 38 36 30 26 20 62 53 45 46 44 40 23 <20 71 62 55 56 54 49 32 28

1500

3180 68 64 59 45 43 42 31 25 65 57 71 54 52 55 29 21 74 66 86 65 63 67 41 33

3000

6355 75 71 68 56 53 52 38 33 71 63 81 67 64 68 37 29 80 72 98 80 77 82 52 41

6450 13665 78 73 73 65 63 61 40 37 73 64 86 77 76 79 41 32 82 73 98 85 80 80 52 43

Notes:
Pst

Static Differential Pressure


Performance Ratings of Air Terminals are in accordance with standards AHRI 880-2008 and AHSRAE 130-2008
Sound Level measurements are in accordance with standard ISO 3741 comparison method
Noise Criteria and dB (A) calculations are based on Standard AHRI 885-2008 (See page 20-11)

RTF Reserves The Right of Alternation

20-9

VARIABLE AIR VOLUME


RAV

Case-Radiated Sound Power Level


For Types RAVBS, RAVBC and RAVBP (fully Open)

<20 42 35 30 27 23 16

<20 46 40 37 34 31 27 14 <20

NC

dBA

4000

2000

1000

40 33 26 21 17 15

500

<20 35 28 27 28 25 24

250

125

dBA

<20 31 27 26 27 20 15

NC

4000

2000

1000

500

28 26 26 26 17 15

250

65
125
255
530
95
210
405
740
125
275
550
955
170
360
700
1375
220
465
900
1905
275
550
1100
2435
390
825
1640
3390
540
1060
2100
4660

125

350 14
mm inch

30
60
120
250
45
100
190
350
60
130
260
450
80
170
330
650
105
220
425
900
130
260
520
1150
185
390
775
1600
255
500
990
2200

NC

300 12
mm inch

dBA

250 10
mm inch

4000

225 9
mm inch

2000

200 8
mm inch

1000

175 7
mm inch

CFM

500

150 6
mm inch

l/s

250

125 5
mm inch

Volumetric Radiated Sound Power Level Radiated Sound Power Level Radiated Sound Power Level
Flow Rate
(dB) at Pst=100Pa
(dB) at Pst=200Pa
(dB) at Pst=500Pa
125

Nominal
Size
D

6 <20

45 39 31 25 22 16 10 <20 46 40 33 29 26 21 12 <20 50 43 40 36 33 29 17 <20


46 43 37 29 27 18 13 <20 49 45 40 34 31 25 16 <20 54 46 43 38 34 32 20 <20
28 23 25 21 15 15

<20 28 25 26 24 18 15

<20 33 28 28 29 28 24

40 35 27 21 19 15

<20 42 37 31 27 25 19

<20 46 41 38 35 32 28 15 <20

7 <20

42 40 31 23 23 16

<20 45 42 35 29 28 23 12 <20 50 46 42 37 35 32 19 <20

46 46 38 31 27 22 15 <20 49 48 42 35 32 28 18 <20 54 51 47 40 36 35 23 <20


30 26 27 21 17 15

<20 30 28 28 25 20 17

<20 34 31 32 31 29 25

9 <20

41 36 27 22 20 20

<20 43 39 32 28 26 23 10 <20 47 44 40 36 33 30 16 <20

43 42 31 24 24 21 10 <20 46 44 36 30 29 26 14 <20 51 48 43 38 36 34 20 <20


48 49 41 32 30 26 17 <20 51 51 44 37 34 32 20 <20 55 53 49 42 38 38 24 <20
32 29 28 20 18 15

<20 32 30 29 25 21 18

<20 34 34 36 33 30 26 12 <20

41 37 27 22 21 25

<20 44 41 33 29 27 27 12 <20 48 46 42 37 34 32 18 <20

44 43 30 25 25 26 11 <20 47 46 36 31 30 28 15 <20 52 50 44 39 37 35 21 <20


50 51 43 33 32 30 20 <20 53 53 46 38 36 35 23 <20 56 54 51 43 40 40 26 <20
32 29 27 22 17 15

<20 33 31 30 26 21 17

42 36 27 21 20 20

<20 45 41 33 29 27 24 11 <20 50 47 42 37 35 32 18 <20

<20 35 35 35 33 31 26 11 <20

46 40 30 23 24 23 10 <20 49 45 37 31 30 28 15 <20 54 51 44 39 38 36 22 <20


50 49 42 31 32 28 18 <20 54 52 46 37 36 34 22 <20 58 55 51 43 40 40 26 <20
31 29 26 23 15 15

<20 33 32 30 27 21 15

<20 36 35 34 33 31 26 11 <20

42 35 26 20 19 15

<20 46 40 33 29 26 21 12 <20 51 47 42 37 35 32 19 <20

47 37 29 21 23 19 10 <20 51 44 37 31 30 27 16 <20 56 51 44 39 38 36 22 <20


50 47 41 28 32 26 17 <20 54 51 45 35 36 32 21 <20 59 55 50 42 40 40 26 <20
36 27 25 22 15 15

<20 36 31 29 26 20 15

<20 38 38 37 34 32 28 13 <20

42 36 27 21 20 15

<20 46 42 34 29 27 24 12 <20 53 50 45 40 38 36 22 <20

47 42 37 26 28 21 13 <20 51 47 42 33 33 29 18 <20 58 55 48 42 41 40 26 <20


51 49 39 30 35 29 18 <20 55 53 44 36 39 35 22 <20 62 57 51 43 42 43 28 <20
37 30 27 24 18 15

<20 38 34 31 28 23 17

42 37 27 23 23 17

<20 47 43 35 31 30 26 13 <20 55 53 46 41 39 38 23 <20

<20 40 40 38 36 34 30 15 <20

46 41 33 26 30 22 12 <20 52 47 41 34 35 31 18 <20 59 55 48 42 42 42 26 <20


56 51 42 31 37 31 21 <20 59 54 46 37 40 36 24 <20 63 58 51 43 43 45 29 <20

RTF Reserves The Right of Alternation

20-10

VARIABLE AIR VOLUME


RAV

Case-Radiated Sound Power Level


For Types RAVBS, RAVBC and RAVBP (fully Open)

NC

dBA

4000

2000

1000

500

250

125

NC

dBA

4000

2000

1000

500

250

125

NC

dBA

4000

600 24
mm inch

680
1420
2820
5825
880
1760
3495
7630
1125
2225
4450
9745
1295
2650
5295
11125
1580
3180
6355
13665

2000

550 22
mm inch

320
670
1330
2750
415
830
1650
3600
530
1050
2100
4600
610
1250
2500
5250
745
1500
3000
6450

1000

500 20
mm inch

CFM

500

450 18
mm inch

l/s

250

400 16
mm inch

Volumetric Radiated Sound Power Level Radiated Sound Power Level Radiated Sound Power Level
Flow Rate
(dB) at Pst=100Pa
(dB) at Pst=200Pa
(dB) at Pst=500Pa
125

Nominal
Size
D

38 32 28 25 20 15

5 <20 40 36 33 30 26 19

9 <20 42 42 39 37 36 32 16 <20

42 37 26 24 25 18

8 <20 47 43 35 32 32 27 14 <20 56 55 47 41 40 40 25 <20

45 39 29 26 31 23 11 <20 52 47 39 34 37 32 18 <20 59 55 48 42 42 43 26 <20


60 52 44 32 38 32 24 <20 62 55 48 37 41 37 27 <20 63 58 51 42 44 46 29 <20
39 35 30 27 23 15

7 <20 42 39 35 32 29 21 12 <20 44 44 40 39 38 34 18 <20

42 38 26 26 28 20

8 <20 48 44 36 34 35 29 15 <20 58 58 48 42 41 42 26 <20

44 38 25 26 33 24 10 <20 53 47 38 35 39 34 19 <20 60 55 48 42 43 45 26 <20


65 54 47 33 40 34 27 20 66 56 50 38 42 38 29 22 64 59 51 42 45 48 30 20
40 37 31 28 25 15

8 <20 44 41 37 34 32 23 14 <20 46 46 41 40 40 36 20 <20

42 38 25 27 30 21

9 <20 48 44 36 35 37 30 16 <20 59 60 49 42 42 44 28 <20

43 36 21 26 34 25 11 <20 53 47 36 35 41 35 20 <20 60 55 48 42 43 46 27 <20


69 55 49 34 41 35 31 26 69 57 52 38 43 39 32 26 64 59 51 41 46 49 30 20
41 40 33 30 28 15 10 <20 46 44 39 36 35 25 16 <20 48 48 42 42 42 38 21 <20
42 39 25 29 33 23 10 <20 49 45 37 37 40 32 18 <20 61 63 50 43 43 46 30 <20
42 35 17 26 36 26 11 <20 54 47 35 36 43 37 21 <20 61 55 48 42 44 48 27 <20
74 57 52 35 43 37 35 31 73 58 54 39 44 40 35 30 65 60 51 41 47 51 31 21
42 42 34 31 30 15 12 <20 48 46 41 38 38 27 18 <20 50 50 43 43 44 40 23 <20
42 39 24 30 35 24 12 <20 49 45 37 38 42 33 19 <20 62 65 51 43 44 48 32 21
41 33 13 26 37 27 12 <20 54 47 33 36 45 38 22 <20 61 55 48 42 44 49 28 <20
75 58 54 36 44 38 37 33 75 59 56 39 45 41 37 33 65 60 51 40 48 52 31 22

Notes:
Pst

Static Differential Pressure


Performance Ratings of Air Terminals are in accordance with standards AHRI 880-2008 and AHSRAE 130-2008
Sound Level measurements are in accordance with standard ISO 3741 comparison method
Noise Criteria and dB (A) calculations are based on Standard AHRI 885-2008 (See page 20-11)

RTF Reserves The Right of Alternation

20-11

VARIABLE AIR VOLUME


RAV

NC determination of RAV VAV Terminal Boxes

NC levels of the different VAV boxes model RAV are calculated based on AHRI 8852008 standard and under the following application assumptions:

Octave bands 2, 3, 4, 5, 6 & 7 only are considered in the acoustical module.

The VAV installation layout is as per Figure 1.

The VAV distribute air into two branches.

Critical paths of sound taken into consideration are Radiated Sound and Discharged Sound.

Lined Duct 600300


VAV

Tee 300

Lined Duct 300300

Flexible Duct 300

Diffuser

Gypsum Tiles

Figure 1: VAV installation layout

RTF Reserves The Right of Alternation

20-12

VARIABLE AIR VOLUME


RAV

Discharge Sound Attenuation Factors table:


Sound Attenuation (Insertion Loss)
calculated as per AHRI 885-2008

Octave Band Frequency, Hz


125

250

500

1000

2000

4000

Environmental Effect

Lined (1" liner) Straight Duct size 300600, 1.5m

18

16

12

Lined Duct Tee (1" liner) size 300mm

11

10

10

Lined (1" liner) Straight Duct size 300300, 0.9m

12

12

Branch power division (2 branches)

Lined Flexible Duct 300mm, 0.9m

12

11

End reflection factor (300mm)

Space Effect (listener at 1.5m in a 60m room)


Total Discharge attenuation

5
23

6
30

7
44

7
60

8
60

9
46

Radiated Sound Attenuation Factors table:


Sound Attenuation (Insertion Loss)
calculated as per AHRI 885-2008

Octave Band Frequency, Hz


125

250

500

1000

2000

4000

Environmental Effect

Solid Gypsum board Ceiling Tiles attenuation


Total Radiated attenuation

21
23

25
26

25
25

27
27

27
27

28
28

RTF Reserves The Right of Alternation

20-13

VARIABLE AIR VOLUME


RAV

ORDERING CODES
RAVXX 150 1 -

W - XXXXXX

Model Code
RAVBS ---- VAV
RAVBC --- CAV
RVABP ---- VAV with by-pass

Nominal Size in mm

Special Option
Here you can mention any special
requirements

Controller
0 ------------- Without Control
1 ------------- Factory Standard
2 ------------- Specific
Heater Option
W------------ with Heater
O ------------ without Heater

RTF Reserves The Right of Alternation

20-14