2015 PRODUCT GUIDE
15/25/28kV Class
CSH Series
INTRODUCTION & PRODUCT RATINGS
Product Ratings
Production Testing
Voltage Class, Phase-to-Phase 15kV 25kV 28kV
IEEE requires a Partial Discharge
Maximum Voltage Rating (phase to ground) 16.2kV
test and choice between AC and
Corona Voltage Level (CEV) 22kV
Impulse Withstand. Richards runs
AC Withstand, 1 minute 42kV
3/3 tests on all Medium Voltage
Impulse-Withstand Voltage (BIL) 162kV BIL
products governed by IEEE 386.
Continuous Current
100% Routine Electrical Test:
Aluminum 600A
Copper 900A
<< Partial Discharge
Short-Time Current << AC Withstand
Aluminum
40kA, 10c. and 10kA, 3s << Impulse Withstand
Copper
EPDM Jacket
Conductor Lugs
Cable Entrance Integral Jacket Seal
Greaseless Core
1. Conductor Lugs 2. IEEE 386 Interface 11 3. Capacitive Test Point 4. EPDM Jacket 5. Cable Entrance 6. Greaseless Core 7. Integral Jacket Seal
The CSH Series is available with a This industry-standard 600/900A The CSH Series is available with an The entire CSH Series is molded The Cable Entrance of the CSH is Hold-out cores that rely on grease or Once the core is removed, a jacket
variety of conductor lugs. We offer a 15/25/28kV Deadbreak interface is optional capacitive test point. This en- from a proprietary EPDM formula- shrinkable, obsoleting the cable a ribbon/spiral design can be unreli- seal is deployed over sealing mas-
range-taking shear bolt option as well compatible with a variety of compo- ables system operators to utilize suit- tion. This material has excellent me- adapter. This eliminates the perfor- able and messy. Richards product tic, completing the jacket restoration
as the traditional 600 or 900A com- nents including Apparatus Bushings, able equipment to test for voltage, or chanical impact/tear resistancean mance risk associated with cable development engineers created a without the need for a separate com-
pression connector. One of the most Elbow Tap Plugs, Hammerhead Insu- install a faulted circuit indicator (FCI). important trait given the often harsh adapter positioning and makes in- short, Greaseless Core design that is ponent.
impressive improvements of the CSH lating Plugs (HIPs) and more. conditions of the underground en- stallation markedly more ergonomic. easy to eject and consistent across
is the ease with which the housing vironment. The bonded outer jacket This cold shrink Cable Entrance also our Cold Shrink Family. Once ejected,
can be installed onto the prepared is semi-conductive, making the CSH allows the CSH to cover a range of the Core separates into halves which
cable/installed lug. Without having fully-shielded. cable sizes, as laid out in our Use can be recycled. Our simple yet effec-
to overcome any interference-fit (re- Range Chart. With fewer components tive design was engineered to per-
member, weve obsoleted the cable and range-taking capabilities, cus- form consistently across a variety of
adapter!), positioning the lug properly tomers are able to reduce inventory. installation environments.
is incredibly easy.
CSH Series ORDERING INFORMATION
Sample Part Number
6 2 CSH T 2 P 18 G
Conductor Ground
Current Voltage Product Test Kit Elbow
Lug Adapter
Ratings Class Series Point Type Size
Code Option
6 = 600A (All Aluminum N = None
Components)* T = W/ Capacitive Test-Point Elbow Only (No Lug):
7 = 600A (Aluminum Select O, P, or Q based on USE RANGE
Components and Cop- CSH CHART. Leave Lug Code blank.
per-Top Lug Compression Lug Kit:
9 = 900A (All Copper Com- Select O, P, or Q based on Use Range
ponents) Chart. Determine Lug Code using TABLE
X.
2 = 15/25/28kV Range Taking Kit w/ Shear Bolt Lug:*
Determine Elbow Size + Lug Code using
TABLE XRA.
Sample Part Number is a P size CSH with Capacitive Test Point, complete with Aluminum Stud, Aluminum Insulating Plug & Cap,
Aluminum Compression Lug for 500 kcmil Strd/Compr, #4 Tinned Copper Ground Braid (with solder block) and Constant Force Spring.
CSH Series
USE RANGE INFORMATION Connectors
PRODUCT CATALOG
2015 EDITION
The following product sizing information is based on AEIC/ICEA dimensional ranges. The true
range of the CSH Series on a particular cable construction may vary. To confirm sizing on
non-standard cables, or to check sizing on cables that fall just outside our min or max, contact
the factory.
COMING SOON!
Medium
Voltage
PRODUCT CATALOG
Conductor Size
Voltage Class
Minimum Maximum
** May not fit some 350kcmil compact 100% (175 mil) insulated power cables. Check minimum insulation diameter to
confirm.