Using Arresters To Stop Water Hammer: Designer'S Notebook

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

DESIGNERS NOTEBOOK

Using Arresters to Stop Water Hammer


Joseph V. Messina, CPD
Water hammer is a water pressure You can use an air chamber or a from the piping sufficiently to allow
surge that occurs in the water piping water hammer arrester to control water air to enter. Regardless of how the
when valves are shut off quickly. It is hammer. However, water hammer piping is arranged, no possible way
prone to happen with quick-shutoff arrestors are a more feasible option. to introduce air exists. An air chamber
valves such as those found on wash- The Problem With Air Chambers only can work if the plumbing system
ing machines or other mechanical In many cases, air chambers are is designed to drain all the risers and
equipment. When the valve is shut installed to cut costs. Air chambers branches so air can be introduced.
off, the flowing water hits the closed are simply capped vertical pieces of Thus, an air chamber cannot be an
valve or faucet and bounces back. The pipe filled with air and installed on the effective means to control shock in a
water continues bouncing until it hits water line. Many times an air cham- piping system.
a point of impactthe connection ber is just an extension of the piping Sizing and Locating Water Hammer
between two pipes or at a joint in a serving the lavatory, sink, or water Arresters
piping systemand causes a bang- closet. The airs purpose is to absorb The alterative to air chambers and
ing or knocking sound when the pipe the shock of the water hammer. Most best solution to control water hammer
vibrates due to the pressure wave. chambers only work for a short period is water hammer arresters, which
This impact eventually, or sometimes before the water absorbs the air in the absorb the surge so the water piping is
immediately, damages valves, fittings, pipe, which causes the air chamber to not damaged. Water hammer arresters
and equipment such as water heaters, become waterlogged. Once this hap- are engineered devices that use gas or
washing machines, dishwashers, and pens, the air chamber no longer can air to control water hammer. The gas
mechanical equipment. The damage protect the piping from water hammer. or air is sealed in the unit permanently
subsequently can cause water leaks or The U.S. Testing Laboratory has run and can control shock for many years.
equipment failure. tests on air chambers to determine Many styles of water hammer arresters
(Note that many valves, fittings, and the elapsed time for an air chamber to are on the market, and they come in
plumbing fixtures are designed to exceed 150 psig and the elapsed time all sizes to fit all applications. While
operate and resist damage up to 150 for failure, as evidenced by a violent the basic principle of operation in
pounds per square inch. This creates pounding and vibration in the piping each unit is different, all are designed
a margin of safety against unexpected system (see Table 1). The tests were with the permanent cushion of gas
pressure increases, since most codes do run with four valve closures per minute or air needed to control shock. Water
not allow pressure more than 80 psi to (1,900 valve closures a day), using 60 hammer arresters should be placed
enter a home or commercial building.) psi at 10 feet per second, and the air upstream from all quick-shutting valves
Calculations can determine the chambers completely failed (filled with and faucets, which can be found on
amount of pressure that is produced water) after the third day. washing machines, icemakers, and
Table 1. Air Chamber Failure Rates dishwashers and would include elec-
tronic operated valves used on hands-
Capacity Line Size Air Chamber Air Chamber Failure Rate
Units (cubic in) (in) Diameter (in) Height (in) Exceeded 150 psi Total Failure free faucets.
1 30 56.7 1st hour 2nd day Standard PDI-WH 201 covers water
2 50 1 58.2 1st hour 3rd day hammer arrester certification, sizing,
3 75 1 1 50 1st hour 2nd day and placement. PDI produces a sizing
4 110 1 1 54 1st hour 2nd day table based on the fixture unit value
5 170 1 2 50.5 1st hour 1st day applied to the line on which placement
6 300 2 3 40.5 1st hour 2nd day
of the water hammer arrester is being
Source: Standard PDI-WH201 Water Hammer Arrester Standard
considered (see Table 2).
When air chambers are used in Water hammer devices should meet
when the water flow is stopped buildings, refilling them with air after PDIs testing requirements. You can
abruptly. This pressure is approxi- they become waterlogged is difficult Table 2. Water Hammer Arrester Sizing
mately 60 times the velocity of the because the water system needs to
water moving through the pipe. Plumb- Pipe Size
be drained and recharged. However, PDI Symbol Fixture Unit Rating (in)
ing engineers generally design the Plumbing and Drainage Institute A 1-11
velocity between five and 10 feet per Standard PDI-WH 201 states that it is B 12-32
second, which can produce a pressure impossible to replenish the air by this C 33-60 1
wave between 300 and 600 psi. Testing D 61-113 1
method because the supply piping in E 114-154 1
of the piping system at this pressure is many plumbing systems forms a trap F 155-330 2
not done and is not a good idea. that makes it difficult to drain the water Source: Standard PDI-WH201 Water Hammer Arrester Standard

52 Plumbing Systems & Design March/April 2005


DESIGNERS NOTEBOOK
refer to Standard PDI-WH 201 for the testing standards and
procedures. TM

After selecting a water hammer device for a project, you


should pay close attention to where the device will be
located. Air chambers often are located behind fixtures, Grinders
By Liberty Pumps
and access to them is not possible without tearing into
the wall, which can be costly. Thus, air chambers may not
be the device of choice. Some manufactures and building
codes require access to a water hammer arrestor, which

Hungry by Design
may necessitate access panel installation to reach the arres-
tor if it needs to be replaced. Some manufacturer warran-
ties state that the manufacturer will pay for any repairs that
are required to access an arrestor, so access panels are not
required, but still recommended.

Joseph V. Messina, CPD, is the discipline


director of plumbing engineering for CUH2A
Inc., Architecture, Engineering, Planning,
in Atlanta. He has more then 30 years
experience specializing in plumbing and re
protection design of instructional, research,
and medical facilities. His email address is
jmessina@cuh2a.com.

Clarication
In the November/December 2004 Designers Notebook
column Discussing Acid Waste Systems, the figures origi-
nally came from Town & Country Plastics Inc.

continued from page 40


you can design and control this kind of pumping system.
The reference contains a wealth of additional design
details to help you solve problems, minimize costs, and
provide comfort to building occupants.
Thoughtful application of primary-secondary pumping
principles in the hydronic system can solve problems by
providing increased flexibility at low cost and even reduc-
ing operating costs. On the other hand, increasing the
complexity of the piping/pumping system without a clear
analysis may simply compound problems.
References
Primary-Secondary Pumping Application Manual, ITT
Fluid Handling Division Bulletin Number T E H 775.
With new V-SliceTM cutter
technology, a stainless steel
Omnivore LSG-Series TM

1968. impeller, and powered by


Franklin Electrics newest
the most advanced
generation motor, the OmnivoreTM
is not only hungry - its ready
grinder available.
ASPE 2006 Convention & Engineered Plumbing Exposition to shred anything in its path.
Tampa Convention Center
October 22-25, 2006
Photo: Tampa Bay Convention Bureau

Tampa, Florida
1-800-543-2550
www.libertypumps.com
Copyright Liberty Pumps, Inc. 2004 All rights reserved.
Franklin Electric is a trademark of its respective owner.

Circle 18 on your reader response card for product information.

March/April 2005 Plumbing Systems & Design 53

You might also like