Direct-driven fans
HCBB 9
Ordering key - Fan 10
Ordering key - Accessories 11 - 12
Description - Accessories, inlet and outlet 13
Charts - Air flow - Pressure rise 14 - 15
Design data 16
Moment of inertia - Sound data 17 - 18
Dimensions and weights - Fan 19 - 22
Tables, dimensions and weights - Accessories 23 - 24
HCBT 25
Ordering key - Fan 26
Ordering key - Accessories 27 - 28
Description - Accessories, inlet and outlet 29
Charts - Air flow - Pressure rise 30 - 31
Design data 32
Moment of inertia - Sound data 33 - 34
Dimensions and weights - Fan 35 - 37
Tables, dimensions and weights - Accessories 38 - 39
Dampers
DMEG 105
HXEG 106 - 111
Fan theory, vibration and insulation of structure borne sound 112 - 114
General
Design
- Robust design for use in industry.
- Direct-driven or belt-driven.
- Range of impeller types, (B, P and T impellers).
- Right-hand and left-hand versions (clockwise/counter clockwise rotation). For direction of discharge alternatives,
please refer to the catalogue section on each fan.
Material
- Carbon steel as standard.
- Stainless or acid-proof steel.
- Other materials possible on request.
Standards
Capacity and sound measurements can be carried out to the following standards:
- Capacity AMCA 210, ISO/DIS 5801
- Sound AMCA 300, ISO 3744, ISO 9614
Surface treatment
- Please refer to the individual ordering keys.
- All guards (belt guards, shaft guards and cooling disc guards) are epoxy painted in a yellow warning colour, (80 ).
Packing
- Fans are delivered on wooden laths suited for handling by fork-lift truck.
Instructions
- Installation and maintenance instructions are supplied with every fan.
General description Page 6
Characteristics
- Compact.
- Low capital investment cost.
- Operational reliability.
- Low operating costs.
- High efficiency, up to 88% with a type B impeller.
Impeller types
Type B impellers:
- Have backward-curved blades which, depending on size, give an overall efficiency of up to 88%.
- Enable the selection of a fan with an at least 80% efficiency within the greater part of the flow-pressure range.
- Are primarily for clean gas applications.
Type T impellers:
- Have straight radial blades for handling dust-laden gases. Not having a wheel inlet ring, this impeller is open and is
thus also suitable for fibrous dusts.
- Is supplied as standard in a strengthened, wear-resistant design.
Dust
Dust quantity and impeller choice.
- B impeller 0 - 30 mg/m3 NB! The stated values apply to dry dust and are for guidance only. Dust composition
and air speed greatly affect particle impact and wear. For further information,
- T impeller 150 - 1000 mg/m 3
please contact ABB Ventilation Products AB, Division Flkt Industri.
Key charts
HCBB HCBT
10 000 10 000
Total pressure risel, Pa
Total pressure rise, Pa
5000 5000
2000 2000
1000 1000
500 500
400 400
0.05 0.1 0.2 0.5 1 2 5 10 20 0.05 0.1 0.2 0.5 1 2 5 10
Gas flow m3/s Gas flow m3/s
General description Page 7
Characteristics
- Compact.
* T impellers are available for fans
- Low capital investment cost. with an impeller diameter of up to
- Operational reliability. 1000 mm.
Impeller types
Type B impellers:
- Have backward-curved blades which, depending on size, give an overall efficiency of up to 88%.
- Enable the selection of a fan with an at least 80% efficiency within the greater part of the flow-pressure range.
- Are primarily for clean gas applications.
Type P impellers:
- Have flat, backward-inclined blades.
- Are for handling clean gases and gases with a low dust content (e.g. flue gases).
Type T impellers:
- Have straight radial blades for handling dust-laden gases. Not having a wheel inlet ring, this impeller is open and is
thus also suitable for fibrous dusts.
- Is supplied as standard in a strengthened, wear-resistant design.
Dust
Dust quantity and impeller choice.
- B impeller 0 - 30 mg/m3
NB! The stated values apply to dry dust and are for guidance only. Dust composition
- P impeller 30 - 300 mg/m3 and air speed greatly affect particle impact and wear. For further information,
- T impeller 150 - 1000 mg/m3 please contact ABB Ventilation Products AB, Division Flkt Industri.
Key charts
10 000
Total pressure rise, Pa
HCH(B,P) 10 000
HCBB-aaa-bb-cc-dd-ee-fff
Size 1) (aaa)
010, 012, 016, 020, 025, 031, 040, 050 and 063.
1)
For variants in a size, impeller diameter, number of poles combination, please refer first to page 16, Design data.
2)
GP40-01 primer can be used where temperatures exceed 120C. This primer tolerates temperatures up to 150C
and vaporises at higher temperatures without emitting any toxic substances.
Ordering key - HCBB - Accessories Page 11
12 2
Duct
11
3 4
10 3
5, 6
4
3
5, 6
7
8
3
5, 6
9
2
2
9
5, 6
8
NB! Flanges comply with ISO 13351
Inlet
1 HCEZ-20 Inlet taper piece with protective screen and fixing lugs for connection to inlet without
connecting flange. (Pressure loss across the accessory, 0.35 x dyn. press. pd).
2 HCEZ-40, 41 Fabric duct, inlet without connecting flanges. 2)
3 HCEZ-27 Inlet flange, (fitted).
4 HCEZ-21 Inlet taper piece with protective screen and connecting flange for installation to inlet with
connecting flange.(Pressure loss across the accessory, 0.35 x dyn. press. pd).
5 HXEG Inlet vane control assembly, see pages 106 - 111. 1)
6 DMEG Regulating damper, see page 105. 1)
7 HCEZ-45, 46 Fabric duct, inlet with connecting flange. 2)
8 HCEZ-25 Counterflange, inlet, (not fitted).
9 HCEZ-29 Inlet connecting flange, for fitting ducts without connecting flange.
Outlet
10 HCEZ-30 Protective screen, outlet.
11 HCEZ-50, 51 Fibre duct, outlet, with connecting flanges. 2)
12 HCEZ-35 Counterflange, outlet, (not fitted).
1)
NB! Inlet vane assemblies/regulating dampers must not be connected directly to the fan without checking that the anti-vibration mountings can
cope with the increased component load on the fan.
2)
For size and temperature limits, please refer to the appropriate ordering keys.
HCBB - Air flow and dynamic pressure rise charts Page 14
31 56
800 53 90
700 53 85
50
600 50 80
47
500 45
42
400
300
0.06 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 3 5 6 7 8 9 10 16
Gas flow, m3/s
1500
1000
500
400
300
Dynamic pressure, Pa
100
50
40
30
0.06 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 3 5 6 7 8 9 10 16
Gas flow, m3/s
Example: Flow 3.0 m3/s, total pressure rise 2100 Pa. Pressure losses across accessories:
HCEZ-20 and 21 inlet taper piece:
Select an HCBB-040 with a 50 cm diameter impeller and 0.35 x dynamic pressure Pd.
a 2-pole motor, or an HCBB-050 with an 80 cm diameter
impeller and a 4-pole motor, see chart on next page.
Moment of inertia (J) See page 17. Sound data See pages 17-18.
HCBB - Air flow and dynamic pressure rise charts Page 15
30
800
80
700 75
600 50
25 47 71
500 45
400
300
0.06 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 3 5 6 7 8 9 10 16
Gas flow, m3/s
1500
1000
500
400
300
Dynamic pressure, Pa
100
50
40
30
0.06 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 3 5 6 7 8 9 10 16
Gas flow, m3/s
Moment of inertia (J) See page 17. Sound data See pages 17-18.
HCBB - Design data Page 16
Sound data
Symbols Formulae:
Lwtot = total sound power level for
a, b, c
sound paths a, b and c ................. dB (ref. 10-12 W). Lwtot , see table 2, page 18 Lwa, see table 2, page 18
a
Lw a,b,c = sound power level for sound paths a, b and c, Ltotb = Lwtot + K2 + K3 Lwb = Lwtot + Kb
respectively by octave band ............................. dB. a b
Lwtot = Lwtot + K2 + K3 Lwc = Lwtot + Kc
Kb, Kc, K2, K3 = corrections for sound paths b and c respectively c a c
(for sound path a, the correction = 0) .............. dB.
-5 b
-10 c
-15
0 4000 8000 12 000
Dpt, Pa
HCBB - Sound data cont. Page 18
Fan Im- No. Sound power level Lwa, dB Fan Im- No. Sound power level Lwa, dB
size peller of Lwtot size peller of Lwtot
Octave band, mid-frequency, Hz a Octave band, mid-frequency, Hz a
dia. pol. dia. pol.
aaa bb 63 125 250 500 1000 2000 4000 8000 dB aaa bb 63 125 250 500 1000 2000 4000 8000 dB
26 84 84 84 79 77 75 72 69 90 40 2 87 87 87 89 86 82 80 78 95
28 84 84 85 79 78 75 73 69 90 42 2 88 88 89 90 87 84 82 79 96
30 85 85 86 80 79 76 74 70 91 45 2 90 90 90 92 89 85 83 81 98
31 86 86 87 81 80 77 75 71 92 47 2 91 91 92 93 90 87 85 82 99
010 33 2 87 87 88 82 81 78 76 72 93 50 2 93 93 93 95 92 88 86 84 101
35 88 88 89 83 82 79 77 73 94 60 2 98 98 99 93 92 89 87 83 104
37 89 89 90 84 83 80 78 74 95 031 63 2 100 100 100 95 93 91 88 85 106
40 90 90 91 85 84 81 79 75 96 67 2 101 101 102 96 95 92 90 86 107
71 2 103 103 103 98 96 94 91 88 109
30 85 85 85 80 78 76 73 70 91 45 4 79 79 80 74 73 70 68 64 85
31 85 85 86 80 79 76 74 70 91 47 4 81 81 81 76 74 72 69 66 87
33 87 87 87 82 80 78 75 72 93 50 4 82 82 82 77 75 73 70 67 88
35 88 88 88 83 81 79 76 73 94
012 37 2 89 89 89 84 82 80 77 74 95 50 2 93 93 94 95 92 89 87 84 101
40 90 90 90 85 83 81 78 75 96 53 2 95 95 95 97 94 90 88 86 103
42 91 91 92 86 85 82 80 76 97 56 2 97 97 97 99 96 92 90 88 105
45 92 92 93 87 86 83 81 77 98 60 2 98 98 99 100 97 94 92 89 106
63 2 99 99 100 101 98 95 93 90 107
33 86 86 86 81 79 77 74 71 92 67 2 101 101 101 103 100 96 94 92 109
35 87 87 87 82 80 78 75 72 93 71 2 102 102 102 104 101 97 95 93 110
37 88 88 88 83 81 79 76 73 94 75 2 103 103 103 105 102 98 96 94 111
40 89 89 89 84 82 80 77 74 95 80 2 104 104 105 106 103 100 98 95 112
016 42 2 90 90 90 85 83 81 78 75 96 040 50 4 81 81 82 76 75 72 70 66 87
45 91 91 92 86 85 82 80 76 97 53 4 83 83 83 78 76 74 71 68 89
47 92 92 93 87 86 83 81 77 98 56 4 85 85 85 80 78 76 73 70 91
50 93 93 94 88 87 84 82 78 99 60 4 86 86 87 81 80 77 75 71 92
63 4 88 88 88 83 81 79 76 73 94
25 78 78 78 80 77 73 71 69 86 67 4 89 89 89 84 82 80 77 74 95
30 83 83 83 78 76 74 71 68 89 71 4 90 90 90 85 83 81 78 75 96
31 84 84 84 79 77 75 72 69 90 75 4 91 91 91 86 84 82 79 76 97
33 85 85 85 80 78 76 73 70 91 80 4 92 92 93 87 86 83 81 77 98
35 86 86 86 81 79 77 74 71 92
37 87 87 87 82 80 78 75 72 93 67 2 102 102 103 104 101 97 95 93 110
020 40 2 88 88 88 83 81 79 76 73 94 71 2 103 103 104 105 102 98 96 94 111
42 89 89 90 84 83 80 78 74 95 75 2 105 105 106 107 104 100 98 96 113
45 90 90 90 85 83 81 78 75 96 80 2 106 106 107 108 105 101 99 97 114
47 91 91 92 86 85 82 80 76 97 63 4 88 88 88 83 81 79 76 73 94
50 93 93 93 88 86 84 81 78 99 67 4 90 90 90 85 83 81 78 75 96
53 94 94 94 89 87 85 82 79 100 71 4 91 91 92 86 85 82 80 76 97
56 95 95 95 90 88 86 83 80 101 75 4 93 93 93 88 86 84 81 78 99
050 80 4 94 94 95 89 88 85 83 79 100
31 2 81 81 82 83 80 77 75 72 89 85 4 96 96 96 91 89 87 84 81 102
33 2 84 84 85 79 78 75 73 69 90 90 4 97 97 97 92 90 88 85 82 103
35 2 85 85 86 80 79 76 74 70 91 95 4 98 98 99 93 92 89 87 83 104
37 2 86 86 87 81 80 77 75 71 92 99 4 99 99 100 94 93 90 88 84 105
40 2 88 88 88 83 81 79 76 73 94 71 6 84 85 81 74 72 70 67 61 89
42 2 89 89 89 84 82 80 77 74 95 75 6 86 87 83 76 74 72 69 63 91
45 2 90 90 90 85 83 81 78 75 96 80 6 87 88 84 77 75 73 70 64 92
47 2 90 90 91 85 84 81 79 75 96
50 2 92 92 92 87 85 83 80 77 98 63* 2 110 105 104 108 100 96 91 91 114
025 53 2 94 94 94 89 87 85 82 79 100 67* 2 111 106 105 109 101 97 92 92 115
56 2 95 95 95 90 88 86 83 80 101 71* 2 113 108 107 111 103 99 94 94 117
60 2 97 97 97 92 90 88 85 82 103 75* 2 114 109 108 112 104 100 95 95 118
63 2 98 98 99 93 92 89 87 83 104 80 2 107 107 108 109 106 102 100 98 115
42 4 80 80 76 70 68 66 62 57 84 82 2 108 108 109 110 107 103 101 99 116
45 4 81 81 77 71 69 67 63 58 85 85 2 108 108 109 110 107 103 101 99 116
47 4 81 82 78 71 69 67 64 58 86 87 2 109 109 110 111 108 104 102 100 117
50 4 83 83 79 73 71 69 65 60 87 80 2 95 95 95 90 88 86 83 80 101
063 85 4 96 96 97 91 90 87 85 81 102
53 4 84 84 80 74 72 70 66 61 88
90 4 98 98 99 93 92 89 87 83 104
95 4 100 100 100 95 93 91 88 85 106
99 4 101 101 102 96 95 92 90 86 107
80 6 88 88 84 78 76 74 70 65 92
85 6 89 90 86 79 77 75 72 66 94
90 6 91 91 87 81 79 77 73 68 95
95 6 93 94 90 83 81 79 76 70 98
99 6 94 95 91 84 82 80 77 71 99
C E
A
F
D outs. B
X
N
K The sketches show a right-hand model.
Y
G1
G
n holes Z
P2 P3
P1
H2 H3 H3
J1 J2 J2
O1 O2 O2
M1 M2 N3
N1 N2
P4
P7 P8
H3 H4 H4
J2
J3 J3
O2
O3 O3
M3
N3 M3
N4
N4
Dimensions HCBB
Fan Imp. dia.
E F H2 H3 H4 M1 M2 M3 N1 N2 N3 N4 P1 P2 P3 P4 P7 P8
size bb
26-31 246 234 360 325 390 319 285 400 549 504 510 637 606 725 644 609 619 610
010
33-40 297 308 425 380 460 393 357 488 680 632 628 786 722 868 773 736 747 735
30-35 270 257 390 350 425 355 319 442 611 565 566 708 660 792 705 668 682 671
012
37-45 327 340 465 415 550 437 400 541 759 708 698 874 792 956 852 814 871 858
33-40 297 278 425 380 460 393 357 488 680 632 628 786 722 868 773 736 747 735
016
42-50 361 371 510 455 555 486 447 599 845 791 775 972 871 1054 941 901 914 899
25 206 126 310 280 330 261 228 330 445 404 417 520 516 610 541 507 514 506
30-35 270 220 390 350 425 355 319 442 611 565 566 708 660 792 705 668 682 671
020
37-45 327 302 465 415 550 437 400 541 759 708 698 874 792 956 852 814 871 858
47-56 398 406 560 500 610 541 500 664 943 885 862 1082 958 1164 1041 999 1012 995
31 246 159 360 325 390 324 285 403 554 504 510 641 606 728 649 609 619 610
33-40 297 233 425 380 460 398 357 491 685 632 628 789 722 871 778 736 747 735
025 42-50 361 326 510 455 555 491 447 602 850 791 775 975 871 1057 946 901 914 899
53-63 441 443 615 545 675 608 561 742 1058 992 961 1210 1056 1287 1153 1105 1125 1106
40 297 201 425 380 460 398 357 491 685 632 628 789 722 871 778 736 747 735
031 42-50 361 293 510 455 555 491 447 602 850 791 775 975 871 1057 946 901 914 899
60-71 489 480 675 600 740 677 629 825 1182 1112 1071 1357 1164 1425 1277 1228 1245 1223
50 361 251 510 455 555 491 447 602 850 791 775 975 871 1057 946 901 914 899
040 53-63 441 368 615 545 675 608 561 742 1058 992 961 1210 1056 1287 1153 1105 1125 1106
67-80 542 515 750 660 820 755 704 917 1319 1245 1194 1512 1292 1577 1415 1363 1385 1361
63 441 318 615 545 675 628 561 756 1078 992 961 1224 1056 1301 1173 1105 1125 1106
050 67-80 542 465 750 660 820 775 704 931 1339 1245 1194 1519 1292 1591 1435 1363 1385 1361
85-99 670 650 920 805 1005 960 884 1153 1669 1563 1489 1892 1590 1958 1765 1688 1714 1684
63-80 552 400 750 660 820 775 704 938 1339 1245 1204 1526 1302 1598 1435 1363 1385 1361
063
82-99 680 585 920 805 1005 960 884 1160 1669 1563 1499 1899 1600 1965 1765 1688 1714 1684
Dimensions L
Motor
Fan size
size
010 012 016 020 025 031 040 050 063
63 338 - - - - - - - -
71 364 384 - 444 - - - - -
80 387 407 433 467 508 558
90S - 420 446 480 521 571 - - -
90L - 445 471 505 546 - 661 - -
100L - - 499 533 574 624 689 - -
112M - - - 536 577 627 692 778 -
132S - - - 602 643 693 758 844 -
132M - - - - - - 758 844 944
160 - - - - 769 819 884 970 1070
180 - - - - - 896 961 1047 1147
200L - - - - - 989 1054 1140 1240
225M - - - - - - 1116 1202 1302
250M - - - - - - 1123 1209 1309
280S - - - - - - - 1397 1497
280M - - - - - - - - 1557
315S - - - - - - - - 1632
315MA - - - - - - - - 1632
HCBB - Dimensions and weights Page 21
E1
A n1 x E C
E1
F1 n2 x F F1 t + 2,5 t t
+ 10
130 - 20
D
F
E
D1 D4 D2 D3 D D D1 D2
ins. ins. outs. ins. ins.
+10 +10
t 40 - 20 130 - 20
nxG 45
L K
HCBT-aaa-bb-cc-dd-ee-fff
Size 1) (aaa)
010, 012, 016, 020, 025, 031, 040, 050 och 063.
1)
For variants in a size, impeller diameter, number of poles combination, please refer first to page 32, Design data.
2)
GP40-01 primer can be used where temperatures exceed 120C. This primer tolerates temperatures up to 150C
and vaporises at higher temperatures without emitting any toxic substances.
Ordering key - HCBT - Accessories Page 27
15 2, 3
Duct
13, 14
4 5
12 4
6, 7
5
4
6, 7
8, 9
10
4
6, 7
11
2, 3
2, 3
11
6, 7
10
NB! Flanges comply with ISO 13351
Inlet
1 HCEZ-20 Inlet taper piece with protective screen and fixing lugs for connection to inlet without connecting
flange. (Pressure loss across the accessory, 0.35 x dyn. press. pd).
2 HCEZ-40, 41 Fabric duct, inlet without connecting flange. 2)
3 HCEZ-60 Flue gas duct, inlet without connecting flanges. 2)
4 HCEZ-27 Inlet flange, (fitted).
5 HCEZ-21 Inlet taper piece with protective screen and connecting flange for installation to inlet with
connecting flange. (Pressure loss across the accessory, 0.35 x dyn. press. pd).
6 HXEG Inlet vane control assembly, see pages 106 - 111. 1)
7 DMEG Regulating damper, see page 105. 1)
8 HCEZ-45, 46 Fabric duct, inlet with connecting flanges. 2)
9 HCEZ-65 Flue gas duct, inlet with connecting flanges. 2)
10 HCEZ-25 Counterflange, inlet, (not fitted).
11 HCEZ-29 Inlet connecting flange, for fitting ducts without connecting flanges.
Outlet
12 HCEZ-30 Protective screen, outlet.
13 HCEZ-50, 51 Fibre duct, outlet, with connecting flanges. 2)
14 HCEZ-70 Flue gas duct, outlet with connecting flanges. 2)
15 HCEZ-35 Counterflange, outlet, (not fitted).
1)
NB! Inlet vane assemblies/regulating dampers must not be connected directly to the fan without checking that the anti-vibration mountings can
cope with the increased component load on the fan.
2)
For size and temperature limits, please refer to the appropriate ordering keys.
HCBT - Air flow and dynamic pressure rise charts Page 30
31 33 95
31 60
30 31 90
1000 28 53 56
50 85
26 53
25 47 80
50
45
42
500
0.06 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 3 4 5 6 7 8 9 10
Gas flow, m3/s
2000
1000
400
100
40
20
0.06 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 3 4 5 6 7 8 9 10
Gas flow, m3/s
Moment of inertia (J) See page 33. Sound data See pages 33-34.
HCBT - Air flow and dynamic pressure rise charts Page 31
31 31
30 63
30
1000 28 80
50
75
25 47 71
45
500
0.06 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 3 4 5 6 7 8 9 10
Gas flow, m3/s
2000
1000
400
100
40
20
0.06 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 3 4 5 6 7 8 9 10
Gas flow, m3/s
Example: Flow 3.3 m3/s, total pressure rise 2500 Pa. Pressure losses across accessories:
HCEZ-20 and 21 inlet taper piece:
Select an HCBT-050 with an 80 cm diameter impeller 0.35 x dynamic pressure Pd.
and a 4-pole motor.
Moment of inertia (J) See page 33. Sound data See pages 33-34.
HCBT - Design data Page 32
Sound data
Symbols Correction K2
Lwtot = total sound power level for a
a, b, c
sound paths a, b and c ................. dB (ref. 10-12 W). 0
-5
K2, dB
Fan Im- No. Sound power level Lwa, dB Fan Im- No. Sound power level Lwa, dB
size peller of Lwtot size peller of Lwtot
Octave band, mid-frequency, Hz a Octave band, mid-frequency, Hz a
dia. pol. dia. pol.
aaa bb 63 125 250 500 1000 2000 4000 8000 dB aaa bb 63 125 250 500 1000 2000 4000 8000 dB
25 90 90 90 89 83 76 69 61 96 40 2 97 99 100 97 91 85 78 72 105
26 89 92 92 89 83 77 70 64 97 42 2 100 100 100 99 93 86 79 71 106
28 90 93 93 90 84 78 71 65 98 45 2 102 102 102 101 95 88 81 73 108
30 91 94 94 91 85 79 72 66 99 47 2 104 104 104 103 96 89 83 75 110
010 31 2 92 94 95 92 86 80 73 67 100 031 50 2 105 105 105 104 98 91 84 76 111
33 93 95 96 93 87 81 74 68 101 60 2 107 109 110 107 101 95 88 82 115
35 94 96 97 94 88 82 75 69 102 63 2 108 111 111 108 102 96 89 83 116
37 95 97 98 95 89 83 76 70 103 45 4 88 90 91 88 82 76 69 63 96
40 96 98 99 96 90 84 77 71 104 47 4 89 91 92 89 83 77 70 64 97
50 4 90 92 93 90 84 78 71 65 98
28 93 93 93 92 85 78 72 64 99
30 92 94 95 92 86 80 73 67 100 50 4 91 94 92 87 83 76 69 63 98
31 93 95 96 93 87 81 74 68 101 53 4 91 94 94 91 85 79 72 66 99
33 93 96 96 93 87 81 74 68 101 56 4 93 95 96 93 87 81 74 68 101
012 35 2 94 97 97 94 88 82 75 69 102
60 4 94 97 97 94 88 82 75 69 102
37 95 98 98 95 89 83 76 70 103
040 63 4 96 99 99 96 90 84 77 71 104
40 96 99 99 96 90 84 77 71 104
67 4 98 101 99 94 91 84 76 70 105
42 97 99 100 97 91 85 78 72 105
71 4 100 103 101 96 92 85 78 72 107
45 98 100 101 98 92 86 79 73 106
75 4 101 104 102 97 94 87 79 73 108
80 4 102 105 103 98 95 88 80 74 109
31 95 95 95 94 87 80 74 66 101
33 94 96 97 94 88 82 75 69 102
63 4 97 100 98 93 89 82 75 69 104
35 95 97 98 95 89 83 76 70 103
67 4 98 101 101 98 92 86 79 73 106
37 96 98 99 96 90 84 77 71 104
71 4 100 102 103 100 94 88 81 75 108
016 40 2 96 99 99 96 90 84 77 71 104
75 4 101 104 104 101 95 89 82 76 109
42 97 100 100 97 91 85 78 72 105
80 4 103 106 106 103 97 91 84 78 111
45 98 101 101 98 92 86 79 73 106
050 85 4 105 108 106 101 98 91 83 77 112
47 99 102 102 99 93 87 80 74 107
90 4 107 110 108 103 99 92 85 79 114
50 100 102 103 100 94 88 81 75 108
95 4 108 111 109 104 100 93 86 80 115
99 4 109 112 110 105 102 95 87 81 116
25 88 91 91 88 82 76 69 63 96
71 6 93 96 94 89 85 78 71 65 100
30 93 93 93 92 86 79 72 64 99
75 6 94 97 95 90 86 79 72 66 101
31 95 95 95 94 87 80 74 66 101
80 6 96 99 97 92 88 81 74 68 103
33 96 96 96 95 88 81 75 67 102
35 97 97 97 96 89 82 76 68 103
80 4 104 107 105 100 97 90 82 76 111
37 96 98 99 96 90 84 77 71 104
85 4 105 107 108 105 99 93 86 80 113
020 40 2 97 99 100 97 91 85 78 72 105
90 4 107 109 110 107 101 95 88 82 115
42 98 100 101 98 92 86 79 73 106
95 4 108 111 111 108 102 96 89 83 116
45 99 101 102 99 93 87 80 74 107
063 80 6 96 99 97 92 89 82 74 68 103
47 99 102 102 99 93 87 80 74 107
85 6 98 101 99 94 90 83 76 70 105
50 100 103 103 100 94 88 81 75 108
90 6 99 102 100 95 92 85 77 71 106
53 101 104 104 101 95 89 82 76 109
95 6 101 104 102 97 94 87 79 73 108
56 102 105 105 102 96 90 83 77 110
99 6 103 106 104 99 95 88 81 75 110
31 2 92 94 95 92 86 80 73 67 100
33 2 95 95 95 94 88 81 74 66 101
35 2 96 96 96 95 89 82 75 67 102
37 2 98 98 98 97 90 83 77 69 104
40 2 99 99 99 98 91 84 78 70 105
42 2 98 100 101 98 92 86 79 73 106
45 2 99 101 102 99 93 87 80 74 107
47 2 100 102 103 100 94 88 81 75 108
025 50 2 101 104 104 101 95 89 82 76 109
53 2 102 105 105 102 96 90 83 77 110
56 2 104 106 107 104 98 92 85 79 112
60 2 105 107 108 105 99 93 86 80 113
63 2 106 109 109 106 100 94 87 81 114
42 4 88 91 89 84 81 74 66 60 95
45 4 89 92 90 85 81 74 67 61 96
47 4 90 93 91 86 82 75 68 62 97
50 4 91 94 92 87 83 76 69 63 98 The above data are valid for the operating ranges shown in
53 4 92 95 93 88 84 77 70 64 99 the charts on pages 30-31.
HCBT - Dimensions and weights - Fan Page 35
C E
A
F
D outs. B
X
N
K
The sketches show a right-hand model
Y
G1
G
n holes Z
P2 P3
P1
H2 H3 H3
J1 J2 J2
O1 O2 O2
M1 M2 N3
N1 N2
P4
P7 P8
H3 H4 H4
J2
J3 J3
O2
O3 O3
M3
N3 M3
N4
N4
Dimensions HCBT
Fan Imp. dia.
E F H2 H3 H4 M1 M2 M3 N1 N2 N3 N4 P1 P2 P3 P4 P7 P8
size bb
25 206 176 310 280 330 261 228 330 445 404 417 520 516 610 541 507 514 506
010 26-31 246 234 360 325 390 319 285 400 549 504 510 637 606 725 644 609 619 610
33-40 297 308 425 380 460 393 357 488 680 632 628 786 722 868 773 736 747 735
28 225 191 330 300 355 289 255 363 494 452 461 576 555 663 589 554 560 552
012 30-35 270 257 390 350 425 355 319 442 611 565 566 708 660 792 705 668 682 671
37-45 327 340 465 415 550 437 400 541 759 708 698 874 792 956 852 814 871 858
31 246 204 360 325 390 319 285 400 549 504 510 637 606 725 644 609 619 610
016 33-40 297 278 425 380 460 393 357 488 680 632 628 786 722 868 773 736 747 735
42-50 361 371 510 455 555 486 447 599 845 791 775 972 871 1054 941 901 914 899
25 206 126 310 280 330 261 228 330 445 404 417 520 516 610 541 507 514 506
30-35 270 220 390 350 425 355 319 442 611 565 566 708 660 792 705 668 682 671
020
37-45 327 302 465 415 550 437 400 541 759 708 698 874 792 956 852 814 871 858
47-56 398 406 560 500 610 541 500 664 943 885 862 1082 958 1164 1041 999 1012 995
31 246 159 360 325 390 324 285 403 554 504 510 641 606 728 649 609 619 610
33-40 297 233 425 380 460 398 357 491 685 632 628 789 722 871 778 736 747 735
025
42-50 361 326 510 455 555 491 447 602 850 791 775 975 871 1057 946 901 914 899
53-63 441 443 615 545 675 608 561 742 1058 992 961 1210 1056 1287 1153 1105 1125 1106
40 297 201 425 380 460 398 357 491 685 632 628 789 722 871 778 736 747 735
031 42-50 361 293 510 455 555 491 447 602 850 791 775 975 871 1057 946 901 914 899
60-63 489 480 675 600 740 677 629 825 1182 1112 1071 1357 1164 1425 1277 1228 1245 1223
50 361 251 510 455 555 491 447 602 850 791 775 975 871 1057 946 901 914 899
040 53-63 441 368 615 545 675 608 561 742 1058 992 961 1210 1056 1287 1153 1105 1125 1106
67-80 542 515 750 660 820 755 704 917 1319 1245 1194 1512 1292 1577 1415 1363 1385 1361
63 441 318 615 545 675 628 561 756 1078 992 961 1224 1056 1301 1173 1105 1125 1106
050 67-80 542 465 750 660 820 775 704 931 1339 1245 1194 1519 1292 1591 1435 1363 1385 1361
85-99 670 650 920 805 1005 960 884 1153 1669 1563 1489 1892 1590 1958 1765 1688 1714 1684
80 552 400 750 660 820 775 704 938 1339 1245 1204 1526 1302 1598 1435 1363 1385 1361
063
85-99 680 585 920 805 1005 960 884 1160 1669 1563 1499 1899 1600 1965 1765 1688 1714 1684
Dimensions L
Motor-
Fan size
size
010 012 016 020 025 031 040 050 063
63 338 - - - - - - - -
71 364 384 - - - - - - -
80 387 407 433 467 - -
90S - 420 446 480 521 - - - -
90L - 445 471 505 546 596 - - -
100L - 473 499 533 574 624 689 - -
112M - - 502 536 577 - 692 - -
132S - - 568 602 643 693 758 - -
132M - - - - - - 758 844 -
160 - - - 727 769 819 884 970 1070
180 - - - - 846 - - 1047 1147
200L - - - - 939 989 - 1140 1240
225M - - - - - - - 1202 1302
250M - - - - - - - 1209 1309
HCBT - Dimensions and weights Page 37
E1
A n1 x E C A1 x B1
Sheet steel
insert
E1
F1 n2 x F F1 t t
t + 2,5 t
+ 10 + 10
130 - 20 130 - 20
D
F
E
D1 D5 D3 D D1 D3 D1 D2 D3
D4 D outs. D2
ins. ins. ins. ins. ins. ins.
HCGB
HCL x
HCMx
HCH x -aaa-bb-cc-dd-ee-fff
Impeller
B = Backward-curved blades (Type B impellers are not available for the HCL fan).
P = Flat, backward-inclined blades.
T = Straight, radial blades.
2)
GP40-01 primer can be used where temperatures exceed 120C. This primer tolerates temperatures up to 150C and vaporises at higher
temperatures without emitting any toxic substances.
Ordering key - Accessories Page 42
2, 3
Duct
15
4 5
13, 14
4
6, 7
12 5
4
6, 7
8, 9
10
4
6, 7
11
2, 3
2, 3
11
6, 7
10
NB! Flanges comply with ISO 13351
Inlet
1 HCEZ-20 Inlet taper piece with protective screen and fixing lugs for connection to inlet without connecting
flange. (Pressure loss across the accessory, 0.35 x dyn. press. pd).
2 HCEZ-40, 41 Fabric duct, inlet without connecting flange. 2)
3 HCEZ-60 Flue gas duct, inlet without connecting flanges. 2)
4 HCEZ-27 Inlet flange, (fitted).
5 HCEZ-21 Inlet taper piece with protective screen and connecting flange for installation to inlet with
connecting flange. (Pressure loss across the accessory, 0.35 x dyn. press. pd).
6 HXEG Inlet vane control assembly, see pages 106 - 111. 1)
7 DMEG Regulating damper, see page 105. 1)
8 HCEZ-45, 46 Fabric duct, inlet with connecting flanges. 2)
9 HCEZ-65 Flue gas duct, inlet with connecting flanges. 2)
10 HCEZ-25 Counterflange, inlet, (not fitted).
11 HCEZ-29 Inlet connecting flange, for fitting ducts without connecting flanges.
Outlet
12 HCEZ-30 Protective screen, outlet.
13 HCEZ-50, 51 Fibre duct, outlet, with connecting flanges. 2)
14 HCEZ-70 Flue gas duct, outlet with connecting flanges. 2)
15 HCEZ-35 Counterflange, outlet, (not fitted).
1)
NB! Inlet vane assemblies/regulating dampers must not be connected directly to the fan without checking that the anti-vibration mountings can
cope with the increased component load on the fan.
2)
For size and temperature limits, please refer to the appropriate ordering keys.
Sound data Page 45
Symbols Formulae:
Lwtot = total sound power level for the relevant sound Lwtot = Lwtot + K1 + K2 + K3
path and appropriate throttling curve...................... dB o
Lwtot = total sound power level to inlet or outlet duct when For division into octave bands, use the formula:
o
the fan is operating on the throttling curve giving Lw = Lwtot + Kok
the lowest sound power level.................................. dB
Lw = Lwtot divided into octave bands .............dB (ref. 10-12 W) Sound paths: a = to inlet or outlet duct.
b = to surroundings (free-inlet fan).
K1 = corr. for diff. throttling curves and sound paths....... dB
c = to surroundings (duct-connected fan).
K2, K3 = correction for different sound paths........................ dB
Kok = approximate deviation from Lwtot NB! The stated values refer to sound power levels. Some fan manufac-
for the particular octave band................................. dB turers still quote sound pressure levels even though these vary with the
acoustic characteristics of the surroundings and distance from the fan.
L = throttling curve = 10 pd/Dpt Sound pressure levels, sometimes weighted as dB(A) or dB(C) values,
Dp
t = total pressure rise................................................... Pa are considerably lower than the corresponding sound power level Lwt.
110
a l pre a 2300-4700 0 -4 -9 -10 -6 -14 -18 -23 -23
Tot 0 800
c
00
600 4
c
100
c
1.5 +5
c a Sound paths: a = to inlet or outlet duct.
1.0 , 0
a,b b = to surroundings (free-inlet fan).
0.5 -5 b
-10 c c = to surroundings (duct-connected fan).
0
2 3 4 5 0 1000 2000 3000
L Dpt, Pa
800
Lwtoto, dB
100
c
K2, dB
ss 0 6
pre 800
c
110
2300-4700 0 -9 -8 -7 -5 -9 -13 -16 -21
800
c
400
c
100 600
c
0
K1, dB
, c
1 a ,b -5 b Sound paths: a = to inlet or outlet duct.
c b = to surroundings (free-inlet fan).
-10
0 -15 c = to surroundings (duct-connected fan).
2 3 4 5 4000 8000 12 000
L Dpt, Pa
2 5 10 20 50 70 x 103 Kok, dB
130 Sound Speed
Pa
000 path range K3 Octave band, mid-frequency, Hz
12
ise
120 re r 600
0 r/min dB 63 125 250 500 1000 2000 4000 8000
c
su
res 0
al p 800 300-1175 0 -7 -4 -6 -11 -14 -22 -29 -35
c
Tot 0 0
4 0 200 a 1175-2300 0 -8 -5 -5 -8 -14 -20 -27 -33
c
0
c
Lwtoto, dB
400
c
600
c
c
K2, dB
b,
a, -10 b b = to surroundings (free-inlet fan).
1
-15 c = to surroundings (duct-connected fan).
c
0 -20
2 3 4 5 0 4000 8000 12 000
L Dpt, Pa
Dimensions and weights - Fan Page 47
C
E
D3*
A
F2 F
F1 D outs. B
D2 h8
X
J2 J1
N
K R
CL Inlet
* Minimum permitted pulley diameter
= D3 (refer to tables on pages 48 - 49).
CL Outlet
J2 J1
Inspection cover location
When delivered, the inspection cover is
Y Y
placed in the upper part of the casing,
30o above the horizontal centre line.
n holes Z
N2
N1 M2
N3
M1
P2
P3
P1
H2 H3 H3
N4
N4
M3
N3 M3
P4
P7 P8
H3 H4
H4
Dimensions
HCG HCL HCM HCH H2 H3 H4 M1 M2 M3 P1 P2 P3 P4 P7 P8
025 020 - - 310 280 330 261 228 330 516 610 541 507 514 506
031 025 016 - 360 325 390 319 285 400 606 725 644 609 619 610
- - 020 - 390 350 425 355 319 442 660 792 705 668 682 671
040 031 025 010 425 380 460 393 357 488 722 868 773 736 747 735
- - - 012 465 415 550 437 400 541 792 956 852 814 871 858
050 040 031 016 510 455 555 486 447 599 871 1054 941 901 914 899
- - - 020 560 500 610 541 500 664 958 1164 1041 999 1012 995
063 050 040 025 615 545 675 608 561 742 1056 1287 1153 1105 1125 1106
031 675 600 740 677 629 825 1164 1425 1277 1228 1245 1223
080 063 050 040 750 660 820 755 704 917 1292 1577 1415 1363 1385 1361
100 080 063 050 920 805 1005 960 884 1160 1600 1965 1765 1688 1714 1684
HCGB
Fan Motor size
A B C D D3min E F K N Wt. imp.
size IEC
025 80-112 250 200 165 255 85 206 101 465 338 3,1
031 80-132 315 250 191 320 100 246 127 515 363 5,0
040 80-112 400 315 223 405 132 297 158 582 397 7,8
040 132-160 400 315 223 405 132 297 158 672 487 7,8
050 90-160 500 400 267 505 140 371 201 727 499 13,5
063 100-160 630 500 317 635 224 451 253 903 624 23,0
063 180-200 630 500 317 635 224 451 253 988 709 23,0
080 112-200 800 630 382 805 212 552 318 1076 730 42,0
080 225 800 630 382 805 212 552 318 1226 880 42,0
100 132-225 1000 800 467 1005 265 680 400 1265 835 71,0
HCL(P,T)
Fan Motor size D3min D3min Wt. imp. Wt. imp.
A B C D E F K N
size IEC HCLP HCLT HCLP HCLT
020 80-132 200 160 145 205 80 95 206 126 425 318 3.6 4.0
025 80-160 250 200 165 255 90 125 246 159 465 338 4.8 5.1
031 80-112 315 250 191 320 100 150 297 201 517 364 7.9 7.7
031 132-180 315 250 191 320 100 150 297 201 607 454 7.9 7.7
040 100-160 400 315 223 405 150 180 361 251 642 457 14.8 14.0
040 180-225 400 315 223 405 150 180 361 251 757 572 14.8 14.0
050 100-160 500 400 267 505 180 250 441 318 803 574 28.0 25.0
050 180-225 500 400 267 505 180 250 441 318 888 659 28.0 25.0
063 132-200 630 500 317 635 180 315 552 400 946 665 42.0 46.0
063 225-280 630 500 317 635 180 315 552 400 1096 815 42.0 46.0
080 160-225 800 630 382 805 280 400 680 500 1095 750 70.0 71.0
080 250-315 800 630 382 805 280 400 680 500 1246 900 70.0 71.0
Dimensions and weights Page 49
HCM(B,P,T)
Fan Motor size D3min D3min D3min Weight, impeller
A B C D E F K N
size IEC HCMB HCMP HCMT HCMB HCMP HCMT
016 80-132 160 125 128 164 - 90 95 246 204 390 301 - 4.9 3.9
020 80-112 200 160 145 205 - 100 106 270 220 425 318 - 6.5 6.5
020 132-160 200 160 145 205 - 100 106 270 220 516 408 - 6.5 6.5
025 80-112 250 200 165 255 - 112 125 297 233 467 339 - 8.5 7.5
025 132-200 250 200 165 255 - 112 125 297 233 557 429 - 8.5 7.5
031 100-160 315 250 191 320 118 150 180 361 293 577 424 16.7 14.5 14.6
031 180-225 315 250 191 320 118 150 180 361 293 692 539 16.7 14.5 14.6
040 100-160 400 315 223 405 160 190 250 441 368 718 532 30.0 25.0 24.0
040 180-225 400 315 223 405 160 190 250 441 368 803 617 30.0 25.0 24.0
050 132-200 500 400 267 505 160 200 280 542 465 846 615 43.0 43.0 47.0
050 225-280 500 400 267 505 160 200 280 542 465 996 765 43.0 43.0 47.0
063 132-225 630 500 317 635 212 250 400 680 585 965 685 72.0 73.0 74.0
063 250-315 630 500 317 635 212 250 400 680 585 1116 835 72.0 73.0 74.0
HCH(B,P,T)
Fan Motor size D3min D3min D3min Weight, impeller
A B C D E F K N
size IEC HCHB HCHP HCHT HCHB HCHP HCHT
010 80-112 100 80 105 104 75 - 95 297 308 347 279 7.6 - 5.9
010 132-160 100 80 105 104 75 - 95 297 308 437 369 7.6 - 5.9
012 80-112 125 100 115 129 80 - 106 327 340 367 289 9.4 - 7.6
012 132-180 125 100 115 129 80 - 106 327 340 458 379 9.4 - 7.6
016 100-160 160 125 128 164 90 - 125 361 371 452 362 14.2 - 11.7
016 180-225 160 125 128 164 90 - 125 361 371 567 477 14.2 - 11.7
020 100-160 200 160 145 205 125 - 140 398 406 487 379 18.1 - 14.7
020 180-250 200 160 145 205 125 - 140 398 406 603 494 18.1 - 14.7
025 100-160 250 200 165 255 140 170 180 441 443 603 474 25.0 23.0 21.0
025 180-250 250 200 165 255 140 170 180 441 443 688 559 25.0 23.0 21.0
031 132-200 315 250 191 320 140 170 180 489 480 695 540 32.0 34.0 29.0
031 225-280 315 250 191 320 140 170 180 489 480 845 690 32.0 34.0 29.0
040 160-200 400 315 223 405 160 212 224 542 515 761 573 41.0 41.0 36.0
040 225-315 400 315 223 405 160 212 224 542 515 911 723 41.0 41.0 36.0
050 160-225 500 400 267 505 224 280 280 670 650 865 635 76.0 67.0 64.0
050 250-315 500 400 267 505 224 280 280 670 650 1016 785 76.0 67.0 64.0
1)
Weights are exclusive of motor and belt drive.
Dimensions and weights Page 52
E1
A n1 x E C A1 x B1
Sheet steel
insert
E1
F1 n2 x F F1 t + 2,5 t t t
+ 10 + 10
130 - 20 130 - 20
D
F
E D
D1 D5 D3 D4 D1 D3 D2 D1 D2 D3
D outs. ins.
ins. ins. ins. ins. ins.
HCEZ-01-bbb-c-dd
Form of delivery
1 = fitted to the ordered fan.
9 = delivered requiring assembly.
Rated power of motor: 4 kW Rated power of motor: 5.5 kW Rated power of motor: 7.5 kW
Fan Code Fan Code Fan Code
speed suf- speed suf- speed suf-
Motor Motor Motor
fix Suitable for: fix Suitable for: fix Suitable for:
r/m bbb dd = r/m bbb dd = r/m bbb dd =
6370 230 01-05 6380 280 02-05 6340 330 03-05
6040 231 01-05 6030 281 02-05 6030 331 03-05
5700 232 01-05 5710 282 02-05 5710 332 03-06
5380 233 01-05 5420 283 02-05 5390 333 03-06
5070 234 01-05 5100 284 02-06 5080 334 03-06
4800 235 01-06 4840 285 02-06 4810 335 02-06
APAL-2-
4560 236 01-06 4570 286 APAL-2- 02-06 4510 336 APAL-2- 02-07
00400-c-0
4280 237 01-06 4340 287 00550-c-0 02-06 4280 337 00750-c-0 02-07
4030 238 01-06 4110 288 02-07 4000 338 02-07
2 poles
3760 239 01-06 3870 289 2 poles 02-07 3770 339 2 poles 02-07
3560 240 01-07 3670 290 02-07 3560 340 02-07
Size 112M
3360 241 02-07 3430 291 Size 132S 02-07 3360 341 Size 132S 02-08
as per IEC
3190 242 02-07 3240 292 as per IEC 02-07 3190 342 as per IEC 02-08
3020 243 02-07 3030 293 02-08 3020 343 02-08
2850 244 02-08 2860 294 02-08 2860 344 04, 06-08
2690 245 02-08 2680 295 02-08 2700 345 04, 06-08
2550 246 02-08 2520 296 04, 06-08 2550 346 04, 06-08
2400 247 04, 06-08 2380 297 04, 06-08 2410 347 04, 06-08
2240 248 04, 06-08 2280 298 04, 06-08 2250 348 04, 06-08
2110 249 04, 06-08 2200 299 04, 06-08 2170 349 04, 06-08
2010 250 04, 06-08 2090 300 04, 06-08 2050 350 04, 06-08
1890 251 04, 06-08 1970 301 04, 06-08 1950 351 06-08
1790 252 APAL-4- 04, 06-08 1860 302 04, 06-08 1810 352 06-08
1690 253 00400-c-0 04, 06-08 1740 303 APAL-4- 06-08 1700 353 APAL-4- 06-08
1600 254 06-08 1650 304 00550-c-0 06-08 1610 354 00750-c-0 06, 08
1510 255 4 poles 06-08 1540 305 06-08 1520 355 06, 08
1435 256 06-08 1450 306 4 poles 06, 08 1435 356 4 poles 06, 08
1360 257 Size 112M 06-08 1370 307 06, 08 1355 357 06, 08
1290 258 as per IEC 06, 08 1280 308 Size 132S 06, 08 1280 358 Size 132M 08
1220 259 06, 08 1200 309 as per IEC 06, 08 1220 359 as per IEC 08
1150 260 06, 08 1130 310 08 1150 360 08
1070 261 06, 08 1060 311 08 1040 361 08
1000 262 06, 08 1010 312 08 1020 362 08
960 313 08
Fan type - Size Motor c-c distance Fan type - Size Motor c-c distance Fan type - Size Motor c-c distance
size size size
HCG HCL HCM HCH IEC Min. * Max. * HCG HCL HCM HCH IEC Min. * Max. * HCG HCL HCM HCH IEC Min. * Max. *
80 410 500 90 640 735 112 915 1050
90 420 515 100 655 770 132 935 1100
025 020 -- -- 100 435 555 112 665 795 160 965 1125
112 445 582 132 685 845 180 990 1150
050 040 031 016
132 470 565 160 715 875 080 063 050 040 200 1010 1205
80 465 555 180 740 895 225 1035 1230
90 475 570 200 765 955 250 1065 1265
100 490 610 225 795 935 280 1100 1310
031 025 016 -- 315 1140 1285
112 500 635 100 705 825
132 525 695 112 720 850 132 1110 1280
160 565 670 132 735 900 160 1140 1300
80 500 590 -- -- -- 020 160 770 930 180 1165 1325
90 515 610 180 790 950 200 1190 1380
100 080 063 050
100 525 645 200 805 1000 225 1210 1405
-- -- 020 -- 225 835 1025 250 1240 1440
112 540 675
132 555 720 250 865 1010 280 1275 1490
160 590 695 100 765 885 315 1315 1460
80 540 630 112 775 910
90 550 645 132 795 960
100 565 680 160 825 980
063 050 040 025
112 575 710 180 850 1005 * Fitting and after installation tensioning
040 031 025 010 200 875 1065 tolerances must be observed. Check the
132 595 760
160 625 785 225 900 1090 belt supplier's recommendations.
180 650 805 250 930 1070
200 675 790 132 860 1025
80 585 675 160 895 1050
90 590 685 180 895 1050
100 605 725 -- -- -- 031 200 935 1130
-- -- -- 012 112 615 750 225 960 1155
132 635 800 250 995 1195
160 665 825 280 1030 1170
180 690 805
Key charts - belt-driven fans Page 58
HCGB, HCLP, HCM(B,P) and HCH(B,P) The charts are valid for gas at a density of 1.2 kg/m2.
05 3 09 16
3000 LP 02 0 0 11 0
02 5 2
0
H
2000 C
G
B
02 03 04 05 06 08 10 11 14 16
5 1 0 0 3 0 0 2 0 0
12
5
1000
800
0.3 0.4 0.5 1 2 3 4 5 10 20 30 40 50 80
Gas flow, m3/s
016
4000
3000
2000
1000
800
0.06 0.1 0.2 0.3 0.4 0.5 1 2 3 4 5 10 14
Gas flow, m /s 3
Fan charts - Belt-driven fans Page 59
Fan charts
In general, the charts specify three maximum speeds for Pressure losses across accessories:
maximum temperatures of 100, 200 and 350oC. Within HCEZ-20 and -21 inlet taper piece: 0.35 x dynamic pressure.
these limits, the maximum speed can be determined by
linear interpolation between 100 and 200oC or between HCEZ-20 HCEZ-21
200 and 350oC.
HCGB
4 360 4
2000 0
450 340
0 0
320
400 0
0 300 5
5 280 0
3500 1000 26000
1000 24
3000 22 00
2500 20 00
180000
2000
10
10
0 0
0.0 0.1 0.4 0.6 0.8 1.0 1.2 0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0 2000 0 Gas flow, m3/s
2500 Gas flow, m3/s 1800 000
2
3000 220000
24
2600
Power demand, kW
Power demand, kW
3500
2800
0
4000 1 300
0
320
1 0
450 340
0
0
360
5000 2
380
0
00
40
nmax, r/min 00 nmax, r/min
55 00
2 < 200C: 5700 < 200C: 4290 42 n
min 3 i
350C: 4870 0 r/ 350C: 3925 r/ m
J (= 1/4 GD2): 0.025 kg m2 nmax = 570 J (= 1/4 GD2): 0.08 kg m2 nmax = 4290
Fan charts - Belt-driven fans Page 60
The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.
HCGB
Gas flow, m3/h Gas flow, m3/h
0 5000 10 000 0 5000 10 000 15 000
1
4000 1 040 2 050
nm nm
ax = 3 2 ax = 2
840 860
3000 280 r/min
r /m 0 3
360 in
3000 0 3 260
340 0
0 240
Total pressure rise, Pa
10 10
0 0
0 1 2 3 0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0
0 0
Gas flow, m3/s Gas flow, m3/s
1800
1 200 0
2200
Power demand, kW
Power demand, kW
2
2400 1800
2
2600 2000
2800 4
3 0
300
0 220
4 0
320 6 240
0
0
5 340
0
260
0 0 8
6 36 nmax, r/min
nmax, r/min
< 100C: 2860 00
7 < 200C: 3840 200C: 2740 28
n 10 in
350C: 3115 /mi / m
J (= 1/4 GD2): 0.212 kg m2
nm =
ax 3 8 40 r 350C: 2360 nm = 2
ax 86 0 r
8 J (= 1/4 GD2): 0.51 kg m2
2000
Total pressure rise, Pa
2000 1800
5
1600 1200
1400
1000
1000 1200 1000
1000
10
0 0
0 1 2 3 4 5 6 7 8 0 2 4 6 8 10 12 14
0 0
Gas flow, m3/s Gas flow, m3/s
1000
2 1200
1000
Power demand, kW
Power demand, kW
4 1400
1200
6 1600 10
8 0 0
180 140
10
0
12 200
20 00
nmax, r/min 16
14 nmax, r/min
< 100C: 2240
200C: 2145 00 < 200C: 1730
16 22 350C: 1510 n
350C: 1840 i n nm = 1730 r/mi
2 2
nma = 22
x 40 r/m 2
28 J (= 1/4 GD ): 3.77 kg m
2 ax
18 J (= 1/4 GD ): 1.3 kg m
Fan charts - Belt-driven fans Page 61
The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.
2000
Power demand, kW
10 800
900
20 900
1000
1000
20 0 30
110
0
0 40 110
120
30 0
50 120
nmax, r/min 00 nmax, r/min
13
< 100C: 1375 < 100C: 1310
40 200C: 1240 60 200C: 1190
in i n
350C: 1065 nm = 1375 r/m 350C: 1020 nm = 1310 r/m
ax 2 2 ax
J (= 1/4 GD2): 10.3 kg m2 70 J (= 1/4 GD ): 18.7 kg m
2000
Total pressure rise, Pa
800
2000
5 5
800
700
700
600
1000 600 1000
500
500
400 400
10 300 10
300
0 0
0.0
0 10 20 30 36 0 10 20 30 40 46
0 300 0 300
400 Gas flow, m3/s 400 Gas flow, m3/s
500 500
10 600
600
Power demand, kW
Power demand, kW
20
700
20 700
800
40
30
800
900
40
60
0
90
0
50 100
nmax, r/min nmax, r/min
nmax, r/min 80 < 100C: 1010
< 100C:1090
60 < 200C: 5700 200C: 915
200C:1000 in
350C: 4870 i n
350C: 865 nm = 1090 r/m 350C: 780 nm = 1010 r/m
1/4 GD2): 0.023 kg m2 ax ax
70 JJ (=
(= 1/4 GD2): 31.6 kg m2 100 J (= 1/4 GD2): 57.7 kg m2
Fan charts - Belt-driven fans Page 62
The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.
HCGB
Gas flow, m3/h
0 50 000 100 000 150 000 200 000
1
4000
nmax = 9 2 160
65 r /min
3
900
3000
4
800
Total pressure rise, Pa
5
2000 700
600
1000 500
400
300 10
0
0 10 20 30 40 50 60
0 300
400 Gas flow, m3/s
20 500
Power demand, kW
600
40
700
60
80 800
100
0
120 nmax, r/min 90
< 100C: 965
200C: 890
140 in
350C: 755 nm = 965 r/m
J (= 1/4 GD2): 110.5 kg m2 ax
160
HCLP
Gas flow, m3/h Gas flow, m3/h
0 1000 2000 3000 4000 0 1000 2000 3000 4000 5000 6000
4000 1 1
2 4000 2
nm nm
ax = 6
100 3 020 ax = 4
900
025
r /m 3
in r/m
600 4 480 in
0 0
3000 4
3000
5 5
500 400
0 0
Total pressure rise, Pa
2000 2000
400
0
3000
2300 1900
0 0
0 0.2 0.4 0.6 0.8 1.0 0 0.5 1.0 1.5 2. 0
0 0
2300 Gas flow, m3/s 1900 2000 Gas flow, m3/s
3000
Power demand, kW
Power demand, kW
1 3000
4000
1
2
5000 4000
4
6000 nm 4800
nmax is not temperature dependent nmax is not temperature dependent ax = 4900 r/min
J (= 1/4 GD2): 0.022 kg m2 nmax = 6100r/min J (= 1/4 GD2): 0.067 kg m2
2.8 5
Fan charts - Belt-driven fans Page 63
The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.
HCLP
Gas flow, m3/h
Gas flow, m3/h
0 5000 10 000 14 000 0 10 000 20 000
1 6000 2 n
nm 2 ma 3
6000 ax =
490 031 1 x=
38
70
040
0r 3 38 4
480 /m 5000 00 r /m
0 in in
5000 4 5
5 4000
4000 4000
300
0
Total pressure rise, Pa
0 0
0 1 2 3 3.8
0 1 2 3 4 5 6
0
19002000 Gas flow, m /s 0
Gas flow, m /s
2000
Power demand, kW
3000
Power demand, kW
10
4000 3000
10
nmax, r/min 20
00 nmax, r/min
< 200C: 4900 nm = 490048r/min < 100C: 3870
ax
350C: 4580 200C: 3580
J (= 1/4 GD2): 0.16 kg m2 350C: 3140 n
ma = 3800
18 J (= 1/4 GD2): 0.44 kg m2 x 3 87
0 r/min
28
2000
Total pressure rise, Pa
2000 2000
1000
1000 10 1000 10
1000
0 0
0 1 2 3 4 5 6 7 8 0 2 4 6 8 10 12
0 0
1000 Gas flow, m3/s Gas flow, m3/s
1000
Power demand, kW
Power demand, kW
10
10
2000
20
20 30
The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.
800 10
1000 1000 10
600 500
0 0
0 10 20 23 0 10 20 26
0 600 0
Gas flow, m3/s 500 Gas flow, m3/s
800
10 10
1000
Power demand, kW
Power demand, kW
20 20
1200 1000
30 30
1400 40
40
50
50
60
60 1600
nmax, r/min nmax, r/min
< 100C: 1770 70 < 100C: 1490 1400
70 1700
200C: 1640 200C: 1370
350C: 1440 n 80 350C: 1210
m ax = n
80 J (= 1/4 GD2): 8.8 kg m2 1770 r/min J (= 1/4 GD2): 15.3 kg m2 max =
1490 r/min
90
100
0
2000
2000
800
10 1000 10
1000 600 500
400
0 0
0 10 20 30 36 0 10 20 30 40
0 400 0
Gas flow, m3/s 500 Gas flow, m3/s
600
20 800 20
Power demand, kW
Power demand, kW
40 40
1000
60
60
80 1000
80 1200
100
nmax, r/min nmax, r/min
100
< 100C: 1400 1100
< 100C: 1180
200C: 1290 120 200C: 1090 n
350C: 1130 n 350C: 960 ma
120 ma x = 1 x = 118
J (= 1/4 GD2): 27.5 kg m2 400 r/min J (= 1/4 GD2) 47 kg m2 0 r/min
140
Fan charts - Belt-driven fans Page 65
The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.
HCLP
Gas flow, m3/h Gas flow, m3/h
0 100 000 200 000 0 100 000 200 000 260 000
5000
1 2 n 6000 2
ma 3
x =
10 125 1 n
ma
x =1
3 140
80 4 06
r/m 5000 0r 4
4000 100 in 100 /m
0 0 in
5
5
4000
3000
800
Total pressure rise, Pa
600 2000
600
1000 10
10
400 1000 400
0 0
0 10 20 30 40 50 56 0 10 20 30 40 50 60 70
0 0
400 Gas flow, m3/s 400 Gas flow, m3/s
20
600 600
Power demand, kW
Power demand, kW
40
60 100
800
80 800
100
120 200
140
nmax, r/min 1000 nmax, r/min
< 100C: 1080 < 100C: 1060 1000
160
200C: 1000 200C: 980 n
n ma
350C: 880 ma 350C: 800 x =1
180 x = 108 300 060 r/
J (= 1/4 GD2): 83 kg m2 0 r/min J (= 1/4 GD2): 166 kg m2 m in
2
5000 1 nm
ax =
3
160
88 4
85 0 r/m
0 in
4000 800
5
3000 700
Total pressure rise, Pa
600
2000
500
1000 400 10
300
0
0 10 20 30 40 50 60 70 80 90
500
Power demand, kW
100 600
700
200
800
nmax, r/min
< 100C: 880
200C: 820 850
300 350C: 720 n
J (= 1/4 GD2): 268 kg m2 ma =
x 880 r/min
Fan charts - Belt-driven fans Page 66
The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.
HCLT
Gas flow, m3/h Gas flow, m3/h
0 1000 2000 3000 4000 0 1000 2000 3000 4000 5000 6000
2800 2800
1
2 2
1 3
3
4
020 n
ma 4
025
n x =3
ma
x = 93
49 5 0r
5 /m
48 0 r/m 38
00
in
2000 0 in 2000 5
46 0 36
00 00
44
0 34
420 0 00
400 0 320
0
380 0 300
0 0
280
340 0
1000 0 1000
300 240
0 0
260 2000 10
0
2200 1600
0 0
0 0.2 0.4 0.6 0.8 1 0 0.5 1 1.s5
0 0
2200 Gas flow, m 3/s 1600 Gas flow, m3/s
2600 2000
1
300 240
Power demand, kW
Power demand, kW
1 0 0
340 2 280
0 0
30
38 0 0
00 3
2 32
40 00
00
4 34
42 00
0
44 0
3 00 36
5
00
46
n 00 n
m 6 m 38
ax 48 ax 00
4 = =
49 00 39
50 3 0
r/ 7 r/
nmax is not temperature dependent nmax is not temperature dependent
m
m
in
in
5 8
0
Total pressure rise, Pa
240
0 180
220 0
0
1000 200 1000 160
0 0
180 140 10
0 10 0
160 120
0 0
1200 1000
0 0
0 1 2 0 1 2 3 4
0 0
1200 Gas flow, m3/s 1000 Gas flow, m3/s
1200
1600 2
1800 1400
Power demand, kW
Power demand, kW
200 4 160
0 0
220
0 6 180
0
240
5 0 8 20
00
26
00 10
22
28 00
12
00
n 14 n
m 30 m 24
ax 00 ax
10 = = 00
31 16 24
20 80
r/m r/m
i 18 n i
nmax is not temperature dependent max is not temperature dependent
n
The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.
HCLT
Gas flow, m3/h Gas flow, m3/h
0 10 000 20 000 0 10 000 20 000 30 000 40 000
2900 2900
2 2
1
n
3 050 1
n
3 063
ma ma 4
x =1 4 x =
97 15
0r 60 5
19 /m 5 15 r/m
00 in 00 in
2000 2000
18
00 14
170 00
0 130
160 0
Total pressure rise, Pa
0 0
0 1 2 3 4 5 6 7 0 2 4 6 8 10
0 0
800 Gas flow, m 3/s 600 Gas flow, m3/s
700
1000 800
120 900
Power demand, kW
Power demand, kW
0 100
10 0
140 110
0 0
10
15 12
00 00
16 20
00 13
00
17
00
14
20 18 30 00
00
n 19
m n 15
ax 00 m 00
= ax
19 40 =
7 0 15
r/m 6 0
n is not temperature dependent i r/
nmax is not temperature dependent
30 J max
m
n
in
50
100
Total pressure rise, Pa
1000 800
10
600
400
0
0 5 10 15 18
0 400
Gas flow, m3/s
600
10
Power demand, kW
800
20
30
10
00
40
50
n
60 m
ax
=
12
12
4 0
00
70 r/
nmax is not temperature dependent
m
80
Fan charts - Belt-driven fans Page 68
The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.
HCMB
Gas flow, m3/h Gas flow, m3/h
0 5000 10 000 14 000 0 10 000 20 000
1 2 2
n 8000 1 n
ma
x =
3 031 ma
x =
3 040
8000 44 45 33
00 20 7000 90
r/m 32 r/m
4 00
in in 4
40 6000 30
00 00
6000
5 5000 5
Total pressure rise, Pa
2000 2000
2000
10 10
1400 1000
1000
0 0
0 1 2 3 4 0 1 2 3 4 5 6
0 1400 0 1000
Gas flow, m3/s Gas flow, m3/s
2000
2000
Power demand, kW
Power demand, kW
0
300
10
10
00 00
40 20 30
00
nmax, r/min nmax, r/min 32
0
20 < 100C: 4520
440 < 100C: 3390
200C: 4180 200C: 3140 in
350C: 3670
30 350C: 2750 r/m
n 90
J (= 1/4 GD2): 0.48 kg m2 max = 4520 r/min J (= 1/4 GD2): 1.18 kg m2 nmax = 33
25
200
4000 0
4000
3000 3000
0 0
0 1 2 3 4 5 6 7 8 9 0 2 4 6 8 10 12 14 16
0 0
1000 Gas flow, m3/s Gas flow, m3/s
1000
10
Power demand, kW
Power demand, kW
10 20
30
0
20 200
40
50
30
00
60 20
70
40
00
The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.
HCMB
Gas flow, m3/h Gas flow, m3/h
0 10 000 20 000 30 000 40 000 50 000 60 000 70 000 0 20 000 40 000 60 000 80 000 90 000
9000 9000
2 2
n
8000 1
n
ma
x= 3 071 8000 1 ma
x=
3 080
19 17
19 20 17 30
0 r/m 0 r /m
7000 18 0 i 4
7000 16 0 in
4
00 00
n
6000 6000
160 5 14 5
5000 0 5000 00
140
4000 0 4000 120
0
0 0
0 2 4 6 8 10 12 14 16 18 0 5 10 15 20 25
Power demand, kW
Power demand, kW
20 0
120
0
120
00
14 50
40
00
00 14
16
60
00 00
18 16
100
80
nmax, r/min nmax, r/min
00
< 100C: 1920 00 < 100C: 1730
19
17
in 200C: 1600 in
200C: 1780 r/m /m
100 350C: 1520 20 350C: 1350 3 0r
J (= 1/4 GD2): 16.3 kg m2 19 J (= 1/4 GD2): 25.8 kg m2 17
= =
ax 140
nm ax
nm
0 100
0
4000
4000
100
0 3000 800
3000
800 2000
2000 600
600 10 10
1000 1000 400
0 0
0 10 20 30 0 10 20 30 39
0 0 400
600 Gas flow, m3/s Gas flow, m3/s
600
20 800
800
Power demand, kW
Power demand, kW
0
40 100
60 0
00 100
12
80
100
100
00 00
14 12
120
140
nmax, r/min nmax, r/min
< 100C: 1590 < 100C: 1370
160
200C: 1470 200C: 1260
350C: 1210 n 200 350C: 1080 n
180 ma =
J (= 1/4 GD2): 47 kg m2 x 1590 r/min J (= 1/4 GD2): 79 kg m2 ma =
x 1370 r/mi
n
Fan charts - Belt-driven fans Page 70
The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.
HCMB
Gas flow, m3/h Gas flow, m3/h
0 5000 100 000 150 000 180 000 0 100 000 200 000
9000 9000
2 2
1 n 3
8000 1
n
m
12 ax =
3 112 8000 ma
x = 125
00 12 10
20 90
7000 r 7000 r /m
4 10 in 4
00
/m
in
6000 6000
100 5 5
0
5000 5000
80
0
4000 4000
800
3000 3000
600
2000 600 2000
10 400 10
1000 400 1000
0 0
0 10 20 30 40 50 0 10 20 30 40 50 60
0 400 0
Gas flow, m 3/s 400 Gas flow, m3/s
600
600
Power demand, kW
Power demand, kW
800
100
0
100 80
00
10
200
00
10
200
nmax, r/min nmax, r/min
00
HCMP
Gas flow, m3/h Gas flow, m3/h
0 1000 2000 3000 0 1000 2000 3000 4000 5000 6000 7000
9000 11 000
1
2
8000 016 10 000
nm 020
1 ax =
65 3
7000 nm 2 00
ax = r /m
62 i
0 60
6000 60 0 r/m 3 00
n
00 4
in
5000
4 5
Total pressure rise, Pa
Total pressure rise, Pa
500
500 5000 0
4000 0
5
2000
300 3000
0 10
10
1000 200 200
0 0
0 0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 0 0.5 1.0 1.5 2.0
0 2000 0 2000 3
3000 Gas flow, m3/s Gas flow, m /s
3000
1 4000
Power demand, kW
4000
Power demand, kW
2 5
5000
5000
6000
4 10
6000
n
ma = n
x 6 2 00 m ax =
r/min
6500 r/min
5 tmax = 200C nmax = 6500 r/min
nmax is not temperature dependent tmax = 350C nmax = 5500 r/min
J (= 1/4 GD2): 0.056 kg m2 J (= 1/4 GD2): 0.09 kg m2
6 15
Fan charts - Belt-driven fans Page 71
The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.
HCMP
Gas flow, m3/h Gas flow, m3/h
0 2000 4000 6000 8000 10 000 0 5000 10 000 15 000
10 000
1 2 2
7000 n 3
n
ma
x = 3 025 1
ma
380 x = 3 4
031
0 9 00
57 r /m
0 0 6000
r/ in
5
m
in
50 4 5000
00
300
5 4000 0
5000
400
0 3000
0 1500 0
2000 Gas flow, m3/s Gas flow, m3/s
3000 2000
Power demand, kW
Power demand, kW
5
4000
10
3000
10
0
500
20
15 nmax, r/min
tmax = 200C nmax = 5700 r/min 200C: 3900 n 3800
ma
tmax = 350C nmax = 4800 r/min n 350C: 3700 x = 39 0
0 r/min
ma =
J (= 1/4 GD2): 0.17 kg m2 x 5700 r/min J (= 1/4 GD2): 0.43 kg m2
19 27
5000
4000 200
0
Total pressure rise, Pa
4000
3000 2000
3000
2000 10
2000 10
1000 1000
1000 1000
0 0
0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 8 9 10 11 12
0 1000 3/s 0
Gas flow, m 1000 Gas flow, m3/s
10
Power demand, kW
Power demand, kW
10 2000
20
30
2000
20
40
50
nmax, r/min
30 nmax, r/min
< 100C: 2520
< 200C: 3000 n 200C: 2330 2400
350C: 2700 ma 60
x =3 350C: 2050 n
J (= 1/4 GD2): 1.06 kg m2 000 ma
r/min J (= 1/4 GD2): 2.8 kg m2 x = 252
0 r/min
70
Fan charts - Belt-driven fans Page 72
The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.
5000
4000 140
0
4000
3000 1200
3000
1000 10 1000
2000 10
2000
800
1000 600
1000
0 0
0 5 10 15 0 5 10 15 20 25
0 0 600 3/s
Gas flow, m3/s 800 Gas flow, m
10 1000 1000
Power demand, kW
Power demand, kW
20
1200
30
50
40 1400
50
60 1600
100
70
80
0
90
nmax, r/min nmax, r/min 180
< 200C: 2000 < 200C: 1900 n
350C: 1750 n 150 ma
100 ma 350C: 1480 x = 19
J (= 1/4 GD2): 8.6 kg m2 x = 20 00 r/min
00 r/min J (= 1/4 GD2): 16 kg m2
110 170
120
4000 0
4000 100
0
3000 100
0
3000
10 800 10
2000 800
2000
600 600
1000 1000
0 0
0 10 20 30 0 10 20 30 40
0 0
600 Gas flow, m 3/s 600 Gas flow, m3/s
800
800
1000
Power demand, kW
Power demand, kW
50 1000
1200 100
1200
100
1400
The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.
HCMP
Gas flow, m3/h Gas flow, m3/h
0 50 000 100 000 150 000 0 100 000 200 000
2 3 2
8000 n 10 000 n 3
1 ma
x =
13 4
100 1 ma
x = 112
0 0r 9000 1 28 4
7000 /m 12 0r
120 in 00 /m
0 5 8000 in 5
6000
7000
5000 100 6000 100
0 0
4000 5000
0 0
0 10 20 30 40 0 10 20 30 40 50 60
0 400 0 400
Gas flow, m3/s Gas flow, m3/s
600 600
Power demand, kW
Power demand, kW
100
200
1000
1000
300
200
6000
Total pressure rise, Pa
5000 800
4000
3000 600
10
2000
400
1000
0
0 10 20 30 40 50 60 70 80
0
400 Gas flow, m3/s
600
100
Power demand, kW
200 800
300
400 0
100
nmax, r/min
< 100C: 1120
500 200C: 1040
350C: 850
0
J (= 1/4 GD2): 247 kg m2 110
600 Max. fan power = 250 kW nmax = 1120 r/min
Fan charts - Belt-driven fans Page 74
The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.
HCMT
Gas flow, m3/h Gas flow, m3/h
0 1000 2000 3000 3600 0 2000 4000 6000
4800 4800
2 2 3
1 n
ma
3
016 1 n
4 020
x = ma
4000 48 4 4000 x =4 5
3 30
48 0 r/ 0r
00 m i 5 /m
n 400 in
0
3000 3000
40
00
0 0
0 0.2 0.4 0.6 0.8 1.0 0 1 1.75
0 0
2000 Gas flow, m3/s 2000 Gas flow, m3/s
Power demand, kW
Power demand, kW
1 3000 2
300
0
2 4
400
3 0
6
4
8 n 40
n ma 00
ma x =
x = 4
48 48 30
30 00 0r
5 n r/m nmax is not temperature dependent /m
max is not temperature dependent in in
J (= 1/4 GD2): 0.038 kg m2 10 J (= 1/4 GD2): 0.068 kg m2
5.6
0 240
2000 0
2000 220
10 1
0
200
0
180
2000 0
1000 1600
1000
1400
1400 120
1000 0
0 0
0 1.0 2.0 2.9 0 1 2 3 4 4.6
0 0 1000
1400 Gas flow, m3/s 1200 Gas flow, m3/s
1400
2000 1600
5 1800
Power demand, kW
Power demand, kW
2000
10 220
0
300 24
0 00
15
10
26
00
20
n 28
n ma 00
m
ax x =
= 25 30
38 50
40 38 30
r/m 00 r/ 00
18 nmax is not2temperature2dependent in nmax is not temperature dependent
m
31
Fan charts - Belt-driven fans Page 75
The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.
HCMT
Gas flow, m3/h Gas flow, m3/h
0 10 000 20 000 0 10 000 20 000 30 000 40 000
4600 4800
3 4 2 3
4000
1 2 n
ma
x =2 5 040 1 n
4
5
050
ma
42 4000 x =1
0 92
24 r/min 190 0 r/m
00 0 in
220
3000 0
3000
200
0
150
180 0
2000 0
2000 10
160 10
0
1400
1200 100
1000 1000 0
1000
800 700
0 0
0 1 2 3 4 5 6 7 0 5 10 11.5
0 800 0 700
1000 Gas flow, m3/s Gas flow, m3/s
1200 1000
10
1400
Power demand, kW
Power demand, kW
10
160 20
0
180 30
0 150
20 0
200 40
0
30 50
22
00
n 60 n
ma ma
40 x = x =
24 2 19 19
20 400 70 20 0
nmax is not temperature dependent r/ m nmax is not temperature dependent r/m 0
in in
J (= 1/4 GD2): 1.05 kg m2 J (= 1/4 GD2): 3.43 kg m2
50 80
0
2000 110
0
100 10
0
900
800
1000
700
600
0
0 5 10 15 18
0
600 Gas flow, m3/s
800
20 900
Power demand, kW
100
0
40 110
0
120
0
60
13
00
80
14
00
n
100 ma
x =
15 15
00 00
nmax is not temperature dependent r/m
120 J (= 1/4 GD2): 7.73 kg m2
in
Fan charts - Belt-driven fans Page 76
The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.
HCHB
Gas flow, m3/h Gas flow, m3/h
0 1000 2000 0 1000 2000 3000
14 000 1 14 000 1 2
2 3
3 010 n
ma
012
12 000 12 000 x =5
n 7 00
ma r/ m 4
x = 4 550 in
63 0
00
10 000 r/m 10 000
60 in 5 500 5
00 0
8000 55 8000
00 450
0
50
00 400
6000 6000 0
450
0 350
400 0
4000 0 4000
350 300
0 0
300 2500 10
0 10
2000 2500 2000 2000
2000
0 0
0 0.1 0.2 0.3 0.4 0.5 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
Power demand, kW
Power demand, kW
2 3500
4000
2 4000
4500
4
3 4500
5000
4 6
5500 5000
5
8
6000
6 n nm = 5500
max is not temperature dependent ax 6300 nmax is not temperature dependent nm =
r/ min ax 5700 r/
J (= 1/4 GD2): 0.138 kg m2 10 J (= 1/4 GD2): 0.222 kg m2 min
6000 34
40 0
00 32 0
6000 0
300 0
350 280 0
0 4000
26 0
4000 300
0 24 00 10
10 220 00
250 200 0
0 2000 0
2000 200
0
1500
0 0
0 0.5 1 1.5 0 1 2 2.5
0 1500 0
2000 Gas flow, m 3/s
2000 Gas flow, m3/s
2500 2200
2 2400
3000 2600
Power demand, kW
Power demand, kW
2800
4 3000
3500
3200
6
3400
4000 10 3600
8
3800
10 4500
4000
12 4200
14 nmax is not temperature dependent 5000 nmax is not temperature dependent 4400
J (= 1/4 GD2): 0.355 kg m2 20 J (= 1/4 GD2): 0.613 kg m2 nm =
nmax = 5100 r/min ax 4500
r/min
Fan charts - Belt-driven fans Page 77
The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.
HCHB
Gas flow, m3/h Gas flow, m3/h
0 5000 10 000 13000 0 5000 10 000 15 000 20 000
12 000
2 2
nm 3
n
ma
3
025 10 000 1
ax =
33
4 031
1 380 x = 39 4
320 20
10 000 0 00 0 r/m
r /m in
360 in 5
0 8000 300
0 5
340
8000 0 280
320 0
0 260
300 6000 0
0 0
0 1 2 3 3.8 0 1 2 3 4 5
0 0 1000
1400 Gas flow, m3/s Gas flow, m3/s
1600 1400
1800 1600
2000 1800
2200
2000
Power demand, kW
Power demand, kW
2400
2200
2600 10
10 2800 2400
3000 0
260
3200 0
20 280
0
340
00
20 30
0
360
00
30 32
0
nmax is not temperature dependent 380 nmax is not temperature dependent n
2 2 nmax = 3900 r/min J (= 1/4 GD2): 1.7 kg m2 max = 3320 r/min
28 J (= 1/4 GD ): 1 kg m
36
0
200 160
0 0
4000 180 4000
0 140
0
1600
1200
1400 10 10
2000 1200 2000 1000
1000 800
0 0
0 2 4 6 8 0 2 4 6 8 10 12
0 1000 0
Gas flow, m3/s 1000 Gas flow, m3/s
1400 1200
1600
10 1800 1400
Power demand, kW
Power demand, kW
20
2000 1600
0
20 220 180
0
0
240 40
0
30 200
00
26
60 00
22
00
40 28
The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.
HCHB
Gas flow, m3/h Gas flow, m3/h
0 20 000 40 000 60 000 0 50 000 80 000
2n 2 n
1 ma 3 1 ma 3
10 000 x =1
90 063 10 000 x =
16 071
0r 90 4
180 4 16 r/m
0 /m 00
in in
170 150 5
8000 0 8000 0
5
160 140
0 0
150 130
0
6000 6000 0
140
0 120
130 0
0 110
120 0
4000 0 4000 100
110 0
0 900
1000
900 800 10
10
2000 800 2000 700
700 600
600 500
0 0
0 10 20 0 10 20
0 0 500
800 Gas flow, m3/s Gas flow, m3/s
900 800
1000
900
20 1100 1000
Power demand, kW
Power demand, kW
1200 1100
40 1300 50 0
0 120
140 0
0 130
60 150
00
00 14
16
80 100
00
00 15
17
100 00
00
18 16
0
100 900
0
4000 900 4000 800
800 700
700 10 600 10
2000 600 2000
500
500 400
0 0
0 10 20 30 0 10 20 30 40
0 500 0 400
Gas flow, m3/s Gas flow, m3/s
600
700
800 700
800
Power demand, kW
Power demand, kW
900
1000 900
0
110 100 100
0
0
100 120 0
110
0
130
00
12
00 200
14
00
nmax is not temperature 13
nmax is not temperature dependent
in in
200 dependent r/ m J (= 1/4 GD2): 147 kg m2 r/m
J (= 1/4 GD2): 75 kg m2 nm = 1500 nm = 1340
ax
ax Max. fan power = 250 kW
280
Fan charts - Belt-driven fans Page 79
The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.
HCHB
Gas flow, m3/h
0 50 000 100 000 150 000 190 000
11 000
2 n
ma 3
10 000 1 x=
12
00
100
r/m 4
110 in
0
8000 5
100
0
6000 900
Total pressure rise, Pa
800
4000 700
600
10
2000 500
400
0
0 10 20 30 40 50
0 400
Gas flow, m3/s
600
700
Power demand, kW
800
100
900
00
10
200
00
11
HCHP
Gas flow, m3/h Gas flow, m3/h
0 5000 10 000 14 000 0 10 000 20 000
10 000 10 000
2 2
n
ma
3 nm 3
1
1 x =3
48 4
025 ax = 3
10 0
4 031
34 0 r/ r/m 5
00 mi 300 in
8000 n 5 8000 0
32 280
00
0
30
00 260
6000 6000 0
280
0 240
0
Total pressure rise, Pa
Total pressure rise, Pa
260
0 220
240 0
4000 0 4000 2000
220 10
0 10 1800
200
0
1800 1600
2000 1600 2000 1400
140 1200
1200 0 1000
0 0
0 1 2 3 4 0 1 2 3 4 5 6
0 1200 0 1000
Gas flow, m3/s 1200 Gas flow, m3/s
1600
2000 1800
Power demand, kW
Power demand, kW
2200 10
2000
2400
10 2200
2600
20
2400
2800
2600
3000
30
20
3200 2800
40 nmax, r/min
< 200C: 3100
n 3400 3000
max = 350C: 2950
nmax is not temperature dependent 348
30 J (= 1/4 GD2): 0.92 kg m2 0 r/m J (= 1/4 GD2): 1.6 kg m2 nmax = 3100 r/min
in 50
Fan charts - Belt-driven fans Page 80
The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.
200 160
0 0
0 0
0 2 4 6 8 10 0 5 10 15
0 0 600
1000 Gas flow, m3/s Gas flow, m3/s
1000
1400 1200
10
1600
Power demand, kW
Power demand, kW
1400
20 1800
2000 1600
30 50
2200
40 1800
2400
50
2000
60 2600
nmax, r/min 100 nmax is not temperature
< 200C: 2770 dependent
70 350C: 2540 J (= 1/4 GD2): 8.1 kg m2
J (= 1/4 GD2): 2.7 kg m2 120 Max. fan power = 100 kW nmax = 2200 r/min
nmax = 2770 r/min
80
120 110
0 0
4000 110 4000 100
0 10 0
1000 10
900
900 800
800
2000 2000 700
700 600
600
500
0 0
0 10 20 0 10 20 30
0 600 0
Gas flow, m3/s 600 Gas flow, m3/s
800
800
1000 900
Power demand, kW
Power demand, kW
1100 1000
50
1200 1100
1300 100
1200
1400
100
1300
1500
1400
1600
150
nmax, r/min 200 nmax, r/min
< 200C: 1745 < 200C: 1555 1500
350C: 1525 1700 350C: 1450
J (= 1/4 GD2): 22.8 kg m2 nmax = 1745 r/min J (= 1/4 GD2): 41 kg m2
190 nmax = 1555 r/min
Fan charts - Belt-driven fans Page 81
The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.
HCHP
Gas flow, m3/h Gas flow, m3/h
0 40 000 80 000 120 000 0 40 000 80 000 120 000 160 000
2 3 2 3
10 000 nm 10 000 nm 4
1 ax =
138
4 080 ax =
12 090
5r
/m 5 1 12 35 r/m 5
in 00 in
8000 130 8000
0
110
120 0
0
100
6000 110 6000 0
0
Total pressure rise, Pa
0 0
0 10 20 30 40 0 10 20 30 40 50
0 400 0 400
600 Gas flow, m3/s Gas flow, m 3/s
600
700
800 700
Power demand, kW
Power demand, kW
900 800
100
100 1000 900
1100
200 1000
1200
200 1100
900
6000
Total pressure rise, Pa
800
4000 700
10
600
2000 500
400
0
0 10 20 30 40 50 60
100
700
800
200
900
300
1000
nmax, r/min
< 200C: 1100
400
350C: 940
J (= 1/4 GD2): 220 kg m2
nmax = 1100 r/min
Max. fan power = 250 kW
Fan charts - Belt-driven fans Page 82
The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.
HCHT
Gas flow, m3/h Gas flow, m3/h
0 500 1000 1500 0 1000 2000 3000
12 000
1 1
10 000 2 010 2
3
012
n 3 10 000
n
ma ma 4
x =5 x =5
80 4 30
8000 0r 0r
/m /m 5
in 8000 50 in
55 00
00 5
6
6000 50 450
Total pressure rise, Pa
0 0
0 0.1 0.2 0.3 0.w4 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
0 0
2000 Gas flow, m 3/s 2000 Gas flow, m3/s
3000
3000
3500
Power demand, kW
Power demand, kW
2 3500
4000
5
450 400
0
0
4
500 45
0 00
10
6
55 n 55
00 ma 00
n x =
ma 53
x = 00
8 58 r/m
00 15 n in
nmax is not temperature dependent r /m max is not temperature dependent
J (= 1/4 GD2): 0.1 kg m2 in J (= 1/4 GD2): 0.17 kg m2
0
360 4000 260
340 0 0
320 0 2400
4000 300 0 3000 2200
2800 0 2000 10
10 1800
2400 2000
1600
2000 2000 1400
1000
0 0
0 0.5 1.0 1.5 0 1 2
0 0
2000 Gas flow, m3/s 1400 Gas flow, m3/s
2000
Power demand, kW
Power demand, kW
3000
240
3200 0
260
10 10 0
360 280
0 0
380
0
400 30
0 00
42
0 0 32
20 00
20 44 n
00
m
n ax 34
ma =
x = 46
00 36 00
47 00
30 r/m
nmax is not temperature dependent r/m nmax is not temperature dependent in
in
2
28 J (= 1/4 GD ): 0.28 kg m
2 J (= 1/4 GD2): 0.45 kg m2
30
Fan charts - Belt-driven fans Page 83
The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.
HCHT
Gas flow, m3/h Gas flow, m3/h
0 2000 4000 6000 8000 10 000 12 000 0 10 000 20 000
8000
2 3
7000 nm 3 4 n 4
1
ax = 30
25
r/m
025 7000
1
2
max =
280 5 031
300 in 5 0r
0 /m
6000 260 in
280 6 0 6
0 6000
0 0
0 1 2 3 0 1 2 3 4 5
0 1000 3/s
0 1000
Gas flow, m Gas flow, m3/s
1400
1600
10 1600
Power demand, kW
Power demand, kW
1800
1800
2000
10
20 200
0
2200
220
2400 0
30
20 240
2600 0
40
260
280 n 0
n 0 ma
ma 50 x =
30 x = 28
30 0 0r
nmax is not temperature dependent 25 30 nmax is not temperature dependent /m
r /m 00 in
J (= 1/4 GD2): 0.87 kg m2 i 60 J (= 1/4 GD2): 1.6 kg m2
36
nm 4 nm
7000
1
2
ax =
240
0r
040 7000 1
2
ax = 1
900
4
050
/m 3 r/m 5
3 in 5 180 in
6000 6000 0
220 6
0 6 170
0
5000 200 5000 160
0 0
150
4000 180 4000 0
0
Total pressure rise, Pa
140
Total pressure rise, Pa
9 0
1600 130
3000 0
3000 1200
10
1400 1100 10
2000 1200 2000 1000
1000 800
1000 800 1000 600
0 0
0 1 2 3 4 5 6 7 8 9 0 5 10
0 0 600
1000 Gas flow, m3/s 800 Gas flow, m3/s
1000
1400
Power demand, kW
Power demand, kW
1200
20
1600 130
0
140
180 50 0
0
150
40 0
200 160
0 0
17
00
60
n 22 n
m 00 100 ma
ax
= x = 18
24 19 00
00 00
r/m nmax is not temperature dependent
nmax is not temperature dependent J (= 1/4 GD2): 7.3 kg m2 r/m
in in
80 J (= 1/4 GD2): 2.9 kg m2 130 Max. fan power = 95 kW
Belt-driven fans with impeller diameter > 1000 mm Page 84
Ordering key - Belt-driven fans with impeller diameter > 1000 mm Page 85
HCGB
HCLP
HCMx
HCH x-aaa-bb-cc-dd-ee-fff
Impeller
B = Backward-curved blades
P = Flat, backward-inclined blades.
Size (aaa)
61 0
o
62 45
o
63 90
o
65 180o 67 270
o
68 315
o
Left *
(LG) Z Z W W Z Z
HCGB
HCLP
HCMx
HCH x-aaa-bb-cc-dd-ee-fff
002 = Standard material, GP40-01 int. and ext. Not fully welded Max. temperature 150oC. 2)
032 = Standard material, GA80TD80-RAL5007 int. and ext. Not fully welded Max. temperature 120oC.
072 = Standard material, GA80TD80-RAL5007 int. and ext. Fully welded Max. temperature 120oC.
112 = Standard material, GA80TB80-RAL5007 int. and ext. Fully welded Max. temperature 120oC.
300 = Parts in gas contact in SS 2333. Other parts in Not fully welded Max. temperature 120oC.
standard material with GA80-RAL 5007 finish.
NB! Shaft in standard material SS 2172.
315 = Parts in gas contact in SS 2333. Other parts in Not fully welded Max. temperature 120oC.
standard material with GA80TD80-RAL 5007 finish.
NB! Shaft in standard material SS 2172.
400 = Parts in gas contact in SS 2343. Other parts in Not fully welded Max. temperature 120oC.
standard material with GA80-RAL 5007 finish.
NB! Shaft in standard material SS 2172.
415 = Parts in gas contact in SS 2343. Other parts in Not fully welded Max. temperature 120oC.
standard material with GA80TD80-RAL 5007 finish.
NB! Shaft in standard material SS 2172.
1)
Removable contact guards around rotating parts are epoxy painted in a yellow warning colour, (80 ).
2)
GP40-01 primer can be used where temperatures exceed 120oC. This primer tolerates temperatures up to 150oC and vaporises at higher tempera
tures without emitting any toxic substances.
3)
Fully welded stand and, whenever applicable, fully welded steel base frame. NB! Parts in gas contact not fully welded.
Page 87
Ordering key - Accessories
Belt drive selection - Use either the HC selection program or contact Flkt Woods AB.
Description - Accessories, inlet and outlet Page 89
7 1
8, 9
10
2, 3
1
4, 5
6
Duc
t
2, 3
4, 5
6
Inlet
1 HCEZ-21 Inlet taper piece with protective screen and flange for connection to inlet flange.
(Pressure loss across the accessory, 0.35 x dyn. press. pd).
2 HXEG Inlet vane control assembly, see pages 106-111. 1)
3 DMEG Regulating damper, see page 105. 1)
4 HCEZ-45, 46, 47 Fabric duct, inlet with connecting flanges. 2)
5 HCEZ-65, 66 Flue gas duct, inlet with connecting flanges. 2)
6 HCEZ-25 Counterflange, inlet, (not fitted).
Outlet
7 HCEZ-35 Counterflange, outlet, (not fitted).
8 HCEZ-50, 51, 52 Fibre duct, outlet, with connecting flanges. 2)
9 HCEZ-70, 71 Flue gas duct, outlet with connecting flanges. 2)
10 HCEZ-30 Protective screen, outlet.
1) NB! Inlet vane assemblies/regulating dampers must not be connected directly to the fan without checking that
the anti-vibration mountings can cope with the increased component load on the fan.
2) For size and temperature limits, please refer to the appropriate ordering keys.
Sound data Page 90
Symbols Formulae:
Lwtot = total sound power level for the relevant sound Lwtot = Lwtoto + K1 + K2 + K3
path and appropriate throttling curve...................... dB
Lwtot = total sound power level to inlet or outlet duct when For division into octave bands, use the formula:
o
the fan is operating on the throttling curve giving Lw = Lwtot + Kok
the lowest sound power level.................................. dB
Lw = Lwtot divided into octave bands .............dB (ref. 10-12 W) Sound paths: a = to inlet or outlet duct.
b = to surroundings (free-inlet fan).
K1 = corr. for diff. throttling curves and sound paths....... dB
c = to surroundings (duct-connected fan).
K2, K3 = correction for different sound paths........................ dB
Kok = approximate deviation from Lwtot NB! The stated values refer to sound power levels. Some fan manufac-
for the particular octave band................................. dB turers still quote sound pressure levels even though these vary with the
acoustic characteristics of the surroundings and distance from the fan.
L = throttling curve = 10 pd/Dpt Sound pressure levels, sometimes weighted as dB(A) or dB(C) values,
Dp
t = total pressure rise................................................... Pa are considerably lower than the corresponding sound power level Lwt.
110 l p
o t a a 2300-4700 0 -4 -9 -10 -6 -14 -18 -23 -23
T 0 800
c
00
600 4
c
100
c
1.5 +5
c a Sound paths: a = to inlet or outlet duct.
1.0 b, 0
a, b b = to surroundings (free-inlet fan).
0.5 -5
0 -10 c c = to surroundings (duct-connected fan).
2 3 4 5 0 1000 2000 3000
L Dpt, Pa
800
Lwtoto, dB
100
c
K2, dB
ess 000
l pr
c
110
2300-4700 0 -9 -8 -7 -5 -9 -13 -16 -21
800
c
400
c
100 600
c
K2, dB
0
b,c Sound paths: a = to inlet or outlet duct.
1 a, -5 b
b = to surroundings (free-inlet fan).
c
-10 c = to surroundings (duct-connected fan).
0 -15
2 3 4 5 4000 8000 12 000
L Dpt, Pa
Dimensions and weights - Fan Page 92
L1
D3*
A
H1
D2 j6
K2 K1
S1 N2
Designations M2
N1
for rotation and
discharge dd = M1
11, 61, 12, 62, V V Y1 x V3 V4
13, 63, 17, 67, 1 2
18, 68, 21, 71,
22, 72, 23, 73
U1 P2
U2 P1
T4
6 holes 25 2 x T3 T1 T2 Y2 holes 25 U U
dd = 11 (0o) = Right-hand model dd = 12 (45o)
o o
dd = 61 (0 ) = Left-hand model dd = 62 (45 )
Designations
for rotation and V5
discharge dd = V V
15, 65, 25, 75 1 2
Y1 x V3 S3
N3
N1
U1 V6 E
M1
T4
U2
P3 P4
discharge direction.
U
Please contact Flkt Woods AB.
dd = 13 (90o) dd = 15 (180o) **
o o
dd = 63 (90 ) dd = 65 (180 ) **
S4 S5 S6
N3 N4 N1
M3 M1
E
P6 P1
P5
U
U U
o o o
dd = 17 (270 ) dd = 18 (315 ) dd = 21 (0 )
dd = 67 (270o) dd = 68 (315o) dd = 71 (0o)
S7
S8
N2
N3
M2
N1
E
M1
P2
P3 P4
U U
dd = 22 (45o) dd = 23 (90o) dd = 25 (180o) **
o o o
dd = 72 (45 ) dd = 73 (90 ) dd = 75 (180 ) **
Dimensions - Fan plus steel base frame Page 93
Motor size
Type of fan - size
160-225 250-355
HCG HCL HCM HCH M1 M2 M3 N1 N2 N3 N4 P1 P2 P3 P4 P5 P6 U U
112 090 071 -- 1065 995 1265 1860 1760 1700 2100 1670 2200 2000 1850 1870 1850 180 200
125 100 080 063 1190 1160 1430 2070 2010 1900 2360 1875 2470 2240 2080 2090 2060 180 200
140 112 090 071 1325 1290 1600 2320 2290 2120 2660 2100 2760 2330 2320 2320 2290 180 200
160 125 100 080 1490 1400 1790 2650 2570 2370 2960 2385 3140 2840 2650 2640 2600 200 240
-- 140 112 090 1665 1620 1990 2970 2880 2650 3310 2655 3490 3160 2950 2950 3000 200 240
-- 160 125 100 1860 1810 2230 3320 3210 2960 3700 2960 3900 3530 3340 3290 3240 200 240
H1 V1 V2
Fan type - size Form 1) dd = Form 1) dd = Form 1) dd = V3 V4 V5 V6 Y1 Y2
11-15, 11-15, 11-15,
HCG HCL HCM HCH D2 F1 F2 21-25 17-18 H2 L2 T3 T4 U1 U2 21-25 17-18 21-25 17-18
112 090 071 -- 70 74.5 20 930 1085 1010 170 295 720 125 80 1023 1141 891 1009 410 1010 505 505 2 3
125 100 080 063 80 85 22 1050 1205 1133 175 335 800 125 80 1113 1223 981 1091 440 1100 550 550 2 3
140 112 090 071 90 95 25 1170 1330 1271 190 384 900 125 80 1253 1375 1121 1241 385 1235 618 618 3 4
160 125 100 080 100 106 28 1350 1520 1426 210 387 970 175 100 1382 1507 1188 1313 425 1365 683 1448 3 4
-- 140 112 090 100 106 28 1500 1700 1610 210 387 970 175 100 1532 1687 1338 1489 475 1515 758 1623 3 4
-- 160 125 100 100 106 28 1670 1890 1796 210 387 970 175 100 1742 1923 1548 1725 540 1725 863 1818 3 4
1)
Form means the designations for rotation and discharge
HCGB
K1 T2
Fan Imp. D3 Form 1) dd = Form 1) dd = Weight,
A B C D1 E K2 L1 T1
size dia. min. 11-13, 17, 18, 21-23 15, 25 11-13, 17, 18, 21-23 15, 25 kg 2)
112 1120 1120 900 573 1125 315 736 533 583 1263 2020 608 493 543 610
125 1250 1250 1000 623 1255 355 821 583 633 1415 2230 680 543 593 770
140 1400 1400 1120 683 1405 425 926 643 703 1578 2460 744 603 663 1040
160 1600 1600 1250 753 1605 500 1033 728 788 1758 2740 886 678 738 1370
1)
Form means the designations for rotation and discharge 2)
Weights are exclusive motor, belt drive and steel base frame.
HCLP
K1 T2
Fan Imp. D3 Form 1) dd = Form 1) dd = Weight,
A B C D1 E K2 L1 T1
size dia. min. 11-13, 17, 18, 21-23 15, 25 11-13, 17, 18, 21-23 15, 25 kg 1)
090 1120 900 710 478 905 315 736 433 483 1168 1830 513 398 448 610
100 1250 1000 800 523 1005 335 821 478 528 1315 2030 580 443 493 770
112 1400 1120 900 573 1125 400 926 528 588 1468 2240 634 493 553 1040
125 1600 1250 1000 623 1255 450 1033 603 663 1633 2485 761 553 613 1370
140 1800 1400 1120 683 1405 530 1153 663 723 1693 2605 821 613 673 1730
160 2000 1600 1250 753 1605 630 1287 728 788 1758 2740 886 678 738 2050
1)
Form means the designations for rotation and discharge 2)
Weights are exclusive motor, belt drive and steel base frame.
HCM(B,P)
D3 K1 T2
Fan Imp. Weight,
A B C D1 min. E Form 1) dd = K2 L1 T1 Form 1) dd =
size dia. kg 2)
HCMB HCMP 11-13,17,18,21-23 15,25 11-13,17,18, 21-23 15,25
071 1120 710 560 403 715 250 280 736 358 408 1093 1680 438 323 378 605
080 1250 800 630 438 805 315 315 821 393 443 1230 1850 495 358 408 745
090 1400 900 710 478 905 335 355 916 433 493 1373 2050 539 398 458 1015
100 1600 1000 800 523 1005 400 450 1023 503 563 1533 2285 661 453 513 1330
112 1800 1120 900 573 1125 450 450 1153 553 613 1583 2385 711 503 563 1685
125 2000 1250 1000 623 1255 500 500 1287 603 663 1633 2505 761 553 613 2030
1)
Form means the designations for rotation and discharge 2)
Weights are exclusive motor, belt drive and steel base frame.
HCH(B,P)
D3 K1 T2
Fan Imp. Weight,
A B C D1 min. E Form 1) dd = K2 L1 T1 Form 1) dd =
size dia. kg 2)
HCMB HCMP 11-13,17,18,21-23 15,25 11-13,17,18, 21-23 15,25
063 1250 630 500 373 635 250 335 821 328 378 1165 1745 430 293 343 710
071 1400 710 560 403 715 280 400 916 358 418 1298 1905 463 323 383 950
080 1600 800 630 438 805 335 400 1023 418 478 1448 2125 576 368 428 1260
090 1800 900 710 478 905 400 450 1143 458 518 1488 2205 616 408 468 1550
100 2000 1000 800 523 1005 500 540 1277 503 563 1533 2295 661 453 513 1920
1)
Form means the designations for rotation and discharge 2)
Weights are exclusive motor, belt drive and steel base frame.
Dimensions and weights - Steel base frame Page 95
11, 12, 63 W 13, 61, 62 Z 160-225 1836 1915 1010 800 1303 228
11, 12, 63 W 13, 61, 62 Z 250-355L 1846 2425 1010 990 1308 294
112
17, 18 W 67, 68 Z 160-225 1836 2025 1130 800 1303 315
17, 18 W 67, 68 Z 250-355L 1846 2537 1109 990 1308 375
11, 12, 63 W 13, 61, 62 Z 160-225 2038 2000 1100 880 1455 246
11, 12, 63 W 13, 61, 62 Z 250-355L 2048 2535 1100 990 1460 313
125
17, 18 W 67, 68 Z 160-225 2038 2110 1210 880 1455 340
17, 18 W 67, 68 Z 250-355L 2048 2590 1200 990 1460 400
11, 12, 63 W 13, 61, 62 Z 160-225 2261 2150 1235 980 1618 277
11, 12, 63 W 13, 61, 62 Z 250-355L 2271 2660 1235 990 1623 337
140
17, 18 W 67, 68 Z 160-225 2261 2260 1360 980 1618 400
17, 18 W 67, 68 Z 250-355L 2271 2800 1341 990 1623 435
11, 12, 63 W 13, 61, 62 Z 160-225 2491 2250 1365 1000 1773 355
11, 12, 63 W 13, 61, 62 Z 250-355L 2511 2720 1365 1020 1793 492
160
17, 18 W 67, 68 Z 160-225 -- -- -- -- -- --
17, 18 W 67, 68 Z 250-355L 2511 2845 1425 1020 1793 575
1)
Form means the designations for rotation and discharge
CL Inlet Fan
C
W = Motor on the right of the fan as viewed from the drive side.
Z = Motor on the left of the fan as viewed from the drive side.
CL Outlet Fan
W = Motor on the right of the fan as viewed from the drive side.
Z = Motor on the left of the fan as viewed from the drive side.
B
1)
Form means the designations for rotation and discharge
11, 12, 63 W 13, 61, 62 Z 160-225 1646 1915 1010 800 1208 218
11, 12, 63 W 13, 61, 62 Z 250-355L 1656 2425 1010 990 1213 284
090
17, 18 W 67, 68 Z 160-225 1646 2025 1130 800 1208 295
17, 18 W 67, 68 Z 250-355L 1656 2537 1109 990 1213 360
11, 12, 63 W 13, 61, 62 Z 160-225 1838 2000 1100 880 1355 239
11, 12, 63 W 13, 61, 62 Z 250-355L 1848 2535 1100 990 1360 303
100
17, 18 W 67, 68 Z 160-225 1838 2110 1210 880 1355 325
17, 18 W 67, 68 Z 250-355L 1848 2590 1200 990 1360 380
11, 12, 63 W 13, 61, 62 Z 160-225 2041 2150 1235 980 1508 267
11, 12, 63 W 13, 61, 62 Z 250-355L 2051 2660 1235 990 1513 325
112
17, 18 W 67, 68 Z 160-225 2041 2260 1360 980 1508 355
17, 18 W 67, 68 Z 250-355L 2051 2800 1341 990 1513 420
11, 12, 63 W 13, 61, 62 Z 160-225 2241 2250 1365 1000 1648 343
11, 12, 63 W 13, 61, 62 Z 250-355L 2261 2720 1365 1020 1658 472
125
17, 18 W 67, 68 Z 160-225 -- -- -- -- -- --
17, 18 W 67, 68 Z 250-355L 2261 2845 1425 1020 1658 550
11, 12, 63 W 13, 61, 62 Z 160-225 2361 2400 1515 1000 1708 354
11, 12, 63 W 13, 61, 62 Z 250-355L 2381 2970 1515 1020 1718 505
140
17, 18 W 67, 68 Z 160-225 -- -- -- -- -- --
17, 18 W 67, 68 Z 250-355L 2381 3120 1639 1020 1718 595
11, 12, 63 W 13, 61, 62 Z 160-225 2491 2610 1725 1000 1773 380
11, 12, 63 W 13, 61, 62 Z 250-355L 2511 3160 1725 1020 1783 539
160
17, 18 W 67, 68 Z 160-225 -- -- -- -- -- --
17, 18 W 67, 68 Z 250-355L 2511 3250 1837 1020 1783 630
Dimensions and weights - Steel base frame Page 96
11, 12, 63 W 13, 61, 62 Z 160-225 1496 1915 1010 800 1133 213
11, 12, 63 W 13, 61, 62 Z 250-355L 1506 2425 1010 990 1138 275
071
17, 18 W 67, 68 Z 160-225 1496 2025 1130 800 1133 290
17, 18 W 67, 68 Z 250-355L 1506 2537 1109 990 1138 350
11, 12, 63 W 13, 61, 62 Z 160-225 1668 2000 1100 880 1270 227
11, 12, 63 W 13, 61, 62 Z 250-355L 1678 2535 1100 990 1275 294
080
17, 18 W 67, 68 Z 160-225 1668 2110 1210 880 1270 310
17, 18 W 67, 68 Z 250-355L 1678 2590 1200 990 1275 370
11, 12, 63 W 13, 61, 62 Z 160-225 1851 2150 1235 980 1413 257
11, 12, 63 W 13, 61, 62 Z 250-355L 1861 2660 1235 990 1418 316
090
17, 18 W 67, 68 Z 160-225 1851 2260 1360 980 1413 340
17, 18 W 67, 68 Z 250-355L 1861 2800 1341 990 1418 405
11, 12, 63 W 13, 61, 62 Z 160-225 2031 2250 1365 1000 1538 332
11, 12, 63 W 13, 61, 62 Z 250-355L 2051 2720 1365 1020 1548 459
100
17, 18 W 67, 68 Z 160-225 -- -- -- -- -- --
17, 18 W 67, 68 Z 250-355L 2061 2845 1425 1020 1558 530
11, 12, 63 W 13, 61, 62 Z 160-225 2141 2400 1515 1000 1598 342
11, 12, 63 W 13, 61, 62 Z 250-355L 2161 2970 1515 1020 1608 489
112
17, 18 W 67, 68 Z 160-225 -- -- -- -- -- --
17, 18 W 67, 68 Z 250-355L 2161 3120 1639 1020 1608 575
11, 12, 63 W 13, 61, 62 Z 160-225 2241 2610 1725 1000 1653 368
11, 12, 63 W 13, 61, 62 Z 250-355L 2261 3160 1725 1020 1663 519
125
17, 18 W 67, 68 Z 160-225 -- -- -- -- -- --
17, 18 W 67, 68 Z 250-355L 2261 3250 1837 1020 1663 610
1)
Form means the designations for rotation and discharge
W = Motor on the right of the fan as viewed from the drive side. Dimensions and weights apply equally to
Z = Motor on the left of the fan as viewed from the drive side. fans with reversed motor location.
11, 12, 63 W 13, 61, 62 Z 160-225 1538 2000 1100 880 1205 224
11, 12, 63 W 13, 61, 62 Z 250-355L 1548 2535 1100 990 1210 288
063
17, 18 W 67, 68 Z 160-225 1538 2110 1210 880 1205 300
17, 18 W 67, 68 Z 250-355L 1548 2590 1200 990 1210 360
11, 12, 63 W 13, 61, 62 Z 160-225 1701 2150 1235 980 1338 250
11, 12, 63 W 13, 61, 62 Z 250-355L 1711 2660 1235 990 1343 307
071
17, 18 W 67, 68 Z 160-225 1701 2260 1360 980 1338 330
17, 18 W 67, 68 Z 250-355L 1711 2800 1341 990 1343 390
11, 12, 63 W 13, 61, 62 Z 160-225 1871 2250 1365 1000 1463 321
11, 12, 63 W 13, 61, 62 Z 250-355L 1831 2720 1365 1020 1413 445
080
17, 18 W 67, 68 Z 160-225 -- -- -- -- -- --
17, 18 W 67, 68 Z 250-355L 1891 2845 1425 1020 1413 515
11, 12, 63 W 13, 61, 62 Z 160-225 1951 2400 1515 1000 1423 330
11, 12, 63 W 13, 61, 62 Z 250-355L 1971 2970 1515 1020 1513 476
090
17, 18 W 67, 68 Z 160-225 -- -- -- -- -- --
17, 18 W 67, 68 Z 250-355L 1971 3120 1639 1020 1513 555
11, 12, 63 W 13, 61, 62 Z 160-225 2041 2610 1725 1000 1568 355
11, 12, 63 W 13, 61, 62 Z 250-355L 2061 3160 1725 1020 1555 505
100
17, 18 W 67, 68 Z 160-225 -- -- -- -- -- --
17, 18 W 67, 68 Z 250-355L 2061 3250 1837 1020 1558 590
1)
Form means the designations for rotation and discharge
W = Motor on the right of the fan as viewed from the drive side.
Z = Motor on the left of the fan as viewed from the drive side.
Location of fan and motor Page 97
c-c distance
Designations for rotation and discharge = dd
Fan type - Size Motor size 11, 61, 12, 62, 13, 63, 21, 71, 22, 72, 23, 73 17, 67, 18, 68
HCG HCL HCM HCH IEC Min. Max. Min. Max.
112 090 071 -- 160M-180L 1235 1355 1365 1480
200L-225M 1180 1355 1310 1475
250M-315L 1430 1690 1545 1790
125 100 080 063 160M-180L 1340 1455 1500 1585
200L-225M 1280 1450 1415 1575
250M-315L 1540 1795 1615 1850
355S-355M 1485 1810 1550 1860
140 112 090 071 160M-180L 1475 1585 1615 1720
200L-225M 1420 1580 1560 1710
250M-315L 1640 1890 1790 2025
355S-355M 1585 1905 1725 2040
160 125 100 080 160M-180L 1610 1715 -- --
200L-225M 1555 1710 -- --
250M-315L 1740 1985 1890 2120
355S-355M 1685 1995 1820 2130
140 112 090 160M-180L 1765 1870 -- --
200L-225M 1710 1860 -- --
250M-315L 1970 2210 2150 2375
355S-355M 1915 2220 2010 2300
160 125 100 160M-180L 1960 2060 -- --
200L-225M 1910 2050 -- --
250M-315L 2140 2370 2275 2480
355S-355M 2080 2380 2215 2500
c/c
Motor location:
W = as per diagram.
Z = reversed motor location.
Dimensions and weights - Slide rails Page 98
XYLS-02, 03, 04
XF
XA min. max.
displacement
XA max.
XC
56 56 56
5 5
5
50 711 18
50 437 14 50 536 14
92 80
92 80 92 80
25
25 25 761
487 586
811
537 636
XYLS-05, 06
XF
XA min. max.
displacement
XA max.
XC
XYLS-05 XYLS-06
Motor bolts, M 20 Motor bolts, M 24
75 80
5 6
18 x 40 24 x 40
92 80 112 160 104 86 135 190
Dimensions
For Max. Weight,
XYLS- motor displacement XA min. XA max. XC XF per pair,
size mm mm mm mm mm kg
100 198 173 371 74 55 8
02 112 171 185 356 74 55 8
132 144 199 343 74 55 8
160 193 230 423 74 65 10
03
180 167 244 411 74 65 10
200 252 302 554 84 95 12
04
225 214 321 535 84 95 12
250 374 178 552 70 20 32
05 280 340 196 536 70 20 32
315 277 233 510 70 20 32
315 476 235 711 91 30 48
06
355 393 276 669 91 30 48
Dimensions and weights - Assessories Page 99
CL
Size A B Weight, kg
4 293 400 7.0 Dimensions A and B refer to the hatch
5 413 560 16.0 opening in the fan casing.
8 293 400 13.7
9 413 560 29.5
Fan size
Fan size
shaft HCG HCL HCM HCH code bb
112 090 071 03
125-140 100-112 080-090 063-071 04
160 125-160 100-125 080-100 05
Dimensions and weights - Assessories Page 100
E1
A n1 x E A1 x B1
Sheet steel
insert
E1
F1 n2 x F F1 t + 2,5 t t
t
H H
Outlet - Protective screen HCEZ-30, counterflange HCEZ-35, fabric duct HCEZ-50/51/52 and flue gas duct HCEZ-70/71
Weight, kg
Size + 10
A A1 B B1 E E1 F F1 G H - 20 g n n1 n2 t HCEZ- HCEZ- HCEZ- HCEZ-
bbb 30 35 50/51/52 70/71
063 630 600 500 470 125 97 125 94.5 12 130 32 22 4 3 8 10.5 9.2 18.8 22.4
071 710 680 560 530 125 74.5 125 62 12 130 32 26 5 4 8 11.9 10.3 21.1 25.3
080 800 770 630 600 125 57 125 97 12 130 32 28 6 4 8 13.4 11.5 23.5 27.9
090 900 870 710 680 125 107 125 74.5 12 130 32 30 6 5 8 15.2 12.8 26.1 31.3
100 1000 970 800 770 125 94.5 125 57 14 130 32 34 7 6 8 17.1 14.2 29.0 34.9
112 1120 1080 900 860 125 97 125 112 14 160 37 36 8 6 8 20.0 16.5 33.9 40.7
125 1250 1210 1000 960 125 99.5 125 99.5 14 160 37 40 9 7 8 22.5 18.2 37.5 45.1
140 1400 1360 1120 1080 125 174.5 125 97 14 160 37 42 9 8 8 25.6 20.3 41.9 50.5
160 1600 1560 1250 1210 125 87 125 99.5 14 160 37 50 12 9 8 35.1 28.5 47.1 56.7
t1 t1 t2 t2
h h h h
E
D1 D3 D1 D1 D1 D2
ins. ins.
Sheet steel
insert
H1 H1
nxG
H2
Inlet - Inlet taper piece HCEZ-21, counterflange HCEZ-35, fabric duct HCEZ-45/46/47 and flue gas duct HCEZ-65/66
Weight, kg
Size + 10
D1 D2 D3 E G H1 H2 h n t1 t2 HCEZ- HCEZ- HCEZ- HCEZ-
bbb - 20 21 25 45/46/47 65/66
063 635 595 880 698 14 130 218 60 16 8 6 11.8 5.9 14.5 15.2
071 715 675 975 775 14 130 218 60 16 8 6 14.0 6.6 16.4 ---
080 805 765 1105 869 14 130 243 60 24 8 6 18.2 7.3 18.2 19.0
090 905 865 1225 958 14 130 243 60 24 8 6 21.0 11.2 26.4 --
100 1005 965 1350 1067 14 130 243 60 24 8 6 24.3 12.4 28.4 30.8
112 1125 1085 1510 1200 18 160 293 60 32 8 6 45.0 16.2 37.7 44.1
125 1255 1215 1700 1337 18 160 293 60 32 8 6 57.0 17.9 41.9 49.5
140 1405 1365 1880 1475 18 160 293 60 32 8 6 67.0 20.0 47.2 55.8
160 1605 1565 2100 1675 18 160 293 60 40 12 10 97.5 30.5 69.0 79.5
Electric motors Page 101
This catalogue section deals with 50 Hz., totally enclosed, foot-mounted, three-phase squirrel cage motors. The two-speed
motors are adapted for driving fans. Size 200 motors and upwards are provided, as standard, with thermistor type tempera-
ture monitors. Quotations for temperature monitors on other sizes supplied on request.
APAL Single-speed motors.
ARAL Two-speed motors with a speed ratio of 1:2 and one stator winding ("Dahlander-connected").
ATAL Two-sped motors with a speed ratio of 1:1.5 and separate stator windings.
For housing and insulation classes, please refer to page 102.
J x nf2 x -3
10
Star-delta starting t= Pf = Fan power demand at rated speed kW
TMAX T
46 P 1 x + 1x S - Pf (incl. where belt-driven, belt-drive losses)
3 TN 4 TN
Permissible starting times PY/D = Minimum motor rating at which star-delta starting is possible kW
With regard to heat build-up, starting times must not exceed those
stated in the table below. TS
= Ratio of motor starting torque to normal torque
The values given in the table are for starts when the motor is in a TN
warm condition after operation.
For cold starts, the values can be doubled. TMAX.
= Ratio of max. motor torque to normal torque
Max. permitted starting times in seconds for individual starts TN
132
Direct on-line starting 15 10 10 20 Ordering key
Star-delta starting 45 30 30 60
Direct on-line starting 15 15 20 20 Motor, single-speed APAL-a-bbbbb-c-0
160
Star-delta starting 45 45 60 60 Motor, two-speed,
Direct on-line starting 15 15 20 20 speed ratio 1:1.5 ATAL-a-bbbbb-c-0
180
Star-delta starting 45 45 60 60
speed ratio 1:2 ARAL-a-bbbbb-c-0
Direct on-line starting 15 15 20 20
200
Star-delta starting 45 45 60 60 Number of poles 1) (see motor tables): 2, 4, 6, 8
Direct on-line starting 15 15 20 20
225
Star-delta starting 45 45 60 60 Rated output 1) (see motor tables):
Direct on-line starting 15 15 20 20 The first three digits of the "bbbbb" code give the number
250 of whole kW, the last two digits are decimals.
Star-delta starting 45 45 60 60
E.g. code 00175 denotes 1.75 kW.
Direct on-line starting 15 18 17 15
280
Star-delta starting 45 54 51 45
Voltage
Direct on-line starting 15 18 16 12
315 Single-speed motor Two-speed motor
Star-delta starting 45 54 48 36
1 = 220-240 VD/380-420 VY 2) 2 = 400 V
Direct on-line starting 15 20 18 30 2 = 380-420 VD/660-690 VY 5 = 500 V
355
Star-delta starting 45 60 54 90
5 = 500 VY (sizes 63-100)
500 VD (sizes 112-355)
Where starting is frequent, the motor cannot be run at the rated output
owing to the effect on the windings of starting heat losses. The per- 1) For the higher speed of a two-speed motor.
missible motor output can be calculated using the number of starts 2) Star-delta starting is not possible if the motor is star connected.
per hour, the load's moment of inertia and the load's rotational speed.
Please contact Flkt Woods AB. Slide rails, set XYLS-aa
NB! A motor can be started using a star-delta starter provided that the Size: 02, 03, 04, 05, 06
motor is delta-connected. During starting, the motor is star-connected
and torque is consequently reduced. Check that the motor's torque
curve is higher than the fan's torque curve throughout the range up to
90% of the synchronous speed. If no torque curves are available, the
following formulae are sufficiently accurate for determining the mini-
mum motor rating.
Electric motors Page 102
Single-speed motors, 50 Hz
Size designation Rated At rated output Size designation Rated At rated output
out- out-
ABB Designation put RPM Approx. Is2) Ts Tmax. Weight ABB Designation put RPM Approx. Is2) Ts Tmax Weight
IEC Motors A at IN TN TN IEC Motors A at IN TN TN
kW 400V 1) kg kW 400V1) kg
APAL- APAL-
63 M2AA 63 B 2-00025-c-0 0.25 2820 0.70 4.0 2.2 2.7 4.5 71 M2AA 71 6-00012-c-0 0.12 930 0.59 2.5 2.3 2.7 5.0
71 M2AA 71 A 2-00037-c-0 0.37 2840 0.93 4.5 2.2 2.7 5.5 71 M2AA 71 A 6-00018-c-0 0.18 920 0.75 2.5 2.0 2.4 5.5
71 M2AA 71 B 2-00055-c-0 0.55 2850 1.33 5.0 2.2 2.7 6.5 71 M2AA 71 B 6-00025-c-0 0.25 920 0.92 3.0 2.0 2.4 6.5
80 M2AA 80 A 2-00075-c-0 0.75 2860 1.7 5.0 2.2 2.7 9 80 M2AA 80 A 6-00037-c-0 0.37 920 1.25 3.5 2.1 2.5 8.5
80 M2AA 80 B 2-00110-c-0 1.1 2870 2.4 5.5 2.4 3.0 10 80 M2AA 80 B 6-00055-c-0 0.55 930 1.78 3.5 2.1 2.5 9.5
90 S M2AA 90 S 2-00150-c-0 1.5 2870 3.3 5.5 2.4 3.0 13 90 S M2AA 90 S 6-00075-c-0 0.75 930 2.36 4.0 1.9 2.3 13
90L M2AA 90 L 2-00220-c-0 2.2 2870 4.55 7.0 2.7 3.4 16 90 L M2AA 90 L 6-00110-c-0 1.1 930 3.25 4.0 1.9 2.3 16
100 L M2AA 100 L 2-00300-c-0 3 2900 5.95 7.5 2.7 3.6 21 100 L M2AA 100 L 6-00150-c-0 1.5 950 4.1 4.5 1.9 2.3 23
112 M M2AA 112 M 2-00400-c-0 4 2850 7.4 7.5 2.8 3.0 25 112 M M2AA 112 M 6-00220-c-0 2.2 940 5.4 5.6 2.1 2.7 27
132 S M2AA 132 SA 2-00550-c-0 5.5 2855 10.5 7.8 3.2 3.4 37 132 S M2AA 132 S 6-00300-c-0 3 960 6.9 6.1 2.4 2.6 39
132 S M2AA 132 SB 2-00750-c-0 7.5 2855 13.9 8.5 3.4 3.6 42 132 M M2AA 132 MA 6-00400-c-0 4 960 8.7 7.1 2.6 2.8 46
160 M M2AA 160 MA 2-01100-c-0 11 2930 20.0 6.3 1.9 2.5 73 132 M M2AA 132 MB 6-00550-c-0 5.5 955 11.9 6.9 2.8 2.8 54
160 M M2AA 160 M 2-01500-c-0 15 2920 26.5 6.6 2.3 2.5 84 160 M M2AA 160 M 6-00750-c-0 7.5 970 15.4 6.7 2.0 2.8 88
160 L M2AA 160 L 2-01850-c-0 18.5 2920 32.0 7.3 2.6 2.7 94 160 L M2AA 160 L 6-01100-c-0 11 970 23.0 7.1 2.2 2.8 102
180 M M2AA 180 M 2-02200-c-0 22 2930 38.5 7.2 2.5 2.7 119 180 L M2AA 180 L 6-01500-c-0 15 970 31.0 7.0 2.1 3.0 151
200 L M2AA 200 MLA 2-03000-c-0 30 2955 53 7.3 2.4 3.1 175 200 L M2AA 200 MLA 6-01850-c-0 18.5 985 36 7.0 2.5 2.7 165
200 L M2AA 200 MLB 2-03700-c-0 37 2950 64 7.3 2.5 3.2 200 200 L M2AA 200 MLB 6-02200-c-0 22 980 43 7.2 2.5 2.7 185
225 M M2AA 225 SMB 2-04500-c-0 45 2960 79 7.3 2.5 2.8 235 225 M M2AA 225 SMB 6-03000-c-0 30 985 56 6.6 2.5 2.7 225
250 M M2AA 250 SMA 2-05500-c-0 55 2970 95 7.5 2.0 3.0 285 250 M M2AA 250 SMA 6-03700-c-0 37 985 69 7.3 2.8 2.8 280
280 S M2CA 280 SA 2-07500-c-0 75 2977 131 7.4 2.0 2.9 480 280 S M2CA 280 SA 6-04500-c-0 45 990 85 7.0 2.6 2.6 440
280 M M2CA 280 SMA 2-09000-c-0 90 2975 152 7.2 2.1 2.7 545 280 M M2CA 280 SMA 6-05500-c-0 55 989 102 7.0 2.7 2.6 475
315 S M2CA 315 SA 2-11000-c-0 110 2982 194 7.6 2.0 3.0 695 315 S M2CA 315 SA 6-07500-c-0 75 992 143 7.5 2.3 2.7 630
315 M M2CA 315 SMA 2-13200-c-0 132 2982 228 7.4 2.2 3.0 770 315 M M2CA 315 SMA 6-09000-c-0 90 991 165 7.1 2.3 2.7 720
315 M M2CA 315 MB 2-16000-c-0 160 2981 269 7.5 2.3 3.0 840 315 M M2CA 315 MB 6-11000-c-0 110 991 201 7.3 2.5 2.8 805
355 S M2CA 355 SA 2-20000-c-0 200 2977 330 6.6 1.3 2.8 1220 355 S M2CA 355 SA 6-13200-c-0 132 992 235 6.8 1.7 2.6 1200
355 M M2CA 355 MA 2-25000-c-0 250 2980 410 6.6 1.3 3.0 1320 355 S M2CA 355 SB 6-16000-c-0 160 992 280 6.8 1.8 2.7 1320
355 M M2CA 355 MB 2-28000-c-0 280 2978 470 5.7 1.1 2.7 1320 355 M M2CA 355 MA 6-20000-c-0 200 993 350 7.5 2.0 2.8 1550
355 M M2CA 355 MB 6-25000-c-0 250 991 475 7.3 2.2 3.0 1550
APAL- APAL-
63 M2AA 63 B 4-00018-c-0 0.18 1370 0.72 3.0 2.2 2.6 4.5 80 M2AA 80 A 8-00018-c-0 0.18 700 0.90 2.5 1.8 2.3 8.5
71 M2AA 71 A 4-00025-c-0 0.25 1400 0.83 3.5 2.2 2.7 5.5 80 M2AA 80 B 8-00025-c-0 0.25 700 1.18 2.5 1.9 2.4 9.5
71 M2AA 71 B 4-00037-c-0 0.37 1410 1.12 4.0 2.2 2.7 6.5 90 S M2AA 90 S 8-00037-c-0 0.37 700 1.60 3.0 1.9 2.4 13
80 M2AA 80 A 4-00055-c-0 0.55 1420 1.45 4.0 2.2 2.7 9 90 L M2AA 90 L 8-00055-c-0 0.55 700 2.35 3.0 1.9 2.4 16
80 M2AA 80 B 4-00075-c-0 0.75 1420 1.9 4.5 2.2 2.7 10 100 L M2AA 100 LA 8-00075-c-0 0.75 700 2.67 3.5 2.1 2.7 20
90 S M2AA 90 S 4-00110-c-0 1.1 1410 2.59 5.0 2.2 2.7 13 100 L M2AA 100 LB 8-00110-c-0 1.1 700 3.42 3.5 2.1 2.7 23
90 L M2AA 90 L 4-00150-c-0 1.5 1420 3.4 5.0 2.4 2.9 16 112 M M2AA 112 M 8-00150-c-0 1.5 695 4.5 4.1 1.9 2.4 28
100 L M2AA 100 LA 4-00220-c-0 2.2 1430 4.8 5.5 2.4 2.9 21 132 S M2AA 132 S 8-00220-c-0 2.2 720 5.9 5.3 1.9 2.5 46
100 L M2AA 100 LB 4-00300-c-0 3 1430 6.48 5.5 2.5 2.9 24 132 M M2AA 132 M 8-00300-c-0 3 720 7.8 5.5 2.4 2.6 53
112 M M2AA 112 M 4-00400-c-0 4 1435 8.6 7.0 2.9 3.1 27 160 M M2AA 160 MA 8-00400-c-0 4 715 10.0 5.2 2.1 2.4 75
132 S M2AA 132 S 4-00550-c-0 5.5 1450 11.1 7.3 2.2 3.0 40 160 M M2AA 160 M 8-00550-c-0 5.5 710 13.4 5.4 2.4 2.6 88
132 M M2AA 132 M 4-00750-c-0 7.5 1450 14.8 7.9 2.5 3.2 48 160 L M2AA 160 L 8-00750-c-0 7.5 715 18.1 5.4 2.4 2.8 118
160 M M2AA 160 M 4-01100-c-0 11 1460 22.5 6.7 2.9 2.8 75 180 L M2AA 180 L 8-01100-c-0 11 720 23.5 5.9 2.4 2.6 147
160 L M2AA 160 L 4-01500-c-0 15 1455 28.5 6.8 3.0 2.8 94 200 L M2AA 200 MLA 8-01500-c-0 15 740 29 7.4 1.8 3.0 175
180 M M2AA 180 M 4-01850-c-0 18.5 1470 35 7.0 3.1 2.7 124 225 S M2AA 225 SMA 8-01850-c-0 18.5 730 37 6.2 1.9 2.7 210
180 L M2AA 180 L 4-02200-c-0 22 1470 41 7.0 2.9 2.8 141 225 M M2AA 225 SMB 8-02200-c-0 22 730 45 6.0 1.9 2.7 225
200 L M2AA 200 MLA 4-03000-c-0 30 1475 56 6.7 2.6 2.8 180 250 M M2AA 250 SMA 8-03000-c-0 30 735 59 6.9 1.9 2.9 280
225 S M2AA 225 SMA 4-03700-c-0 37 1480 68 6.6 2.4 2.5 215 280 S M2CA 280 SA 8-03700-c-0 37 741 74 6.8 1.6 2.7 460
225 M M2AA 225 SMB 4-04500-c-0 45 1480 83 6.7 2.7 2.6 230 280 M M2CA 280 SMA 8-04500-c-0 45 741 90 7.1 1.8 2.8 500
250 M M2AA 250 SMA 4-05500-c-0 55 1480 98 7.5 2.3 2.8 275 315 S M2CA 315 SA 8-05500-c-0 55 741 107 7.1 1.8 2.8 630
280 S M2CA 280 SA 4-07500-c-0 75 1483 137 6.9 2.2 2.8 445 315 M M2CA 315 SMA 8-07500-c-0 75 740 142 7.1 1.8 2.8 715
280 M M2CA 280 SMA 4-09000-c-0 90 1484 163 7.6 2.5 2.9 490 315 M M2CA 315 MB 8-09000-c-0 90 740 169 7.3 1.9 2.8 800
315 S M2CA 315 SA 4-11000-c-0 110 1487 198 6.5 2.1 2.6 675 355 S M2CA 355 SA 8-11000-c-0 110 742 215 5.6 1.4 2.2 1200
315 M M2CA 315 SMA 4-13200-c-0 132 1486 238 6.3 2.2 2.7 730 355 M M2CA 355 MA 8-13200-c-0 132 743 265 5.8 1.5 2.3 1350
315 M M2CA 315 MB 4-16000-c-0 160 1486 282 7.0 2.4 2.7 850 355 M M2CA 355 MB 8-16000-c-0 160 742 310 6.4 1.8 2.5 1550
355 S M2CA 355 SA 4-20000-c-0 200 1487 345 7.0 2.1 2.7 1220
355 M M2CA 355 MA 4-25000-c-0 250 1487 430 7.2 2.3 2.8 1350
355 M M2CA 355 LA 4-31500-c-0 315 1488 545 7.4 2.4 2.8 1550
Voltage code
1 = 220-240 VD/380-420 VY, 50 Hz
2 = 380-420 VD/660-680 VY, 50 Hz
5 = 500 VY (sizes 63-100)
500 VD (sizes 112-355)
1) Conversion factor where the rated supply is other than 400V, 50Hz. Housing class IP 55
Dust-proof, spray-proof design. Sizes 63 - 355 are delivered as standard in a
Rated supply at 50 Hz design complying to IP 55.
and motor wound for: conversion factor
220 V 1.82 Drain holes
230 V 1.74 The basic versions of sizes 63 - 100 are supplied without drain holes but can be
415 V 0.96 provided with holes if required. The housing class then becomes IP 54 unless
500 V 0.80 special felt plugs are used.
660 V 0.61 Sizes 112 - 355 are supplied with closeable plastic plugs in the drain holes. The
690 V 0.58 plugs are in the open position when the motors are delivered.
2) Is Insulation class
= ratio of motor start current to motor full-load current.
IN All motors have class F insulation.
The standard rated outputs of motors from ABB Motors are, in most cases, based
3) Temperature rise as per insulation class F. on the temperature increases applying to insulation class B.
Where temperature rises are also to class F, this is specified in the tables.
Electric motors Page 103
3000 and 1500 rpm synchronous, 2 and 4 poles. 1500 and 750 rpm synchronous, 4 and 8 poles.
One stator winding (YY/Y). One stator winding (YY/Y).
ARAL-2 ARAL-4
2 0.55 2800 1.4 4.0 1.5 2.0 4 0.37 1390 1.2 3.3 1.8 1.8
71 M2AA 71 B 00055-c-0 6.5 71 M2AA 71 B 00037-c-0 6.5
4 0.11 1440 0.5 3.0 1.4 2.4 8 0.09 980 0.49 2.0 1.4 2.8
2 0.75 2850 1.9 4.5 1.8 2.4 4 0.55 1380 1.6 3.1 1.5 1.8
80 M2AA 80 A 00075-c-0 9 80 M2AA 80 A 00055-c-0 8.5
4 0.15 1460 0.67 3.5 1.4 2.4 8 0.11 700 0.54 2.3 1.4 1.8
2 1.1 2860 2.6 5.0 1.8 2.4 4 0.75 1390 2.0 3.4 1.5 1.9
80 M2AA 80 B 00110-c-0 10 80 M2AA 80 B 00075-c-0 9.5
4 0.23 1460 0.88 3.7 1.3 2.4 8 0.16 700 0.70 2.4 1.2 1.9
2 1.5 2860 3.3 5.2 1.8 2.4 4 1.1 1410 2.8 4.2 1.8 2.3
90 S M2AA 90 S 00150-c-0 13 90 S M2AA 90 S 00110-c-0 13
4 0.33 1460 1.1 3.9 1.1 2.4 8 0.26 700 1.2 2.4 1.2 1.9
2 2.2 2860 4.6 5.9 2.1 2.6 4 1.5 1420 3.7 4.8 2.2 2.7
90 L M2AA 90 L 00220-c-0 16 90 L M2AA 90 L 00150-c-0 16
4 0.45 1460 1.4 4.4 1.2 2.6 8 0.31 710 1.5 2.8 1.7 2.5
2 3.5 2880 7.0 6.2 2.1 2.8 4 2.2 1430 5.1 5.1 1.9 2.5
100 L M2AA 100 LB 00350-c-0 25 100 L M2AA 100 LA 00220-c-0 20
4 0.7 1470 2.0 4.8 1.2 3.0 8 0.48 720 1.8 3.0 1.2 2.1
2 4.5 2875 8.4 7.0 1.8 2.3 4 2.8 1430 6.4 5.2 2.0 2.6
112 M M2AA 112 M 00450-c-0 32 100 L M2AA 100 LB 00280-c-0 23
4 1 1450 2.4 6.0 1.9 2.8 8 0.6 720 2.2 3.0 1.2 2.2
2 6.2 2880 11.8 7.0 2.0 2.6 4 3.5 1430 7.0 6.8 1.6 2.5
132 S M2AA 132 S 00620-c-0 42 112 M M2AA 112 M 00350-c-0 32
4 1.3 1455 3.5 6.5 2.6 3.3 8 0.7 720 2.5 4.4 1.7 2.7
2 8.3 2875 15.4 7.4 2.5 2.7 4 5.0 1450 9.9 6.4 1.5 2.3
132 M M2AA 132 M 00830-c-0 56 132 S M2AA 132 S 00500-c-0 48
4 1.7 1455 4.2 6.6 2.7 3.3 8 1.0 725 3.3 3.6 1.0 2.0
2 10 2910 19.0 5.9 1.5 2.3 4 6.8 1460 13.7 7.6 2.0 2.8
160 M M2AA 160 MA 01000-c-0 73 132 M M2AA 132 M 00680-c-0 59
4 2 1465 4.8 6.1 2.4 2.8 8 1.4 730 5.1 3.6 1.4 2.7
2 16 2915 28.5 6.6 1.8 2.4 4 10.5 1460 21 6.9 2.2 2.7
160 M M2AA 160 M 01600-c-0 94 160 M M2AA 160 M 01050-c-0 94
4 3.2 1465 7.0 6.3 2.5 2.8 8 2.2 735 7.4 3.7 1.5 2.3
2 19.5 2930 36 7.6 2.3 2.9 4 15.5 1460 30 6.9 2.2 2.6
160 L M2AA 160 L 01950-c-0 100 160 L M2AA 160 L 01550-c-0 117
4 4.5 1465 9.7 6.4 2.5 2.8 8 2.7 735 9.5 3.9 1.7 2.6
2 21.5 2935 38 7.0 2.1 2.6 4 17 1470 33 5.8 1.7 2.3
180 M M2AA 180 M 02150-c-0 137 180 M M2AA 180 M 01700-c-0 137
4 4.7 1465 10 5.3 2.1 2.3 8 3.4 730 11 4.3 1.2 1.9
2 26 2940 47 6.9 2.3 2.6 4 22 1475 43 6.7 2.0 2.6
180 L M2AA 180 L 02600-c-0 151 180 L M2AA 180 L 022000-c-0 161
4 5.2 1470 11 5.8 2.4 2.4 8 4.4 735 15 3.9 1.7 2.3
2 32 2940 58 7.1 2.0 2.5 4 29 1470 54 6.9 2.2 2.4
200 L M2AA 200 MLA 03200-c-0 180 200 L M2AA 200 MLA 02900-c-0 180
4 8 1465 16 6.2 2.0 2.2 8 6.5 730 17 4.2 1.9 1.9
200 L M2AA 200 MLB 03900-c-0 2 39 2950 69 7.4 2.0 2.6 4 33 1475 61 7.8 2.6 2.6
205 200 L M2AA 200 MLB 03300-c-0 205
4 10 1475 19 6.2 2.0 2.3 8 8 730 21 4.2 1.9 1.8
2 45 2955 76 7.4 2.0 2.6 4 42 1480 85 7.8 2.5 3.0
225 M M2AA 225 M 04500-c-0 235 225 M M2AA 225 SMB 04200-c-0 265
4 13 1475 25 5.3 2.0 2.1 8 10 740 27 5.0 2.2 2.3
4 50 1465 91 7.3 2.3 2.5
225 M M2AA 225 SMC 05000-c-0 265
8 11 735 28 4.7 2.0 2.0
4 60 1475 104 7.9 2.6 2.7
1500 and 1000 rpm synchronous, 4 and 6 poles. 250 M M2AA 250 SMB 06000-c-0
8 15 735 34 4.7 2.1 2.0
335
Two separate stator windings (Y/Y). 4 65 1484 121 7.5 2.7 2.9
280 S M2CA 280 SA 06500-c-0 445
8 15 743 38 5.3 2.8 2.3
4 80 1486 150 8.5 3.3 3.4
ATAL-4 280 M M2CA 280 SMA 08000-c-0 490
4 0.30 1400 0.9 3.3 1.5 2.0 8 20 743 50 5.4 2.9 2.6
71 M2AA 71 B 00030-c-0 6.5
6 0.10 950 0.56 2.3 1.4 2.1 4 90 1486 164 8.5 3.6 3.5
280 M M2CA 280 MB 09000-c-0 550
4 0.45 1400 1.3 3.7 1.7 2.1 8 23 742 56 5.4 2.8 2.6
80 M2AA 80 A 00045-c-0 8.5
6 0.15 960 0.73 2.6 1.3 2.2 4 110 1487 197 6.8 1.9 2.6
315 S M2CA 315 SMA 11000-c-0 730
4 0.65 1400 1.7 3.9 1.7 2.1 8 22 744 56 4.9 2.1 2.5
80 M2AA 80 B 00065-c-0 9.5
6 0.22 960 0.94 2.9 1.4 2.2 4 132 1486 235 6.8 2.0 2.6
315 M M2CA 315 MB 13200-c-0 850
4 1.0 1400 2.5 4.2 1.8 2.2 8 26 746 65 4.8 2.0 2.4
90 S M2AA 90 S 00100-c-0 13
6 0.3 940 1.2 2.6 1.0 1.7 4 160 1486 283 7.0 2.1 2.7
315 L M2CA 315 LA 16000-c-0 970
4 1.5 1400 3.5 4.3 1.7 2.1 8 32 743 80 4.8 2.1 2.5
90 L M2AA 90 L 00150-c-0 16
6 0.45 940 1.6 2.9 1.0 1.8 4 200 1489 340 6.8 1.4 2.8
355 M M2CA 355 MA 20000-c-0 1350
4 2.0 1430 4.5 5.0 1.8 2.4 8 40 745 90 4.8 1.3 2.5
100 L M2AA 100 LA 00200-c-0 20
6 0.6 960 2.0 3.3 1.0 1.9 4 250 1490 435 7.5 1.5 3.2
355 L M2CA 355 LA 25000-c-0 1550
4 2.5 1430 5.5 5.6 2.0 2.5 8 50 745 120 5.1 1.4 2.6
100 L M2AA 100 LB 00250-c-0 23
6 0.8 960 2.5 3.5 1.1 2.0
4 3.0 1445 6.3 6.0 1.3 2.3
112 M M2AA 112 M 00300-c-0
6 1.0 975 3.1 4.0 1.0 2.2
33 Voltage code
4 4.5 1460 9.2 6.5 1.5 2.3 2 = 400 V
132 S M2AA 132 A 00450-c-0 48
6 1.5 985 5.1 4.2 1.0 2.2
5 = 500 V
4 6.0 1460 12 7.1 1.8 2.5
132 M M2AA 132 M 00600-c-0 59
6 2.0 980 5.6 4.5 1.3 2.0
4 10.5 1460 21 6.4 2.0 2.5
160 M M2AA 160 M 01050-c-0 94
6 3.5 965 8.6 4.1 1.3 1.7 1) Conversion factor for 500 V supply = 0.80.
4 14.5 1460 28 6.9 2.2 2.6
160 L M2AA 160 L 01450-c-0 117
6 4.5 970 11 4.6 1.5 1.9 2) Is
4 16 1470 31 6.3 1.9 2.5 = ratio of motor start current to motorfull-load current.
180 M M2AA 180 M 01600-c-0
6 5 980 12.5 4.6 1.5 2.0
137 IN
4 20 1470 39 7.2 2.4 2.7
180 L M2AA 180 L 02000-c-0 161
4 6.5 980 16 5.0 1.8 2.0
4 23 1475 43 7.7 1.6 2.8
200 L M2AA 200 MLA 02300-c-0 175
6 7.2 985 15 7.8 1.9 2.9
4 30 1470 54 7.7 1.6 2.7
200 L M2AA 200 MLB 03000-c-0 200
6 9 985 18 7.9 1.7 2.5
4 34 1470 60 7.7 1.5 2.7
225 M M2AA 225 SMB 03400-c-0 225
6 11 985 21 6.7 1.3 2.3
4 42 1475 75 8.4 1.7 3.0
225 M M2AA 225 SMC 04200-c-0 255
6 14 985 27 6.8 1.4 2.3
4 63 1475 110 7.5 2.4 2.7
250 M M2AA 250 SMB 06300-c-0 335
6 18.5 985 40 7.3 3.0 2.6
4 77 1486 144 7.6 2.4 2.9 Voltage code
280 S M2CA 280 SA 07700-c-0 490
6 25 991 54 7.7 3.2 2.7
2 = 400 V
4 90 1485 161 7.4 2.3 2.7
280 M M2CA 280 MB 09000-c-0 550 5 = 500 V
6 28 991 58 7.7 3.2 2.8
Dimensions - Motors Page 104
HD HD
HC
H H
K KA K BC A
A E C B
E C B B' AB
BB AB BB
HD HD
AC
H H
K K A
A E C B
E C L AB
AB B'
B'
BB
BB
HD
HC GA
H
DB
E C B A
B' AB D
BB
L
Size
as per Single- Two-
ABB Motors speed speed A1) AB AC B1) B'1) BB C D1) DB E EA F1) GA H1) HC HD K KA L L12) L23)
63 B All All 100 120 - 80 - 98 40 14 M5 30 - 5 16 63 123 150 7 10 213 - -
71 (A, B) All All 112 136 - 90 - 112 45 14 M5 30 - 5 16 71 141 172 7 11 239 - -
80 (A, B) All All 125 154 - 100 - 125 50 19 M8 40 - 6 21.5 80 159 192 10 14 272 - -
90 S All All 140 170 - 100 - 125 56 24 M8 50 - 8 27 90 179 212 10 14 295 - -
90 L All All 140 170 - 125 - 150 56 24 M8 50 - 8 27 90 179 212 10 14 320 - -
100 L(A) All All 160 197 - 140 - 172 63 28 M10 60 - 8 31 100 199 236 12 15 358.5 - -
112 M All All 190 222 221 140 - 168 70 28 M10 60 40 8 31 112 - 258 12 - - 3614) 3884)
132 S (A, B) All All 216 262 261 140 1784) 212 89 38 M12 80 50 10 41 132 - 295.5 12 - - 4474) 4474)
132 M All All 216 262 261 1404) 178 212 89 38 M12 80 50 10 41 132 - 295.5 12 - - 4474) 481,54)
160 5) 5) 5) 254 310 - 210 2544) 287.5 108 42 M16 110 - 12 45 160 - 368.5 15 - 602.5 - -
160 6) 6) 6) 254 310 - 2104) 254 287.5 108 42 M16 110 - 12 45 160 - 368.5 15 - 643.5 - -
180 7) 7) 7) 279 340 - 241 2794) 316 121 48 M16 110 - 14 51.5 180 - 403.5 15 - 680 - -
180 8) 8) 8) 279 340 - 2414) 279 316 121 48 M16 110 - 14 51.5 180 - 403.5 15 - 700.5 - -
200 ML. 2-8 All 318 380 386 2674) 305 365 133 55 M20 110 - 16 59 200 - 496.5 18 - 773 - -
225 SM. 4-8 4/8 356 418 425 286 3114) 360 149 60 M20 140 - 18 64 225 - 542 18 - 865 - -
225 SM. 2 2/4 356 418 425 2864) 311 360 149 55 M20 110 - 16 59 225 - 542 18 - 835 - -
225 SM. 4-8 4/6, 4/8 356 418 425 2864) 311 360 149 60 M20 140 - 18 64 225 - 542 18 - 865 - -
250 SM. 2 - 406 474 471 3114) 349 409 168 60 M20 140 - 18 64 250 - 590 22 - 872 - -
250 SM. 4-8 4/6, 4/8 406 474 471 3114) 349 409 168 65 M20 140 - 18 69 250 - 590 22 - 872 - -
280 SA 2 - 457 545 - 368 - 450 190 65 M20 140 - 18 69 280 558 730 24 - 1060 - -
280 SA 4-8 4/8, 4/6 457 545 - 368 - 450 190 75 M20 140 - 20 79.5 280 558 730 24 - 990 - -
280 SMA 2 - 457 545 - 368 419 501 190 65 M20 140 - 18 69 280 558 730 24 - 1060 - -
280 SMA 4-8 4/8 457 545 - 368 419 501 190 75 M20 140 - 20 79.5 280 558 730 24 - 1060 - -
280 MB - 4/6 457 545 - 419 - 501 190 75 M20 140 - 20 79.5 280 558 730 24 - 1120 - -
315 SA 2 - 508 622 - 406 - 535 216 65 M20 140 - 18 69 315 627 820 28 - 1095 - -
315 SA 4-8 - 508 622 - 406 - 535 216 80 M20 170 - 22 85 315 627 820 28 - 1125 - -
315 SMA 2 - 508 622 - 406 457 535 216 65 M20 140 - 18 69 315 627 820 28 - 1195 - -
315 SMA 4-8 - 508 622 - 406 457 535 216 80 M20 170 - 22 85 315 627 820 28 - 1125 - -
315 MB 2 - 508 622 - 457 - 540 216 65 M20 140 - 18 69 315 627 820 28 - 1195 - -
315 MB 4-8 - 508 622 - 457 - 540 216 80 M20 170 - 22 85 315 627 820 28 - 1225 - -
355 SA 2 - 610 714 - 500 - 584 254 70 M20 140 - 20 74.5 355 715 920 28 - 1310 - -
355 SA 4-8 - 610 714 - 500 - 584 254 100 M24 210 - 28 106 355 715 920 28 - 1380 - -
355 MA 2 - 610 714 - 560 - 644 254 70 M20 140 - 20 74.5 355 715 920 28 - 1370 - -
355 MA 4-8 - 610 714 - 560 - 644 254 100 M24 210 - 28 106 355 715 920 28 - 1440 - -
355 MB 2 - 610 714 - 560 - 644 254 70 M20 140 - 20 74.5 355 715 920 28 - 1370 - -
355 MB 4-8 - 610 714 - 560 - 644 254 100 M24 210 - 28 106 355 715 920 28 - 1440 - -
355 LA 4-8 - 610 714 - 630 - 714 254 100 M24 210 - 28 106 355 715 920 28 - 1520 - -
Material, finish
o
001 = Standard material, GA80-RAL5007 int. and ext. Fully welded Max. temperature 120 C.
002 = Standard material, GP40-01 int. and ext. Fully welded Max. temperature 150oC. 1)
072 = Standard material, GA80TD80-RAL5007 int. and ext. Fully welded Max. temperature 120oC.
112 = Standard material, GA80TB80-RAL5007 int. and ext. Fully welded Max. temperature 120oC.
290 = Standard material, hot-dip galvanized. Fully welded
300 = SS 2333 throughout. Fully welded
400 = SS 2343 throughout. Fully welded
1) o
GP40-01 primer can be used where temperatures exceed 120 C. This primer tolerates temperatures up to
150oC and vaporises at higher temperatures without emitting any toxic substances.
Counterflange HCEZ-25-bbb-cc
Size (= damper size)
Material
01 = unpainted steel (for welding in).
03 = SS 2333.
04 = SS 2343.
0 10 20 30 40 50 60 7090
1000 a 100
Closed
Total pressure drop, Pa
500 50
400 40
300
n
30
ope
200 20
ully
er f
100
mp
10
Da
C
50 5
0,5 1 2 3 4 5 10 20 304050
Air velocity, m/s
Description
The HXEG inlet vane control assembly is designed for flow control in centrifugal fans and is connected directly to the
fan inlet flange. The assembly is of a robust construction and provides highly economic flow control. The size range fol-
lows that of the HC fans and the flanges comply with ISO 13351. NB! The HXEG must not be connected directly to the
fan without checking that the anti-vibration mountings can cope with the increased component load on the fan.
- The HXEG is available in sizes 031-160. The max. permitted gas temperature is 350C.
- Robust construction, (handles pressures up to 20 kPa).
The assembly's chief components are: casing, guide vanes, hub and control mechanism. The casing has connecting
flanges on both ends. The guide vane shaft is supported on bearings in the hub and casing. The hub is supported by
radial stays. The assemblies can be connected to fans which, under fully throttled conditions at 20C, will give max.
pressure rise of 20 kPa.
Regulation is either by an actuator or manually with the lever.
Control
The assembly can be equipped with an actuator. Four different actuators are available as accessories: HXEZ05 (electric),
HXEZ-06 (electric), HXEZ-07 (pneumatic) and HXEZ-08 (electric).
Actuator
Actuators are double-acting and are console mounted on the assemblies.
Actuator specifications
HXEZ- Type Max. actuation pressure (N) Electrical details Environment Control
Sizes
HXEG 031, 040, 050, 063, 071, 080, 090, 100, 112, 125, 140 and 160.
The assemblies are suitable for standard fans. Assemblies and fans have common size codes.
Principles of operation
The guide vanes, which can be set in various positions, impart a rotary motion to the gas stream as it reaches the
impeller. This lowers the pressure and output characteristics of the fan and ensures good operating economy over a
relatively wide control range.
Pressure drop
The pressure drop with the vanes fully open is 0.2 pd where pd is the dynamic pressure.
Instructions
Installation and maintenance instructions are
included in the delivery.
Ordering key - Inlet vane control assembly HXEG and accessories Page 107
Material, finish
001 = Standardmaterial, GA80-RAL5007 int. and ext. Fully welded Max. temperature 120oC.
002 = Standard material, GP40-01 int. and ext. Fully welded Max. temperature 150oC. 1)
072 = Standard material, GA80TD80-RAL5007 int. and ext. Fully welded Max. temperature 120oC.
112 = Standard material, GA80TB80-RAL5007 int. and ext. Fully welded Max. temperature 120oC.
290 = Standard material, hot-dip galvanized. Fully welded
300 = SS 2333 throughout. Fully welded
400 = SS 2343 throughout. Fully welded
Version
1 = right-hand.
2 = left-hand.
Material, finish
001 = Standard material, GA80-RAL5007 int. and ext. Max. temperature 120oC.
002 = Standard material, GP40-01 int. and ext. Max. temperature 150oC. 1)
072 = Standard material, GA80TD80-RAL5007 int. and ext. Max. temperature 120oC.
112 = Standard material, GA80TB80-RAL5007 int. and ext. Max. temperature 120oC.
290 = Standard material, hot-dip galvanized.
300 = SS 2333 throughout.
400 = SS 2343 throughout.
Version
1 = right-hand.
2 = left-hand.
Actuator HXEZ-aa-bbb-ccc-d
Type of actuator. Refer to table on page 106
aa = 05, electric.
aa = 06, electric.
aa = 07, pneumatic.
aa = 08, electric.
1)
GP40-01 primer can be used where temperatures exceed 120oC. This primer tolerates temperatures up to 150oC
and vaporises at higher temperatures without emitting any toxic substances.
Inlet vane control assembly HXEG - Dimensions and weights Page 108
HXEG HXEG 031 with inlet taper piece HXEG 040 - 160
G
50
Open Closed 8 holes 12
10,5 366 pitch
491 C
Hold, t = 8
315 D
400 K
ins. ins.
R holes F H vanes
E B
210
435 A
Size A B C D E F G H K R Weight
031 - - - - 448 12 41.5 7 628 12 47
040 264 225 491 400 448 12 41.5 7 628 12 38
050 289 225 596 500 551 12 41.5 7 728 12 40
063 348 250 671 630 698 14 66.5 7 858 16 52
071 290 225 735 710 775 14 51.5 11 940 16 68
080 306 235 805 800 869 14 51.5 11 1030 24 76
090 322 235 885 900 958 14 56.5 11 1130 24 94
100 354 265 965 1000 1067 14 71.5 11 1230 24 108
112 368 280 1200 1120 1200 18 90.5 13 1375 32 141
125 387 300 1266 1250 1337 18 90.5 13 1507 32 171
140 454 335 1341 1400 1475 18 135.5 13 1657 32 211
160 493 375 1441 1600 1675 18 145.5 13 1857 40 298
570 570
ao ao
U U
10
Left-hand model Right-hand model
Gas flow
090
When the pneumatic actuator HXEZ-7 is used in 300
080
the above operating conditions, the forces given 200 1000 071
by the chart must be increased by 0.5 x a kPa. 063
Using the calculated actuating force as the star-
ting point, the necessary min. pressure can be 100 500 050
400
read directly from the chart. 040
300
031
50
200
40
Size
30
100
Power demand, %
40
Fans HCBB, HCGB, HCMB and HCHB L2
(all trottling curves).
L3
20 L4
L5
L6
Fans HCLP, HCMP and HCHP
(all trottling curves).
0
0 20 40 60 80 100
Example calculation
A size 100 HCMB centrifugal fan is controlled by an inlet vane control assembly and is to operate at constant speed at
two points (load 1 and load 2). Determine the speed and power demand for both operating points.
Chart 1 Chart 2
1 n=
3 HCMB
13
8000 2
70
r/m 100
in
7000 4 60
12
00
6000
I 5
5000
Tota pressure rise, Pa
100 40 MB
4000
0
II HC
3000 800
2000
20
600
10
1000 400
0 0
0 10 20 30 39 0 20 40 60 80 100
0 400
600 Gas flow, m3/s Gas flow, %, q / qo x 100
800
Power demand, kW
00
10
qo and Peo are the gas flow and power demand respectively
100 when the inlet vane control assembly is fully open.
00
12
nmax
< 100C 1370 r/min
200C 1260 r/min in
r/m
200 350C 1080 r/min 70
13
J (= 1/4 GD2) = 79 kg m2 n=
220
Inlet vane control assembly HXEG - Example calculation, cont. Page 111
Calculation
Absolute pressure at the fan inlet Pa1 Pa 99 000 - 2500 = 96 500 99 000 - 2000 = 97 000
1 1
Gas velocity at the fan outlet, v m/s 23.64 x = 29.6 17.33 x = 21.7
1 x 0.8 1 x 0.8
Size of the outlet, see fan dimension sketch
0.742 0.778
Dynamic pressure at the fan outlet, pd Pa x 29.62 = 325 x 21.72 = 183
2 2
Pressure drop across the open inlet vane control assembly Pa 0.2 X 325 = 65 0.2 X 183 = 37
Total pressure rise across the fan Pa 3400 + 65 = 3465 2500 + 37 = 2537
0.742
Power demand at r = 0.742 kg/m3 kW x 155 = 95.8 -
1.2
Pd 283 = 2.69
Throttling curve number, L, L = 10 - 10 x
Pt 3923
Gas flow (qo) with the assembly fully open, the same
throttling curve and fan speed n (1240 rpm in this case) m3/s - 21.8
Power demand (Peo) with the assembly fully open, the sa-
me throttling curve and fan speed n (1240 rpm in this case) kW - 149
Pe/Peo - 0.695
0.778
Power demand at r = 0.778 kg/m3 kW x1036= 67.2
- 1.2
The calculation shows that fan speed should be 1240 rpm. The power demand at working point 1 will then be 95.8 kW and 67.2 kW at working point 2, (allowance must
also be made for losses in the bearings and belt drive).
Centrifugal fan HC - Fan theory Page 112
The calculation assumes that the fan follows the same throttling curve throughout the entire
starting process.
Torque
% of Md
100
50
0
0 50 100
Speed %
We Bring Air to Life
Solutions for all your air climate and air movement needs
Flkt Woods is a global
Flkt Woods is providing solutions for ventilation and air climate for buildings as
leader in air management. well as fan solutions for Industry and Infrastructure.
We specialise in the design
Air Handling Units (AHUs) Fans
and manufacture of a wide
Modular, compact and small AHU Advanced axial, centrifugal and
range of air climate and air units. Designed to ensure optimisa- boxed fans for general and specialist
movement solutions. And tion of indoor air quality, operational applications. Comprehensive range
our collective experience performance and service life. including high temperature and ATEX
compliant options. Engineered for
is unrivalled. Air Terminal Devices and Ducts energy efficiency and minimised life
Supply and exhaust diffusers and cycle cost.
Our constant aim is to
valves for installation onwalls, ceiling
provide systems that or floor are all included in our large
Chillers
precisely deliver required range and fit all types of applications. Air-cooled and water-cooled chillers
function and performance, with cooling capacity up to 1800kW.
Chilled Beams Designed to minimised annual energy
as well as maximise consumption in all types of buildings.
Active induction beams for ventilation,
energy efficiency. cooling and heating, and passive
convection beams for cooling. For
Controls and drives
suspended or flush-mounted ceiling Variable speed drives and control
installation and multi-service config- systems, all tested to ensure total
uration. With unique Comfort Control compatibility with our products.
and Flow Pattern Control features. Specialist team can advise on energy
Copyright 2010 Flkt Woods Group
Energy recovery
Dessicant-based product and systems
that recover energy, increase ventilation
and control humidity.
FWG-Centrifugal fans HC_Technical data
Flkt Woods AB
SE-351 87 Vxj, Sweden
Phone +46 470 71 77 00
www.flaktwoods.se