[NOTES]
Actual Correct
Rated PSI Rated RPMs Actual RPMs
PSI PSI
Churn 220 2000 220 2000 220
100% 200 180 1895 200
150% 175 140 1790 175
Rated PSI
Fire Pump Flow Test Actual PSI
Correct PSI
250
200
150
100
50
0
Churn 100% 150%
PITOT TUBE READINGS
CALCULATOR Number Size Pitot PSI GPM
PSI 10 1
TIP SIZE 1 1/8 2
GPM 110 3
4
PSI 40 5
TIP SIZE 1 3/4 6
GPM 526 7
8
PSI 75 9
TIP SIZE 2 1/2 10
GPM 1276 11
12
TOTAL GPM 0