Floating Floor

 The Walking frequency for the occupancies as recreational and with full partition furnished floor
as:

Page | 1

As per Allen, D.E and Marray, T.M 1993:

  2.86 ln  


K = Occupancy constant = 58 kN
B = Damping factor = 0.05 for the roof
W = Slab Wight in kN = [( 6m x 5m ) x 0.27m] x 2.5 x 9.8 + the dead load = 614.7 kN

  1.8 hz

Date 15 Feb 2017


By.M.A
 The natural frequency for the panel only between two columns as per Bares 1971:


  


Page | 2 = frequency constant = 1.57 ( 1+2) = 1.57(1+(6/5)^2) = 3.831

   

 

o E = Dynamic modulus of elasticity for the slab = 1.25 from static modulus of elasticity
= 37475 Mpa
o h = slab thickness = 27mm
o  = Poissons ratio = 0.2
o  = mass per unit surface area of the slab for slab 0.27m thick = 0.000675 kg/mm2
o   9810 /
  30505127.51 mm2/sec
  !  3.24 hz > 1.8 hz safe



Date 15 Feb 2017


By.M.A
 The natural frequency for the slab between three columns (1 way mode) as per Szilard 1974:

Page | 3

1.57 &
  %
$ '

As    
 = 30505127.51 mm2/sec
  

  1.92() > 1.8 hz safe

Date 15 Feb 2017


By.M.A
  is the natural frequency for the floating floor system with the Eq. as it can be detriment at
the max peak for transmissibility:

Page | 4

The transmissibility (ratio of force transmitted to foundation to the input force), is:

Area 44.57936 m2
Load per area 628.0933598 KG/M2 Less than 978kg/m2
Spring stiffness 2744000 N/M DEFLECTION 25MM
Rubber pad stiffness 36736000 N/M DEFLECTION 0.3''
Eq load 7000 KG
Slab load 21000 KG
Fneq1 3.04 hz Less than 25hz as min chiller vibration freq
Fneq2 6.97 hz Less than 25hz as min chiller vibration freq

Transmissibillity
1000000
100000
10000
Transmissibillity

1000
100
10
1
0 5 10 15 20 25 30
0.1
0.01
Hz

Date 15 Feb 2017


By.M.A
 The max accepted acceleration for vibration as per ATC,1999; AISC/CISC 1997:

Page | 5

T at typical min ferq. For chiller 25hz.T = 0.014


Po = (2.1+7)*9.8*0.014= 0.384kN
W = 614.7 kN
B = Damping factor = 0.05 for the roof

Fn= 3.24 hz for the panel


ap/g = 0.004 = 0.4%..... ap= 0.0392 m/s2

Fn= 1.92 hz for the one way mode


ap/g = 0.0064 = 0.64%..... ap= 0.06 m/s2

Date 15 Feb 2017


By.M.A
 The max accepted RMS vibration speed as per Ashrea = RMS 0.016 in/sec
curve I:

Page | 6

ap/g = 0.004 = 0.4%..... ap= 0.0392 m/s2

So Vibration speed with chiller min vibration 25 hz =  = 2.5 e-4m/s..RMS =




1.765 e-4 m/s =0.0069 in/sec Safe

ap/g = 0.0064 = 0.64%..... ap= 0.06 m/s2

So Vibration speed with chiller min vibration 25 hz =  = 3.8 e-4 m/s..RMS = 2.7


e-4 m/s =0.01 in/sec.Safe

Date 15 Feb 2017


By.M.A