What Do and What Should Our Digital Revenue Meters Measure On Distorted Networks?

You might also like

Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 6

What do and what should our digital revenue meters measure

on distorted networks?
Dr. Andrs Dn Dvid Raisz
Budapest University of Technology and Economics, Department of Electric Power Engineering

II.POWER CONSIDERATIONS ON DISTORTED


Abstract This paper deals with power formulations and NETWORKS
energy considerations of non-sinusoidal systems. It is proved
in the paper that the so-called distortion power has no Harmonic currents tend to flow along the
physical meaning, and there is no need to take it into minimum impedance loop. If this current path
consideration. Simple patterns will underline these
statements. Furthermore the novel IEC recommendation of consists of resistance, harmonic active power
digital energy meters to measure the active energy should be (loss) will arise.
revised. There are different digital energy meters on the Generally speaking the harmonic active power
market. Results of laboratory tests are given on the accuracy
of energy meters from different manufacturers. on the network can be calculated as Ph = P P1
Keywords: harmonic power, power quality, energy meter where
accuracy 1
T

I. INTRODUCTION
P uidt (1)
T0
As it is well known the last decade of the 20 th 1
T

T 0
century power engineers will remember as the P1 u 1i 1dt (2)
decade of application of power electronics in
power systems. Low voltage and high voltage Assume that the voltage and the current consist
systems are loaded with non-linear consumers, of more different frequency sinusoidal
distorting the voltage of the supply system. The components (kf and mf, where k and m are
loads consume energy and they have to pay for whole numbers).
it. However the watt-hour meters are considered The time functions of u and i can be expanded in
to measure power of sinusoidal voltage and Fourier series and consequently the time function
current. The relating standard IEC 61036: 2000 of the instantaneous power p = ui consists of
[1] does not think on the practice when gives the different type of trigonometrical function
reference conditions. The watt-hour meters multiplications. Below the typical results of the
should comply with their classification under time integral of the different type trigonometrical
certain circumstances, like cos = 1, functions are discussed. There are 3 different
fundamental voltage is nominal, fundamental types to be investigated:
2
current is between given limit values, the
harmonic content of the voltage and current is
A. cos kt cos mtd t
0
(3)

between given limits. However especially the 2

harmonic current limits are much lower than B. sin kt cos mtd t (4)
they occur in the practice. 0
2
Several authors published results on the revenue
meter accuracy [2], [3], [4]. The results in these C. sin kt sin mtd t
0
(5)
papers do not cover the effect of a wide range of
k = m and k m where k, m = 0, 1, 2, .
possible harmonic distortion. In the present paper
the authors try to give a summary on the effect of First consider type A expressions:
cos kt cos mt
the possible harmonic distortions on the accuracy
1
of the revenue meters. cos k m t cos k m t 6
Another important issue is the definition of 2
harmonic power. Most of the papers discuss the Regarding the boundaries if k m, then both
problem from point of view of compensation [5] parts give zero. If k = m (k 0), then the second
and [6]. part results in
This paper tries to go back to the basics and 1 1
cos k m t (7)
discusses the energy balance of the network, 2 2
including the energy represented by harmonics. and the result of the integral:

1
2
1 1 U 12 U 2k ,
d t t 0
2

2 U eff (11)
(8)
2 0 2 h 2

If k = 0 and m = 0, then the integral of both 2
I eff I12 I 2m (12)
parties of eq.6 gives , the sum is 2. m2




2
U eff I eff
2
U 12 U 2k I12 I 2m
Regarding type B : k2 m2
sin kt cos mt

1 U 12 I12 U 12 I 2m U 2k I 2m I12 U 2k (13)


sin k m t sin k m t (9) m2 k2 m2 k 2
2
U 2
I 2
The result is zero for all k and m. eff
2 2
eff

U I 1 1

Regarding type C: 1 THD 2I THD 2U THD 2I THD 2U (14)


sin kt sin mt
where U 12 I12 S12
is the fundamental apparent
1
cos k m t cos k m t (10) power
2 If the short circuit power is infinite, THD U = 0
this is -1 times the result of eq. 6. and
Looking at type A, if k=m the result of
S2
cos(k+m)t will be a double frequency 1 THD I2 (15)
S12
component cos2kt, and cos(k-m)t gives the
average which is the center of the double The product U 1 I m 0
2 2
and accordingly
frequency swing. If k m, the average will be
m 2

zero, because of the cos(k-m)t. I 12 U k2 0 ,


k 2
The cases k m mean that the frequency of the
however according to the integral these products
voltage and current components is different
yield zero.
neither active nor reactive power can be
The product of the harmonic RMS voltage and
interpreted because the integral
2
current results in greater value than the product
cos kt cos mtd t results in zero. of the equal harmonic orders
0

At fundamental frequency supply the apparent
power gives the quantity characteristic to the
U I
k 2
2
k
m 2
2
m U
k 2
2
k I k2

sizing of the equipment. Because the active and


reactive powers are orthogonal, the apparent Conclusion: the equation S2 = P2 + Q2 is not
power can be calculated with the well-known applicable in case of distorted signals to calculate
equation: the reactive power, when S and P are measured.
S2 = P2 + Q 2 Turning back to eq. (14), regarding the real
However in case of distorted voltage and current values of the THDU, the THDU2 -terms can be
this kind of equation can be utilized only neglected and receive again
harmonics by harmonics, because the cases k
m result in zero. S2 P12 Q12 D 2
The apparent like power formally can be 1 THD 2
I (16)
calculated (S = UeffIeff), but it has no physical S12 P12 Q12
meaning, it is not characteristic to the sizing of D2
1 2 1 THD 2I (17)
the equipment (e.g. capacitor, transformer, S1
motor). The cases k m result in zero, but the D S1 THD I (18)
RMS product includes all frequency components. Actually D is a measure of the current distortion,
The statement can follow introducing the THD but weighted with the fundamental apparent
definition for the k-th and m-th harmonic orders: power.
If the goal is to punish the distorting consumer it

2
is a better way to determine its real current against distorting loads.
contribution to the distortion. 3. To measure the current distortion, the
monoparameter variation based separation
Simple examples are given in the Appendix to method [7] should be used.
prove the above-mentioned statement.
On Fig. A1 the clean initial situation is shown IV. TESTS OF ENERGY METER ACCURACY ON
with a resistive load supplied by a single-phase DISTORTED NETWORKS
AC voltage generator through a bridge (resistive In this section an approval of the results of the
network). theoretical investigations is given. Two kinds of
Regarding Fig. A3 a dominant nonlinear load is tests were carried out: the first one was a
considered. The result is, that the fundamental systematic procedure with different harmonic
power received by the load includes the distortions and different harmonic powers. In the
harmonic power (generated by the nonlinear second one on-site test measurements were
load) as well. implemented as actual signals.
Fig. A5 of the Appendix shows a non-dominant In both test series the equipment used to supply
nonlinear consumer. The 3rd harmonic voltage the energy meters was an OMICRON relay test
distortion is determined by another nonlinear generator used in energy meter test mode. The
load. Due to this situation, the originally 3rd signals generated with OMICRON were
harmonic generator load will consume 3rd observed and checked by TRANSANAL-16
harmonic power from the network, and this will multichannel measuring equipment. (See Fig.1.)
be converted to useful energy on the DC-side.
The 5th harmonic current is not compensated,
therefore the 5th harmonic power of the nonlinear
load remains negative.
Therefore the consumed fundamental frequency Fig. 1. Test arrangement
power will be less than without the 3 rd harmonic
compensation. In this case the positive consumed A) Settings for the systematic sensitivity
power is the quantity that should be considered analysis
Fundamental frequency


PCP Re U h I h if Re U h I h 0 Voltage: single phase or symmetric three-phase,
h 1 nominal values for the meters: 230V or 100V
to calculate the consumed energy. The positive Current: 0.5x In, e.g. 0.5A or 2.5A
consumed power is the sum of the positive Power factor: tg = 0.2 and 0.4
harmonic powers: Harmonic content
This consumed power (energy) definition Voltage distortion: 0%, 5% for the actual
includes the additional harmonic losses, caused harmonic
by the nonlinear loads of the network, as well as Current distortion: 0%, 25%, 50%, 100% for the
the consumed harmonic energy that will be actual harmonic
converted into useful energy on the load-side. Phase shift between harmonic voltage and
Fig. A2, A4 and A6 show the fundamental and current: 0, 180, 90
harmonic power flows in case of the initial Phase shift between the initial phases of the
situation and in case of dominant and non- fundamental and harmonic voltage: 0, 45.
dominant nonlinear loads. Harmonic orders for voltage and current
simultaneously: one of the 3, 5, 13, 23 orders.
III. CONCLUSIONS OF THE THEORETICAL One set of measurements is carried out using one
INVESTIGATIONS
harmonic order.
1. The watt-hour meters should measure the
positive consumed power including the
harmonic power as well. B) Investigations using real measured
2. Instead of the distortion power the harmonic waveforms
current distortion should be introduced as the The second type of measurements have been
base of a penalty factor to be introduced

3
carried out applying distorted voltage and current is measured correctly. From the measured values
waveforms to the OMICRON generator it can be observed that the harmonic reactive
according to the spectra of previously on-site energy is not measured at all. It can be stated that
recorded signals. These measurements however the reactive energy is measured correctly in case
involved only those four meters that turned out to of all investigated harmonics.
be the most accurate during the above-mentioned
sensitivity investigations. Type F: From the measured values it can be
The waveforms were obtained from data observed that the harmonic reactive energy is not
recorded at a big LV consumer supplied from measured at all. It can be stated that the reactive
MV. energy is measured correctly in case of all
investigated harmonics. The active energy
V. CLASSIFICATION OF THE WATT-HOUR measurement can be called inaccurate only in
METERS BASED ON THE SYSTEMATIC case of the 23rd harmonics. Here the fundamental
SENSITIVITY ANALYSIS
frequency reactive energy is measured as well,
Type A: This meter measures in the presence but with a higher error than at harmonics of
of harmonic distortion practically in every case lower order.
both active and reactive energy inaccurate.
Type G: The active energy measurement is
Type B: Measures reactive energy falsely in correct in all cases, at every harmonic order. The
the presence of 23rd harmonics, and the active reactive energy measurement is incorrect in all
energy measurement in this case is less accurate cases, at every harmonic order. Apparently the
compared to the other cases. Having harmonic reactive energy measuring algorithm is faulty.
loads with harmonic order less than 23rd the
active energy measurement is correct, while from VI. SPECTRA OF THE APPLIED VOLTAGE AND
the reactive energy measurements one can CURRENT WAVEFORMS IN CASE OF REAL,
PRE-RECORDED SIGNALS ALONG WITH THE
conclude that this meter is programmed not to MEASURED ENERGY VALUES
measure harmonic reactive energy. The presence
of harmonic reactive energy has in some cases Remarkable errors can be expected in cases of
strong influence on the measured reactive energy. highly distorted current and voltage signals of
Setting harmonic reactive energy to zero leads to LV loads, depending on the level of distortion.
an accurate measurement of reactive energy. The power measurement error is further
increased if the voltage from which the
Type C: The active energy measurement was synchronizing signal is obtained, has more zero-
correct in all investigated cases. From the crossings due to its harmonic content.
columns containing greater reactive energy The distortion of the signals in the example can
values it can be seen that the meter is not be considered as typical at LV. The four best
supposed to measure harmonic reactive energy. meters according to the systematic analysis
However, in the columns containing smaller Q measured the active energy with a negative error
values the error is between 5-10 %. Setting of 1-1.5 % due to the distortion, compared to the
harmonic reactive energy to zero leads to an values measured in mere fundamental frequency
accurate measurement of reactive energy. conditions.
The reactive energy measurement showed a little
Type D: In the presence of 3rd and 5th error only in case of the meter type D, all other
harmonics the active energy measurement was meters reading values were equal to those at the
correct, but not in the presence of 13 th and 23rd fundamental frequency case.
harmonics. The harmonic reactive energy is not
measured correctly. VII. CONCLUSIONS ARISING FROM THE
MEASUREMENTS
Type E: The active energy measurement was
correct in all cases except the one with 23rd The accuracy of the energy measurement in case
harmonics. Here the harmonic active energy is of distorted signals can change depending on the
not measured, but the fundamental active energy level of distortion and the harmonic frequency.

4
The measurement error will increase if the nonlinear load it would be useful to involve
amplitude and frequency of the distorting in the measurements the current distortion
harmonic signal increases. and penalize above a certain level. Of course,
The utility companies are vitally concerned by in such a case the harmonic content of the
the harmonic distortion of dominant nonlinear current caused by an individual load has to be
loads. The energy measured at the consumer is determined with great certainty.
less than the energy computed from the
fundamental frequency signals, the difference is IX. REFERENCES
equal to the harmonic energy loss in the network. [1] IEC 61036:1996+A1 2000, Alternating Current Watthour meters for
However the generators cover this loss, and the active energy (Classes 1 and 2)
[2] P.S. Filipski and P.W. Labaj: Evaluation of Reactive Power Meters
distributing company has to pay for it at the HV in the Presence of High Harmonic Distortion, IEEE Trans. on Power
revenue metering points. Delivery, Vol.7, No.4, pp. 1793-1799, Oct. 1992
[3] R. Arsenau, P.S. Filipski: Application of a Three Phase
So regarding the standard in power the utility Nonsinusoidal Calibration System for Testing energy and Demand
company buys the harmonic losses but does not Meters Under Simulated Field Conditions, IEEE. Trans. on Power
Delivery, Vol.3, No.3, pp.874-879, July 1988
sell them to the customer, although he could do [4] D.L. Lubkeman et.al: Automated Testing of Solid-State Watthour
so by charging for positive consumed energy Meters in the Presence of Harmonic Distortion, Proc. of the ICHPS
V, Sept. 23-25, 1992, Atlanta, Georgia, USA, pp.345-351
instead of total energy. The harmonic network [5] M. Depenbrock: The FBD-Method, a Generally Applicable Tool for
loss caused by a dominant nonlinear load differs Analyzing Power Relations, Proc. of the ICHPS V, Sept. 23-25,
1992, Atlanta, Georgia, USA, pp. 135-141
from the fundamental frequency network loss so [6] D.A. Marshall et.al: A Comparative Evaluation of Power Theories,
that the former can be measured at the PCC of Proc. of the ICHPS V, Sept. 23-25, 1992, Atlanta, Georgia, USA, pp.
142-150
the load while the latter cannot. [7] A.M. Dan: Identification of Individual Distorting Loads and
In the case of non-dominant nonlinear consumers Evaluating their Harmonic Emission Level: Method of Mono-
parameter Variation, Proceedings of the 7th IASTED International
the harmonic power can also be positive (see Multi-Conference, Palm Sprins, California, USA, 2003, pp-. 471.
Appendix), which means that the consumer
converts harmonic power to power needed for X. AUTHORS
his own technology. That is why the positive
Univ.Doz. Dr. Andrs Dn (dan@vmt.bme.hu)
consumed energy is recommended to be Dvid Raisz MSc. (raisz@vmt.bme.hu)
considered instead of the total power (see also Budapest University of Technology and Economics
Appendix). Dept. of Electric Power Systems,
The conclusions drawn from the theoretical Power Systems and Environment Group
investigations coincide with those arising from Egry Jozsef u. 18. 1111 Budapest, Hungary
Tel.: (+36 1) 463 3019 , Fax: (+36 1) 463 3013
the laboratory analysis.
XI. APPENDIX
VIII. CONCLUSIONS

1. A solution has to be found, which ensures The harmonic active and reactive power is
both in case of dominant and non-dominant supplied by the generator. The so-called
consumers, that the consumer pays the distortion reactive power is actually proportional
energy-equivalent of the harmonic network to the current distortion.
losses and the consumed harmonic power.
i
The most reasonable solution would be, if the
norm was modified, so that the meters RN = 4
measure the positive consumed energy
UG UL RDC = 40
calculated for all harmonics.
2. As long as the norm does not dispose like
above, it would be useful to prescribe the
proposed measuring algorithm in the tenders. Fig. A1 Initial situation
3. As concerning the reactive energy, the
measurement of the fundamental frequency
UG = 311 V, UL = 283 V,
component of the reactive energy is proposed
PG = 1100 W, PL total = 1000 W, PL 1 = 1000 W, PDC
to be prescribed.
= 1000 W, PN = 100 W, QG = 0.3 Var
4. Concerning the distortion caused by the

5
iG iL
Rectifier RDC = 40
RN = 4
UL
Generator Network Load
UG

PL1 PDC I
CDC = 10 000 F
PG
PN1
Fig. A5 Non-dominant nonlinear load

UG = 239 V, UL = 200 V, THDUL = 14 %


I = 12.5 A, 0o ; 150 Hz
Fig. A2 Power flows in case of the initial situation, zero (3rd harmonic overcompensation)
harmonic power
THDIG = 70 %, THDIL = 93 %
i
RDC = 40
PG = 1161 W , PDC = 1000.7 W
RN = 4
PL 1 = 972 W, PL 3 = + 74 W, PL 5 = -40 W,
PL total = 1000.7 W
UG UL
PN 1 = 189 W, PN 3 = 47 W, PN 5 = 40 W,
CDC = 10 000 F PN total = 282 W

QL 1 = -8 VAr, QL 3 = -4 VAr, DL = 921 VA,


Fig. A3 Dominant nonlinear load DG = 816 VA
(Quantities of load calculated from UL and iL.)
UG = 266 V, UL = 228 V, THDUL = 11 % Rectifier
I (3) = 6 A : -178o I(5) = 1.9 A : 3.4o
I RMS = 8.1 A, THDI = 68 %, Generator Network Load

PG = 1264 W, PDC = 1000 W PL1 PDC


PL 1 = 1084 W, PL 3 = -74 W, PL 5 = -7 W, PG PN1
PL total = 1000 W
PN 1 = 180 W, PN 3 = 74W, PN 5 = 7 W, PLh
PN total = 264 W

QL 1 = -13 Var, QL 3 = 0.03 Var


DL = 751 VA, DG = 859 VA, DN = 0 VA
Fig. A6 Power flows in case of a non-dominant nonlinear
load (Positive harmonic power)
Rectifier
Generator Network Load

PL1 PDC
PG
PN1 PLh
PNh

Fig. A4 Power flows in case of a dominant nonlinear load


(Negative harmonic power)

You might also like