Professional Documents
Culture Documents
Test Report Bay 101 Trafo-1 Bcpu
Test Report Bay 101 Trafo-1 Bcpu
Test Report Bay 101 Trafo-1 Bcpu
PROTECTION RELAY
Firm. V04.93.01
Aux. Volts : 110 VDC
Ver.
P.Set : V04.93.01
Gateway : 20.0.14.100
TESTING KIT :
Make : Doble Serial
No. : 120501561
Model : F6150
Date : 10/02/2017
Current
Phase Primary Current read on relay display
injected
injected In A
(Amps)
IR IY IB 3I0
Apply voltage in the relay as per the table below. Observe the reading
on the relay display.
Voltage
Phase
applied Primary Voltage read on the relay Display in Kv
applied
(Volts)
VR VY VB VRY VYB VBR VO
R-Y-B 110 76 76 76 132 132 132 0
Paramete
Description Setting
r
1507 51 Pickup 0.5 Amp
1508 51 Time Delay 0.20 sec
1504 50-1 Pickup oo Amp
1505 50-1Time Delay oo sec
1502 50-2 Pickup oo Amp
1503 50-2 Time Delay oo sec
1607 51N Pickup 0.1 Amp
1608 51N Time Delay 0.25 sec
1604 50N-1 Pickup oo Amp
1605 50N-1Time Delay oo sec
1602 50N-2 Pickup oo Amp
1603 50sN-2 Time Delay oo sec
Pickup Current in
Operating Time in millisec
Amp
Phase
Injected Calculated Observed
Setting Setting
2*I 5*I 2*I 5*I 2*I 5*I
R-E 0.1 0.2 0.5 0250 2507 1069 2480 1050
0250 2507 1069 2490 1050
Y-E 0.1 0.2 0.5
0250 2507 1069 2480 1040
B-E 0.1 0.2 0.5
Apply 3-Phase voltage only and then remove any single phase
voltage. Check for fuse fail indication.
Apply 3-Phase voltage and current above 50% rated and then
remove any single phase voltage. Check for fuse fail.
Result:
Fuse Failure Monitor Function checked: OK / NOT OK
P.T selection relays 75AB and 75CD checked and found healthy :
OK / NOT OK