REL 301-302

The REL 301-302 model supports:

- 3 mho trip zone for the phase loops and 3 mho zones for the ground loops
- A pilot zone for phase and a pilot zone for ground (available only in the ABB REL 302)
- directional element (phase, ground and negative sequence element)
- the phase overcurrent elements (3 time defined elements (Ioc))
- the ground overcurrent elements(one inverse characteristic element(Toc), 3 time defined elements (Ioc))
- a phase undervoltage element (3 phases)

Unsupported features:

- zone extension
nd
- overcurrent elements directional characteristic for the 2 zone phase torque control
- automatic reclosing and synchronizing feature
- breaker failure protection
- out of step logic
- directional minimum sensitivity in volt-amperes (a minimum sensitivity of 0.1 is present)

Data entry notes:

- inside the PF model the zone 1 and zone 2 directional setting can be forward or reverse. To be
consistent with the device characteristic only the forward setting must be used