Voltage Scheme Checks.: Vline Vmin, VBB Vdead, Fmin FBB Fmax Vline Vdead, VBB Vdead
Voltage Scheme Checks.: Vline Vmin, VBB Vdead, Fmin FBB Fmax Vline Vdead, VBB Vdead
We dont have w VT , As VTs are not provided for monitoring the Bus Voltages, a
separate LV scheme (Voltage Selection Scheme) is utilized to display BB voltages in
the HMI/SCADA and also for making proper selection of bus bar voltage by ss use of
line VTs secondary for sync closing.
The Dead bus and Dead line connection are special cases. In this case, connection
is made depending on the configuration under the following conditions:
dead line
Vb.b> Vmin , VLine < V dead , fmin < fbb< fmax
Dead bus :
Vline > vmin , Vbb< Vdead , fmin< fbb< fmax
Dead line dead bus :
Vline < vdead , Vbb < vdead
(whereby the
individual reference voltage depends on the isolator position)
Voltage application If the voltage application is used, the user must set a switching sequence with
the following
components:
Voltage application
Synchronisation
voltage deselection
: 5 V (VT secondary)
Full interlocking, dead line or dead busbar check and synchronizing check using
conventional
(busbar) and incoming (line) voltage, phase angle diff between and frequency diff,
blocking
voltage range, null voltage %age etc. should be possible to preset independently.
Under frequency
load shedding setting and stage selection and time delay for each stage should also
be an