GENERAL NOTES
TABLE-2 1. ALL DIMENSIONS ARE IN MILLIMETRE (UNO)
LOCK NUT REFER NOTE: 3 OF 2. FOR CONCRETE GENERAL NOTES AND CONCRETE SURFACE PROTECTION
ENGINEERING NOTES BOLT TYPE APPLICATION DETAILS REFER DRAWING NO D-000-5310-210.
STANDARD WASHER LOCK NUT
(TYP.) 3. FOR STRUCTURAL STEEL GENERAL NOTES REFER DRAWING NO D-000-5310-220.
BASE PLATE STANDARD WASHER STANDARD WASHER
A A

(PROJECTION)

(PROJECTION)

(PROJECTION)
TYPE-1 ALL PLANT EQUIPMENT INCLUDING VERTICAL VESSEL, HORIZONTAL DRUMS,

(THREAD)

(THREAD)

(THREAD)
'Z2'

'Z2'

'Z2'
TOP OF GROUT TOP OF GROUT TOP OF GROUT EXCHANGERS, PUMPS, STEEL STRUCTURES, PLATFORMS AND WHERE SIGNIFICANT

'C'

'C'

'C'
'P'

'P'

'P'
TOP OF TOP OF TOP OF OR REPETITIVE TENSION LOADS ARE ENVISAGED.
STRUCTURAL STRUCTURAL STRUCTURAL
CONCRETE CONCRETE CONCRETE TYPE-2 ALL AS FOR TYPE 1 AND 3 WHERE SIGNIFICANT OR REPETITIVE TENSION LOADS
ARE ENVISAGED, BUT LOCATION TOLERANCES ARE CONTROLLED BY USING ROBUST
PRECISE TEMPLATES TO EQUIPMENT ITEMS SUPPLIED BY EQUIPMENT SUPPLIER
WHERE NECESSARY, FOR LARGE BOLT ASSEMBLIES. FOR VERTICAL VESSELS &

'G'
B COLUMNS, BOX TYPE TEMPLATES SHALL BE OBTAINED FROM THE EQUIPMENT B
SUPPLIER.

(BOLT LENGTH)

(BOLT LENGTH)

(BOLT LENGTH)
OF CONSTRUCTION
NOTE)
'A' TYPE-3 MINOR EQUIPMENT, ACCESS PLATFORM, CROSSOVER, MINOR PIPE SUPPORTS, STAIRS,

'L'

'L'

'L'
'A' LADDERS AND HANDRAIL ETC. WHERE NO TENSION IN BOLT IS DEVELOPED.
(BOLT DIAMETER)
(BOLT DIAMETER)

'E'

'E'

'E'
TYPE-4 & 5 FOR SECURING HEAVY EQUIPMENT SUPPORTED ON OVERSIZE OR MULTIPLE BASE
PLATES WHERE MAXIMUM TOLERANCE IN BOLT POSITION IS NECESSARY TO
C FACILITATE INSTALLATION. C
'Eg' N.B.- TYPE 4 & 5 SHALL NOT BE USED IN CONFINED AREA SUCH AS PIERS.
'Eg' LEGEND
'Eg'
ANCHOR BOLT DESIGNATION (TYPICAL)
TABLE-3
(THREAD)

(THREAD)

(THREAD)
4 - M20 - T2 - 2 - 675 - 150
'F'

'F'

'F'
CHECK FOR ULTIMATE CAPACITY: CHECK FOR WORKING CAPACITY:
'Z1'

'Z1'

'Z1'
ANCHOR BOLT PROJECTION ('P')
D TOTAL LENGTH OF BOLT ('L') D
FOR COMBINED SHEAR & TENSION, BOLTS FOR COMBINED SHEAR & TENSION,BOLTS SHALL BE
HEXAGONAL NUT HEXAGONAL NUT HEXAGONAL NUT SHALL BE CHECKED FOR ULTIMATE CHECKED FOR WORKING LOAD DESIGN AS BELOW: NUMBER OF NUTS
(TACK WELDED WITH (TACK WELDED WITH (TACK WELDED WITH STRENGTH DESIGN AS BELOW: TYPE OF BOLT
ANCHOR BOLT) ANCHOR BOLT) ANCHOR BOLT)
Fus Fut Fs Ft DIA. OF ANCHOR BOLT
+ 1.2 + 1.0
ANCHOR BOLT DETAIL ANCHOR BOLT DETAIL ANCHOR BOLT DETAIL Pus Put Ps Pt NUMBER OF ANCHOR BOLTS

E
TYPE-1 TYPE-2 TYPE-3 WHERE Fus = APPLIED ULTIMATE SHEAR WHERE Fs = APPLIED WORKING SHEAR
E
Pus = ULTIMATE SHEAR CAPACITY. Ps = ALLOWABLE SHEAR CAPACITY.
(NTS) (NTS) (NTS)
Fut = APPLIED ULTIMATE TENSION Ft = APPLIED WORKING TENSION
Put = ULTIMATE TENSION CAPACITY Pt = ALLOWABLE TENSION CAPACITY

TO ARRIVE AT WORKING CAPACITY, FACTOR OF 1.5


LOCK NUT SHALL BE USED (WORKING CAPACITY = ULTIMATE
CAPACITY/1.5).
F STANDARD WASHER LOCK NUT F
WORKING CAPACITY CAN BE INCREASED BY

(PROJECTION)
BASE PLATE STANDARD WASHER 25%%%, WHEN STRESSES ARE PRODUCED BY WIND

(THREAD)
'Z2'
TOP OF GROUT LOADING, ACTING ALONE OR IN COMBINATION WITH

'C'
TOP OF GROUT

'P'
DEAD AND LIVE LOADS.
TOP OF TOP OF
STRUCTURAL STRUCTURAL
CONCRETE CONCRETE

10 ABOVE TOP OF
G G

ROUGH CONCRETE
CS PIPE SLEEVE
'A' GALVANIZED (ASTM A36) SPECIAL NOTES:

(BOLT LENGTH)
(BOLT DIAMETER) 'A'
(BOLT DIAMETER)
1. READ THIS DRAWING ALONG WITH DRAWING NO D-000-5310-207.

'L'
EDGE TO BE ROUGHENED 'Eg'
AND CLEANED BEFORE
NOMINAL 2. FOR DETAIL OF BOLT PROJECTION IN CASE THE ANCHOR CHAIR IS USED,

G1
'E'
INSTALLATION
PIPE DIA. 'D'
75 (MIN.)
REFER DRAWING NO D-000-5310-207.
H H
TO BE FILLED
WITH GROUT
3. AS PER CLAUSE 3.6.6 OF SPECIFICATION FOR PRESSURE VESSELS (COLUMNS,
(STRENGTH SAME AS BOLT SLEEVE TO BE
TACK WELDED WITH
VESSELS, REACTORS, HEAT EXCHANGERS & FILTERS) S-000-5351-001, THE
PARENT CONCRETE)
ANCHOR PLATE
1
(THREAD)

4. THE BOLT MATERIAL SHALL BE PRIMARILY AS INDICATED IN NOTES FOR


'F'

'Z1'

J MATERIAL SPECIFICATION OF DRAWING NO D-000-5310-207. J


'T'

5. FOR SPECIAL REQUIREMENT FOR EQUIPMENT AS PER MECHANICAL VENDOR


HEXAGONAL NUT (TO BE
TACK WELDED WITH
HEXAGONAL NUT (TACK
WELDED WITH ANCHOR BOLT BOTTOM SQUARE THE FOLLOWING BOLT MATERIAL CAN BE USED :
ANCHOR BOLT) AND ANCHOR PLATE 'B'
ANCHOR PLATE a) ANCHOR BOLT MATERIAL - ASTM A193, GRADE B7
AT TWO POINTS)
= = b) HEXAGONAL NUT MATERIAL - ASTM A194, GRADE 2H
K
C) WASHER MATERIAL - ASTM F436M K
ANCHOR BOLT DETAIL ANCHOR BOLT DETAIL THE ABOVE SPECIAL REQUIREMENT SHALL BE INDICATED IN THE RESPECTIVE
TYPE-4 TYPE-5 EQUIPMENT FOUNDATION CONSTRUCTION DRAWING.
(NTS) (NTS) 6. THE TABLE-1 IS APPLICABLE FOR BOTH THE MATERIAL MENTIONED IN NOTE
4 AND 5 AS ABOVE.
TABLE-1
L L
INDIVIDUAL BOLT CAPACITY FOR GROUP OF 4 BOLTS

ULTIMATE STRENGTH WITHOUT


SUPPLEMENTARY REINFORCEMENT
ULTIMATE STRENGTH WITH
SUPPLEMENTARY REINFORCEMENT
ULTIMATE STRENGTH WITH
SUPPLEMENTARY REINFORCEMENT
(FOR PRESSURE VESSELS - THREADED
MIN. BOLT
EMBEDMENT SLEEVE
MIN. EDGE
DISTANCE
MIN.
C/C SPACING
ANCHOR
BOLT
MINIMUM
PEDESTAL
*SUPPLEMENTARY
REINFORCEMENT
FOR CONSTRUCTION
COLUMNS, VESSELS, REACTORS, LENGTH INSIDE DETAIL FROM CENTRE OF BOLT LENGTH SIZE IN PEDESTAL
HEAT EXCHANGERS & FILTERS) CONCRETE OF BOLT
M (REFER SPECIAL NOTE 3) M
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 D-000-5310-207 STANDARD DRAWING FOR ANCHOR BOLT DETAILS
D-000-5310-220 STRUCTURAL STEEL GENERAL NOTES
NOMINAL EFFECTIVE TENSION SHEAR TENSION SHEAR TENSION SHEAR FROM ABOVE TOTAL TYPE- TYPE- BOTTOM SQUARE SLEEVE SLEEVE SLEEVE TYPE- TYPE- TYPE- TYPE- TYPE- TYPE- TYPE- TYPE- MAIN BAR LINKS D-000-5310-210 CONCRETE GENERAL NOTES AND CONCRETE SURFACE
BOLT DIA. TENSILE CAPACITY CAPACITY CAPACITY CAPACITY CAPACITY CAPACITY TOP OF BASE THREADED 1, 2, 3 ANCHOR PLATE DIA. LENGTH LENGTH 1, 2, 3 1, 2, 3 1, 2, 3 1, 2, 3 PROTECTION DETAILS
& SHEAR NUT PLATE LENGTH 4&5 TYPE-5 TYPE-1 & 5 TYPE-1 TYPE-5 4&5 4&5 4&5 4&5 DRAWING NO. TITLE
(SINGLE (DOUBLE REFERENCE DRAWINGS
AREA
NUT) NUT)
N N
1 REISSUED FOR CONSTRUCTION HIM KSD/SMR PK/SM SL/MKG 02/09/2014
A -- Put Pus Put Pus Put Pus 'Z1' 'Z2' 'C' 'F' 'E' 'B' 'T' 'D' 'G' G1 'Eg' 'S' 'L' 'X' 'Y' 'X' 'Y' -- -- 0 ISSUED FOR CONSTRUCTION VDM KSD/SMR PK/SM SL/MKG 11/04/2014
B ISSUED FOR APPROVAL CAJ KSD/SMR PK/SM SL/MKG 14/03/2014
mm kN kN kN kN kN kN mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm -- --
A ISSUED FOR APPROVAL HIM KSD/SMR PK/SM SL/MKG 07/03/2014
-- -- -- -- -- -- -- ENGG. PROJ.
M16 157 11.80 3.60 -- -- -- -- 25 45 85 30 -- 250 -- 100 -- 80 -- 365 -- -- 250 250 REV DESCRIPTION DRAWN CK'D APPD. APPD. DATE
ALL RIGHT RESERVED THIS DOCUMENT IS THE PROPERTY OF OMAN REFINERIES AND PETROCHEMICALS COMPANY LLC
M20 245 13.60 4.40 -- -- -- -- 30 55 95 35 -- 300 -- -- -- -- -- -- 100 -- 80 -- 430 -- -- 300 300 -- -- AND CONTAINS INFORMATION WHICH IS PROPRIETARY, THIS INFORMATION IS TO BE HELD IN CONFIDENCE.
P NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE P
M16 157 12.70 4.10 26.00 24.50 26.00 18.80 40 45 105 45 375 -- 80 16 50 100 385 100 -- 80 -- 530 -- 300 300 -- -- 4-T16 2-2L-T10 WITHOUT THE PRIOR WRITTEN CONSENT OF OMAN REFINERIES AND PETROCHEMICALS COMPANY LLC

M20 245 12.70 4.10 32.70 29.70 32.70 29.40 45 55 115 50 425 -- 105 16 75 150 435 100 -- 80 -- 595 -- 300 300 -- -- 4-T16 2-2L-T10 Oman Refineries and Petrochemicals Company LLC
M24 353 17.20 5.50 47.30 44.40 47.30 42.40 50 65 125 55 500 -- 105 20 75 150 510 120 -- 100 -- 685 -- 350 350 -- -- 8-T16 2-3L-T10

M30 561 23.50 7.60 76.00 59.30 76.00 59.30 55 80 140 60 600 -- 130 20 100 200 610 150 -- 120 -- 805 -- 450 450 -- -- 12-T16 2-4L-T10
Q SOHAR REFINERY IMPROVEMENT PROJECT Q
M36 817 31.60 10.20 109.50 59.30 109.50 59.30 70 90 150 75 700 -- 190 25 150 200 710 180 -- 150 -- 930 -- 525 525 -- -- 12-T16 2-4L-T10
TITLE :
M42 1104 39.10 12.70 148.00 59.30 148.00 59.30 75 105 165 80 800 -- 190 25 150 250 810 210 -- 170 -- 1050 -- 600 600 -- -- 12-T16 2-4L-T10 STANDARD DRAWING
M48 1465 48.70 15.70 193.20 74.20 193.20 74.20 85 120 180 90 900 -- 190 30 150 250 910 240 -- 200 -- 1175 -- 700 700 -- -- 16-T16 2-5L-T10 FOR ANCHOR BOLT DETAILS
D-000-5310-208

M56 2022 60.80 19.70 261.80 89.00 261.80 89.00 95 140 200 100 1000 -- 260 30 200 300 1010 280 -- 230 -- 1305 -- 800 800 -- -- 16-T16 2-6L-T10
DATE: PREP'D: CK'D: APP'D:
R M64 2680 73.80 24.00 340.60 89.00 340.60 89.00 110 155 215 115 1100 -- 260 40 200 300 1110 320 -- 260 -- 1435 -- 900 900 -- -- 16-T16 2-6L-T10 07/03/2014 HIM KSD/SMR PK/SM R
UNIT NAME & UNIT NUMBER: JOB NUMBER: SCALE: SH'T NO:
* MINIMUM REINFORCEMENT (MAIN BAR AND LINKS) IN PEDESTAL TO ACHIEVE COMMON-0000 120476/JI-2022 NTS 1 OF 1
DESIRED ANCHOR BOLT CAPACITY. PCWBS: DRAWING NUMBER: SIZE REV:
0000 D-000-5310-208 A1 1