====================================================================== <Details> An installed CPU Bus unit does not match the Special I/O Unit registered in the I/O table. ---------------------------------------------------------------------- <Countermeasure> 1. Check the unit No. stored in the CPU Bus Unit Setting Error Flag. - The errant unit number is displayed at the bottom of screen. 2. Mount the correct unit and change the registered I/O table. - Change the registered I/O table after mounting the correct unit. (If an I/O table does not need to be edited (reserving words and setting start address), change the registered I/O table. Select "I/O table" in the Project Workspace with working online in PROGRAM mode. Then, select "Options" - "Create" in the PLC IO table window.)
- Refer to the following manual for details on creating an I/O
Table. <Notes> - Always turn OFF the power supply to the PLC before replacing Units, Inner Board, fuse, battery, wiring, or connecting cable. ---------------------------------------------------------------------- Remarks: - If an I/O table needs to be edited, transfer it to the PLC after editing it. (Refer to the following manual for details on editing and transferring an I/O table.) ---------------------------------------------------------------------- <Reference> Manual/ CX-Programmer OPERATION MANUAL MANUAL No./ W446-E1-XX Section/ I/O Table Component ======================================================================