Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

OF5-01

TEMPERATURE DEPENDENCY OF WAVE PROPAGATION VELOCITY


IN MV POWER CABLE
1* 1 2 2
Yan LI , Peter A. A. F. Wouters , Paul Wagenaars , Peter C. J. M. van der Wielen and
1,2
E. Fred Steennis
1
Eindhoven University of Technology, P.O. Box 513, 5600 MB Eindhoven, Netherlands
2
DNV KEMA Energy & Sustainability, P.O. Box 9035, Arnhem 6800 ET, Netherlands
*Email: <y.li.4@tue.nl>

Abstract: Propagation velocity of high frequency signals, e.g. from partial discharge, is a
vital parameter for time domain power cable diagnostic techniques. The propagation
velocity is mainly dependent on the permittivity of the insulation material, which can be
affected by external parameters like temperature or water ingress. This paper focuses on
the influence of temperature on the propagation velocity in medium voltage (MV) cables.
Laboratory scale tests are performed for both PILC and XLPE cable. Test results show
that the high frequency signal propagation velocity for XLPE will increase with the
temperature rise while PILC has opposite behaviour. The variation of propagation velocity
of XLPE is confirmed by data of a power cable subjected to strong load cycling monitored
over eight months.

1 INTRODUCTION power cable via 50 coaxial cable. The injected


pulse and its reflections are recorded by an
In time domain reflectometry measurements, e.g. oscilloscope. Heating is accomplished by a 10 kW
in partial discharge diagnostic techniques for DC current source, capable of generating 600 A at
power cable [1-3], propagation velocity should be a maximum voltage of 16 V. It is connected to the
accurately known for precise defect location. On conductor from the second segment to the last
one hand, the propagation velocity can be affected cable segment.
by temperature. On the other hand, information on
variability in propagation velocity informs on
changing conditions as temperature variation by
e.g. cable loading or insulation ageing.

Two sets of laboratory scale test are presented to


evaluate the temperature effect on wave
propagation velocity in both XLPE (Section 2) and
PILC cables (Section 3). The effect is compared
after translating measured temperature to
temperature inside the insulation (Section 4). In
addition, propagation time data are extracted from
Smart Cable Guard systems [4] installed on live Figure 1: Test circuit for TDR on heated XLPE
cable connections with XLPE insulation (Section cable; the connector numbers correspond to the
5). The field data, with variation recorded over a connector types illustrated in Figure 2.
year is then compared with the load profile. The
observed temperature effect on propagation
velocity will be briefly further discussed in Section
6.

2 LABORATORY TEST ON XLPE CABLE

2.1 Test circuit


Six segments of 12/20kV XLPE single core
(aluminium) cable are connected to form the test
circuit. Each piece is about 12 m resulting in a
cable circuit of about 72 m. The test circuit is open
at both sides. Pulse signals are injected into the
cable via one open end and reflections are
recorded at the same end (time domain (1) (2) (3)
reflectometry, TDR). Due to space limitation, the
test circuit is half inside the test room and half Figure 2: Connector types applied for combining
outside in open air. Figure 1 illustrates the test XLPE cable segments; numbers correspond with
circuit. An 8 ns wide pulse is injected into the the connectors indicated in Figure 1

1861
OF5-01

Temperature sensors are attached on the surface


of the cable outer jacket to measure the outer 0.1 14.4C,12.0C
sheath temperatures of indoor and outdoor cables.
20.4C,17.0C
These sensors are shown in Figure 1 as dots and 0.05
27.6C,21.9C

Amplitude [V]
labeled as T1 and T2. Letters A-G indicate the 0
reflection points of TDR measurements shown 37.3C,27.0C
later in Figure 3. Figure 2 shows the connector -0.05 48.7C,31.8C
types. Connector type 3 was improvised for the -0.1
present measurements. The cable earth screen
connections were realized with short wires parallel -0.15
to the connectors for all types. -0.2
0.95 1 1.05 1.1
2.2 Test results Time [s]

After heating for about 3 hours, the cable outer


(b)
jacket temperature has increased from 9 C to
48 C (indoor) and from 8 C to 30 C (outdoor).
TDR signals are recorded continuously. Results at 0.6
different temperatures are shown in Figure 3. All
reflected signals are labelled with symbols to 0.4
identify the reflections coming from the transition

Amplitude [V]
between coaxial cable and power cable (A), the 5
cable connectors (B-F) and the open far end (G). 0.2 14.4C,12.0C
Reflection C (from connector type 1), E (from 20.4C,17.0C
connector type 2) and G (from open end) are 0 27.6C,21.9C
zoomed in and shown in Figure 4. It is qualitatively 37.3C,27.0C
observed that with the increase of temperature, the 48.7C,31.8C
propagation time decreases, indicating that the -0.2
propagation velocity has increased. 1.3 1.35 1.4 1.45 1.5
Time [s]

(c)
10 10.8C,9.0C
8 20.8C,17.4C Figure 4: (a) depicts reflection C from connector 1;

30.9 C,23.4 C (b) shows reflection E from connector 2 and (c)
Amplitude [V]

6 illustrates reflection G from open end


40.8C,28.8C
4 48.8C,32.1C
C 2.3 Analysis
2 B F
DE
In order to analyse the measured result, two issues
0
A
have to be addressed. The first issue is the
G
-2 temperature correction, since the temperature
0 0.5 1 1.5 2 sensors are attached on the outer jacket of the
Time [s]
XLPE cable. The propagation velocity is mainly
determined by permittivity of the insulation.
Figure 3: Reflection patterns at different Therefore, the measured jacket temperature will be
temperatures; the legend indicates first the indoor converted to the temperature at the midpoint of the
temperature, next the outdoor temperature, letters insulation. The second issue concerns the
A-G correspond to the ones in Figure 1 quantitative calculation of the pattern shift at
different temperatures.

0.8 14.4C,12.0C Insulation temperature conversion: A thermal


20.4C,17.0C ladder network can be used to model the
0.6
27.6C,21.9C temperature distribution in radial direction of the
Amplitude [V]

0.4 37.3C,27.0C cable [6]. Each layer of cable can be modelled by a


thermal resistor and a thermal capacitor. The heat
48.7C,31.8C
0.2 source can be represented as a current source.
0 According to the thermal ladder network,
logarithmic temperature distribution across the
-0.2 dielectric material is assumed. Based on this
model, the time response of the temperature in the
0.75 0.76 0.77 0.78 0.79 0.8
Time [s] middle of dielectric material is shown in Figure 5.
The measured temperature of the outdoor cable
(a) jacket is then converted to outdoor temperature at

1862
OF5-01

midpoint of the insulation, Table 1. The outdoor reflection from the far end. This might be caused
temperature is used since the propagation time by the indoor and outdoor temperature difference
between the connector 1 and open far end will be and lower signal to noise ratio. Directly past this
used for analysis in order to exclude the indoor peak, structures arise which travelled additional
and outdoor temperature difference. Tjx is the length along a not heated part. Later also the
jacket temperature of the XLPE cable, and Tdx is heated part is included resulting in a steeper time
the temperature at the middle of insulation of the shift again.
XLPE cable; t is the heating time according to
Figure 5.
0 12
1
-2 2 10
15
3
-4 8
4

time delay [ns]

amplitude [V]
-6 6
10 -8 4
T [C]

-10 2

5 -12 0

-14 -2

-16 -4
0 0.5 1 1.5 2 2.5 3 3.5
0 time [s]
0 0.5 1 1.5 2 2.5 3
t [h]
Figure 6: Time shift of reflection patterns of XLPE
Figure 5: Derived temperature difference between cable at different temperatures
the midpoint of XLPE insulation and the outer
jacket surface for single core XLPE cable 3 LABORATORY TEST ON PILC CABLE

Table 1: Insulation temperature for XLPE; the 3.1 Test circuit


outer jacket temperature Tjx is converted to the
The laboratory scale cable setup at DNV KEMA is
midpoint value Tdx of the insulation reached at time
utilized for PILC cable test. The setup consists of
t (see Figure 5)
50 m three core XLPE cable and 70 m three core
PILC cable (outdoor). 100 ns wide pulse is injected
Ref. 1 2 3 4 into the cable. Due to the setup limitation, the
Tjx (C) 12.0 17.0 21.9 27.0 31.8
current source for heating (same as for XLPE test)
is connected to the earth screen of cables, which is
t (h) 0.27 0.60 1.15 2.24 5.47 lead for PILC and copper for XLPE. Figure 7
shows the test setup. Since the resistivity of lead is
Tdx (C) 23.6 30.3 35.3 40.4 45.2
much higher than copper, heating power
Quantitative time shift: The minimum square distributes mainly along the PILC cable. Due to
error (MSE) [5] detection with time window is power source limitation, about 130 A current could
applied to get the time shift between two patterns. be loaded to the cable. Two temperature sensors
When time shift between pattern P (reference) and are attached on the surface of the PILC and the
Q (at elevated temperature) is calculated, a time XLPE cable separately.
window (length t) taken from the complete record
will be shifted along pattern Q back and forth to
find the best match in pattern P, i.e. where the
minimum error occurs. The time window length is
chosen to be 1500 ns to get a reasonable flat
result excluding error from noise. Figure 6 shows
the calculated time shift along the pattern between
heated cable and reference cable. The numbers in
the legend correspond to the patterns in Table 1.
The pattern shifts more as the temperature
difference increases. The shift becomes most
nd rd
apparent as from the 2 3 reflection (at 700 ns,
B-C in Figure 3). This is where the heated part of
the cable begins. The time delay increases after
each clear reflection from joint due to longer
propagation distance. After the steep part the time
delay slowly increases around and just after the Figure 7: Test setup for TDR on heated PILC
cable

1863
OF5-01

3.2 Test results


1
Approximately 3 hours heating increased the
temperature of the PILC cable with about 25 C 0.8
and the XLPE with about 5 C. The measured

Amplitude [V]
0.6 PILC:23.5C XLPE:24.0C
result is shown in Figure 8. In the pattern, the
injected pulse is located around 2.1 s. The first 0.4
PILC:28.1C XLPE:24.9C
reflection near 2.6 s is from the coaxial cable PILC:33.1C XLPE:25.8C
connection to the power cable; the reflection 0.2 PILC:38.2C XLPE:26.1C
around 4.1 s arises from the transition joint, and PILC:43.0C XLPE:27.3C
the reflection around 5 s from the open end. The 0
PILC:48.1C XLPE:28.8C
later reflections are secondary or higher order 4.85 4.9 4.95 5 5.05 5.1 5.15
reflections. The transition joint reflection and the far Time [s]
end reflection are depicted enlarged in Figure 9. It
is observed that with the increase of temperature, (b)
the propagation time increases, indicating a lower
propagation velocity, which is opposite to the Figure 9: (a) enlargement of reflection from PILC
observations for XLPE insulation. to XLPE transition joint; (b) enlargement of
reflection from open end
6 PILC:23.5C XLPE:24.0C
3.3 Analysis
PILC:28.1C XLPE:24.9C

4

PILC:33.1 C XLPE:25.8 C Insulation temperature conversion: Applying a
PILC:38.2C XLPE:26.1C similar approach as for the XLPE cable heating
PILC:43.0C XLPE:27.3C test, the temperature difference between the
Amplitude [V]

2
PILC:48.1C XLPE:28.8C insulation midpoint and jacket of PILC cable is
shown in Figure 10. The measured outer jacket
0 temperature for PILC cable is converted to
temperature at the midpoint of the paper insulation
-2 as shown in Table 2.

-4 2.5
0 2 4 6 8 10
Time [s]

2
Figure 8: Reflection patterns at different
temperatures; the legend indicates first the indoor
1.5
temperature, next the outdoor temperature
T [C]

1
PILC:23.5C XLPE:24.0C

PILC:28.1 C XLPE:24.9 C
0 0.5
PILC:33.1C XLPE:25.8C
-0.1 PILC:38.2C XLPE:26.1C
Amplitude [V]

PILC:43.0C XLPE:27.3C
0
-0.2
0 0.5 1 1.5 2 2.5 3
PILC:48.1C XLPE:28.8C t [h]
-0.3
Figure 10: Derived temperature difference
-0.4 between the midpoint of paper insulation and the
-0.5 outer jacket surface for the three-core PILC cable
4.05 4.1 4.15 4.2 4.25
Time [s] Table 2: Middle of insulation temperature for PILC

(a)
Ref. 1 2 3 4 5

Tjp (C) 23.5 28.1 33.1 38.2 43.0 48.1

t(h) 0.08 0.35 0.60 1.05 1.83 3.13

Tdp (C) 25.0 30.1 35.3 40.4 45.2 50.3

Quantitative time shift: The previously described


MSE method is applied to the PILC cable patterns
to find the time shift. The results are shown in

1864
OF5-01

Figure 11 for five measurements. The time shift of the PILC cable is affected more by temperature.
increases with propagation time and temperature Also this figure suggests that the variation is not
difference. The steep rise observed directly after linear and becomes more pronounced at higher
the reflection from the injection cable is caused by temperatures.
the time window beginning to cover the reflection
from the PILC to XLPE transition point, which gives
2.5
a clear shift. The increase in time delay directly -XLPE
after the first reflection is where the heated cable PILC
starts. 2

1.5

time shift [%]


100 10
1
2 1
3
4 0.5
time delay [ns]

amplitude [V]
50 0 0
0 5 10 15 20 25

temperature difference [ C]

Figure 12: Propagation time variation comparison;


the absolute values are indicated
0 -10 5 FIELD DATA
0 2 4 6 8 10
time [s]
Propagation time data from installed Smart Cable
Figure 11: Time shift of reflection patterns of PILC Guard system recorded over a year is compared
cable at different temperatures with load profile data over the same time period.
The propagation time and load of a XLPE cable
st
4 COMPARISON OF THE TEMPERATURE section (4.8 km long with 6 RMUs) from May 1 ,
th
EFFECT OF PILC AND XLPE CABLE 2010 to January 14 2011 is shown in Figure 13. It
shows that though the load does not have a clear
Test results show that the XLPE and PILC cable summer winter cycle, the propagation time is lower
have an opposite temperature effect on at summer time and higher at winter time. This
propagation velocity. With the conversion from indicates a clear ambient temperature variation. On
measured jacket temperature to conductor top of the ambient temperature effect, the load also
temperature, it is possible to compare both cables. influences the propagation time. The peak load
th
For XLPE, the time shift is calculated from around July 9 , 2010 corresponds to a lower
reflection C (from connector 1 in Figure 1) to G propagation time at that period. A weekly trend is
(from open end) utilizing the outdoor part observed. The propagation time variation is
(consistent with the temperature data in Table 1). opposite compared to the load current variation.
For PILC, the time shift is derived from the Besides, the variation within each day is observed.
reflections at both ends of the PILC cable. The The relatively high load on Thursday and Monday
comparison between the XLPE and PILC cables correlates with the relatively large drop in
propagation time variation is shown in Figure 12. propagation time. Further, there is a delay between
The deviations caused by different time window the increase in current and the thermal response.
lengths are indicated in the error bar. The velocity
500 500 12:40
Saturday
Propagation time [s] Load [A]
Load [A]

00:40
0 0 0 0 0
0
1 8: 25:0 0 5: 05:0 1 6: 10:0 0 5: 35:0
28

29

01

03

05

2010 2010 2010 2010


04-06- 13-08- 21-10- 30-12-
6-

6-

7-

7-

7-
-0

-0

-0

-0

-0
s]

10

10

10

10

10

31.7 31.8
Propagation time [

31.6
31.6
31.5

31.4 31.4
28

29

01

03

05

02: 43 05:44 16: 35 10: 40


6-

6-

7-

7-

7-

2010 2010 2010


30-05- -2010 01-10- 28-11-
-0

-0

-0

-0

-0

01-08
10

10

10

10

10

Figure 13: Propagation time and load of XLPE cable for year and week cycle

1865
OF5-01

This thermal response time of typically 3 hours is 9 REFERENCES


more apparent when the cable load starts
compared to when the load is switched off [1] G. M. Hashmi, R. Papazyan, M. Lehtonen:
probably because the temperature rise due to Comparing Wave Propagation Characteristics
higher load is faster than the temperature of MV XLPE Cable and Covered-Conductor
decrease caused by lighter load. It should be noted Overhead Line using Time Domain
that the load profile is not the same over the Reflectometry Technique, 2007 International
complete cable section. The measured current Conference on Electrical Engineering (ICEE
represents the highest loaded part of the section. '07), pp.1-6, 11-12 April 2007
[2] G. M. Hashmi, R. Papazyan, M. Lehtonen:
Unfortunately, at present there is no correlated Determining wave propagation characteristics
PILC data available for propagation time and load of MV XLPE power cable using time domain
current. From the laboratory tests a clearer effect is reflectometry technique, 2009 International
expected here. Conference on Electrical and Electronics
Engineering (ELECO 2009), pp.I-159-I-163, 5-
6 DISCUSSION 8 Nov. 2009
[3] S. Markalous, T. Strehl, C. Herold, T. Leibfried:
The velocity change of the XLPE cable with Enhanced signal processing for conventional
temperature can be attributed to the real part of the and unconventional PD measuring methods:
permittivity of the XLPE. The decrease of velocity Wavelet de-noising, automatic detection
in percentage is in agreement with the decrease algorithms and averaging for arrival time-based
in the measured temperature range [7,8], which is PD location in transformers and power cables,
about 0.7-3% in the temperature range of 20 C to 2008 International Conference on Condition
60 C. For PILC, increases with temperature [9]; Monitoring and Diagnosis (CMD 2008),
however quantitative analyses on the temperature pp.1115-1118, 21-24 April 2008
dependence of in high frequency range is scarce [4] Peter C.J.M. van der Wielen and E. Fred
in literature. Furthermore, it is acknowledged that Steennis: Risk-controlled application of current
the insulation parameters of paper insulation can MV cable feeders in the future by intelligent
vary a lot depending on manufacturer, production continuous diagnostics, in 2011 IEEE Power
year, country and even from cable to cable. Further and Energy Society General Meeting, pp.1-6,
study is needed to demonstrate the velocity 24-29 July 2011
dependence of for PILC cable in live circuits. [5] F. Censi, G.Calcagnini, M. D Alessandro, M.
Another factor that may affect the velocity is the Triventi, P. Bartolini: Comparison of alignment
change in dimension of the cable. This may have algorithms for P-Wave coherent averaging,
an effect on the pressure on the dielectrics. Computers in Cardiology, 2006 , pp.921-924,
17-20 Sept. 2006
7 CONCLUSION [6] George J. Anders: Rating of Electric Power
Cables in Unfavorable Thermal Environment,
Experiments show that high frequency signals pp.1-75, May 2005, Wiley-IEEE Press
propagates faster with higher temperatures for [7] V. Dubickas, H. Edin: On-line time domain
XLPE cable and slower for PILC. reflectometry measurements of temperature
variations of an XLPE power cable, 2006 IEEE
It is observed that the temperature effect on Conference on Electrical Insulation and
propagation velocity is more significant for PILC Dielectric Phenomena, pp.47-50, 15-18 Oct.
than for XLPE. 2006
[8] C. Fanggao, G. A. Saunders, R. N. Hampton,
The temperature dependence of the real part of S. M. Moody and A. M. Clark: The effect of
permittivity () dominates the velocity change for hydrostatic pressure and temperature on the
XLPE cables. For PILC, further work is needed to permittivity of crosslinked polyethylene,
explain the origin of the velocity dependency with Seventh International Conference on Dielectric
temperature. Materials, Measurements and Applications,
pp.267-270, 1996
8 ACKNOWLEDGMENTS [9] I. Mladenovic, C. Weindl, C. Freitag:
Comparison of parametric partial discharge
The authors would like to thank DNV KEMA and dissipation factor characteristics of MV
Energy and Sustainability, Enexis, Alliander and PILC cables, Conference Record of the 2012
Locamation for their financial support. IEEE International Symposium on Electrical
Insulation (ISEI), pp.319-322, 10-13 June 2012

1866

You might also like