Type of system : Deluge water spray system Design density of discharge : 10.2 Lpm/m2 for Transformer body & 6.1 Lpm/m2 for non absorbing ground surface area Reference drawings: aaaa Transformer Details : Length : 6.4 m Width : 4.3 m Height : 5.3 m Theoretical Water Demand Calculations for ICT Transformer
A. Transformer absorbing surface are ( side and top) = 140.94 m square
B. Transformer non absorbing surface ( ground) = 27.52 m square C. Water required for absorbing area = 140.94 * 10.2 = 1437.588 lpm D. Water required for non absorbing area = 27.52 * 6.1 = 167.872 lpm E. Total water required = 1437.588 + 167.872 = 1605.46 lpm Actual water required based on hydraulic calculation =
Dimensions of the Transformer body
LENGTH (M) Width (M) Height (M) 6.4 4.3 5.3 a Surface area of top surface (L x W) x 1 27.52 b Surface area of front & back surface (L 67.84 x H) x 2
c Surface area of side-1 & side-2 surface 45.58
(W x H)X 2 d Total protected area (a + b + c) 140.94 e Design density as per NFPA-15 10.2 10.2 Absorbing area Design density as per NFPA-15 10.2 Non Absorbing area f Water requirement (d x e) 1437.588