Section F Screwplug Ref

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

INTRODUCTION TO SCREW PLUG

IMMERSION HEATERS

Screw Screw
Plug Sheath Plug Heater Integral
Application Size Material Material Type Thermostat
Clean water 1" Copper Brass ARTM Yes
114" Copper Brass MT No
2" Copper Brass EMT No
2" Copper Brass ARMT Yes
2" Copper Brass MT No
2" Incoloy Brass CH-SD No
212" Copper Brass ARMT Yes
212" Copper Brass MT No
Process water 1" SS SS ARTMS Yes
2" SS SS ARMTS Yes
2" SS SS MTS No
2" SS SS EMTS No
212" SS SS ARMTS Yes
212" SS SS MTS No
Solution water 2" Incoloy SS ARMTI Yes
2" Incoloy SS MTI No
212" Incoloy SS ARMTI Yes
Screw plug immersion heaters 212" Incoloy SS MTI No
consist of hairpin bent tubular Light weight oil 1" Steel Steel ARTMO Yes
elements brazed or welded into a 114" Steel Steel MTO No
screw plug and provided with wiring 2" Steel Steel ARMTO Yes
boxes for electrical connections. 2" Steel Steel MTO No
Screw plug immersion heaters are 212" Steel Steel ARMTO Yes
screwed directly through a threaded 212" Steel Steel MTO No
opening in a tank wall or through Medium weight 2" Steel Steel ARTMO Yes
matching pipe coupling, half oil 2" Steel Steel MTO No
coupling or welding flange. Sizes of 212" Steel Steel ARTMO Yes
screw plug heaters are available 212" Steel Steel MTO Yes
with 12", 34" 1", 114", 2" and 212" pipe Heavy weight 2" Steel Steel ARTMO Yes
threads. A wide selection of screw oil 2" Steel Steel MTO No
plug sizes, kilowatt ratings, 212" Steel Steel ARTMO Yes
voltages, sheath materials, terminal 212" Steel Steel MTO No
housings, and thermostats makes Specialty 1
2" Incoloy Steel RI No
these compact heaters ideal for all Heaterswater, 12" SS Steel RIO No
types of applications. oil & corrosion 12" Incoloy Brass RIN No
fluids 1
2" SS Brass RINO No
Screw plug immersion heaters are 1
2" SS SS RIS No
used for heating liquids and gases 1
2" Hasteloy Hasteloy RIH No
in a variety of processes. Those 3
4" Incoloy Steel RI No
heaters are ideal for process water 3
4" SS Steel RIO No
heating and freeze protection. All 3
4" Incoloy Brass RIN No
types of oils and heat transfer 3
4" SS Brass RINO No
solutions can also be heated using 1" Copper Brass TMW No
these compact easily controlled 1" SS SS TMWS No
units. The direct immersion method 1" Steel Steel TMO No
is energy efficient and well suited for 1" Incoloy Brass CJ Yes
many applications. 114" Copper Brass TMW No
2" Incoloy Brass DWH Yes

SS denotes Stainless Steel

F-3
PRODUCT DESCRIPTION Material carbon steel, brass and
OMEGALUX heavy duty tubular stainless steel. 60F to 240F thermostat (TH) and
elements are welded or brazed to a 0 to 127F(TL). the temperature
screw plug. Uniform heat Sizes 12", 34", 1", 114", 2", 212",
nominal. adjustment screw and scale are
distribution and repressed element inside requiring the removal of cover
bends provide long element life.For TERMINAL ENCLOSURES to change temperature setting.
heaters with built-in thermostats, a General Purpose sheet metal,
thermowell (hollow tube sealed at painted with red enamel. ARTM, ATMTI ARTMS AND
one end) is welded or brazed to the ARMTO SERIES The integral
screw plug and allows thermostat Type E-2 Combination moisture thermostat is available with
resistant/explosion resistant. temperature ranges at 60 to 250F
sensing element replacement or 0 to 100f for ARMT, ARMTI and
without draining the tank. Type E-2 explosion resistant ARMTS heaters. ARMTO heaters
Screw plug heaters are equipped enclosure involve the use of a wiring are available with three different
with a steel enclosure, and are also enclosure for use temperature ranges: 200 to 550F,
available with a combination Class I Groups C & D, Division 60 to 250F and 0 to 100F. This
control is wired in as a line
F
moisture resistant/explosion 1 & 2. Class II, Groups E, F & G,
Division 1 & 2. Class III, Division 1 & thermostat for loads up to 4.2 kW on
resistant enclosure. 240 volts. For high wattage rating, 3
2. Not intended for use in hazardous
Screw plug type heaters are phase operation and 480 Volts, this
areas. control is for pilot duty only and
screwed directly through a threaded should be wired to operate the
opening in tank wall. Heavy tank Safe operation of heaters equipped
with these enclosures depends holding coil of a magnetic contactor
walls may be drilled and tapped if by customer.
thickness is sufficient to engage 34 of upon employment of electrical
wiring meeting National Electric Note: The integral thermostat
threads. Lighter tank walls should functions as a temperature control
be equipped with suitable pipe half- Code for hazardous locations and
limiting maximum operating only. this is not a fail safe device so
coupling attached with proper braze an approved pressure and/or
or weld material. temperatures (including temperature
on outside of vessel, piping, flanges, temperature limit control should be
screw plugs, enclosures and other used with these heaters to assure
heat conducting parts) as directed safe operation.
Standard Pipe by flammable liquids, vapors or Caution: Explosion resistant Type
Thread Elements gases present. Approved pressure E-2 construction refers to heater
and /or temperature limiting controls design features which provide
must be used to assure safe explosion resisting containment of
operation in the event of system electrical wiring according to
Thermowell malfunctions. National Electric Code. abnormal
TEMPERATURE CONTROL application or use of heaters which
Many screw plug type heaters are results in excessive temperature
Tank Wall available with built-in thermostatic can crete hazardous conditions
Pipe Weld controls. In some installations, which can lead to fire.
Coupling where there is more than one heater Corrosion Policy
in a tank, you may consider one OMEGALUX cannot warrant any
heater with a built-in control that will electric immersion heater against
CONSTRUCTION FEATURES control the other heaters by wiring failure is the result of operating
Material copper, steel, Incoloy thermostat into the holding coil conditions beyond the control of the
and stainless steel. circuit of a magnetic contactor. If the heater manufactures. It is the
Number of elements in screw thermostat is separate from the responsibility of the purchaser to
plugs one, two or three heater, the thermostat sensing make the ultimate choice of sheath
depending on screw plug size. element should be located material based on his knowledge of
approximately 4 to 6 inches above the chemical composition of the
Element diameters 0.315", the heater. corrosive solution, character of
0.375", and 0.475". materials entering the solution, and
ARTM, ATMO AND ARTMS
Watt densities 6.5, 15, 23, 45 SERIES controls which he maintains on the
and 75 watts per square inch The ARTM, ARTMO and ATTMS process.
typical. automatic thermostat has a
temperature range range of 60-
SCREW PLUG
180F. Also available with alternate

F-4
SCREW PLUG IMMERSION HEATER
FOR PROCESS WATER

U 1", 2", 212" Stainless High conductivity elements Note: The integral thermostat
Steel Screwplug Filled with highest purity blends of functions as a temperature control
magnesium oxide refractory (MgO) only. This is not a fail-safe device so
U Stainless Steel Sheath compacted to a rock hard density to an approved pressure and/or
U 0.75 to 18 kW insure maximum electrical temperature limit control should be
U With or Without resistance, and assure long life. used with these heaters to assure
Thermostat safe operation.
Heavy coil construction Watt
density on the heating coil is To set the control temperature of
APPLICATIONS designed for low watt density heaters equipped with the standard
For process water pH 5-9 operation by increasing the coil general purpose enclosure, adjust
Use with industrial or municipal diameter and length to give the knob on the outside of the
water with mild or alkaline maximum coil surface area and limit terminal enclosure. For those
conditions, which require heater coil surface temperature, providing heaters equipped with E-2
sheath more resistant to corrosive longer coil life. enclosures, (explosion
influences or where a pH factor resistant/moisture tight)* remove the
Liberal electrical clearances
range of pH 5 to 9 exits. terminal enclosure lid to expose the
are provided in all terminal
temperature adjusting knob. For
For very weak 2-3% corrosive enclosures in accordance with the
safety reasons, power to heater and
solutions For very weak NEC insuring that proper arcing and
pilot duty power must be turned off
solutions with alkaline or acid creepage clearances are
before removing enclosure lid.
content of up to 3% by volume, such maintained. Termination insulators
as soap and detergent solutions, provide electrical isolation between This control is wired in as a line
soluble cutting oils and rinsing terminations and grounded metal thermostat for loads up to 4.2 kW on
applications where carryover from sheaths all to insure personnel 120 Volts and up to 6 kW on 240
prior chemical processes causes safety and equipment service life. Volts. For high wattage rating, 3
solution contamination buildup. phase operation and 480 Volts, this
Easy access to terminal wiring
control is for pilot duty only and
For temperature ranges to 180F Superior performances at element
should be wired to operate the
Dependable operation at those bends with all bent elements
holding coil of a magnetic contractor
temperatures normal to the plating repressed in hydraulic presses after
by customer.
or other chemical treating or severe bending to assure recompaction of
process cleaning applications. refractory material to eliminate hot Terminal Enclosures
spots and electrical insulation voids. Specify type enclosure required
For industrial tanks, vessels, & when ordering.
process piping Or any Grounding connector standard
application where a screw plug A solid terminal connector is General purpose -- Sheet metal,
heater can be used or is necessary standard on all OMEGALUX NEMA 1.
for a physical connection to an immersion heaters insuring positive
ground and personal safety. E-2 -- Combination moisture tight
industrial process. explosion resistant*
FEATURES Precise temperature Standard
heaters provided with built-in Caution: Explosion resistant type
Rugged construction Sturdy E-2 construction refers to heater
elements welded to stainless steel temperature controls. for those units
not provided with controls, see design features which provide
screwplugs provide superior rigidity explosion resisting containment of
and strength. Heavy duty jumper OMEGA controllers. Standard
temperature ranges are: electrical wiring according to
straps and terminal posts assure National Electric Code. Abnormal
permanent tightness of connections Temp. Temp. application or use of heaters which
carrying capacity. Range Range results in excessive temperatures
Type F Type F can create hazardous conditions
Long life metal sheath High
2 & 212" NPT which can lead to fire.
grade 300 Series stainless steel 1" NPT Screw Plug Screw Plug
outer sheath provides the benefits *Not intended for use in hazardous areas.
of strength and durability in those TL 0-127 T1 0-100

applications where stainless TH 60-240 T2 60-250


performance is required. Standard 60-180 T3 200-550

F-17
SCREW PLUG IMMERSION
HEATER FOR SOLUTION WATER
U 2", 212" Stainless Steel High conductivity elements
Filled with highest purity blend of Note: The integral thermostat
U Incoloy Sheath magnesium oxide refractory (MgO) functions as a temperature control
U 2 to 18 kW compacted to a rock hard density to only. This is not a fail-safe device so
U With or Without insure maximum thermal conductivity, an approved pressure and/or
Thermostat maximum electrical resistance, and temperature limit control should be
assure long element life. used with these heaters to assure
safe operation.
APPLICATIONS Heavy coil construction Watt
For severe hard water pH5 to 9 density on the heating coil is To set the control temperature of
For use with industrial severe hard designated for low watt density heaters equipped with the standard
water containing minerals, scale operation by increasing the coil general purpose enclosure adjust
and salts or with acid or alkaline diameter and length to give the knob on the outside of the
conditions where the highest quality, maximum coil surface area and limit terminal enclosure. For those
high nickel bearing Incoloy sheath coil surface temperature, providing heaters equipped with an E-2
or more durability than copper or longer coil life. enclosure (explosion resistant/ F
stainless is required. moisture resistant)* remove the
Liberal electrical clearances terminal enclosure lid to expose the
For weak 5 to 6% corrosive are provided in all terminal temperature adjusting knob. For
solution For weak and reclaimed enclosures in accordance with the safety reasons, power to heater and
water solutions with an alkaline or NEC insuring that proper arcing and pilot duty power must be turned off
acid contents up to 6% by volume; creepage clearances are before removing enclosure lid.
or solutions with high mineral maintained.Termination insulators
content containing heavy provide electrical isolation between This control is wired in a line
detergents; soluble cutting oils or terminations and grounded metal thermostat for loads up up to 4.2 kW
caustic cleaning applications. sheaths all to insure personnel on 120 Volts and up to 6 kW on
safety and equipment service life. 240 Volts. For high wattage ratings
For temperature ranges at 180F and 480 Volts, this control is for pilot
This type Screw Plug Immersion Superior performance at element duty only and should be wired to
Heater will provide dependable bends with all bent elements operate the holding coil of a
operation at the normal repressed in hydraulic presses after magnetic contactor by customer.
temperatures commonly bending to assure recompaction of
encountered in the plating, chemical refractory material to eliminate hot Terminal enclosures Specify type
treating, or severe process cleaning spots and electrical insulation voids. enclosure required when ordering.
applications. Easy access to terminal wiring E1: General purpose, sheet metal
For industrial tanks, vessels, & with a large terminal enclosure NEMA 1.
process piping Or any providing ample wiring and
E2: Combination moisture resistant/
applications where a screw plug termination space insuring cool
explosion resistant.*
heater can be used or is necessary terminations and making installation
for a physical connection to an easy. * Caution: Explosion resistant type
industrial process. E-2 construction refers to heater
Precise Temperature Control
design features which provide
FEATURES Standard heaters provided with
explosion resisting containment of
Rugged construction Sturdy built-in temperature controls. For
electrical wiring according to
0.475" diameter elements welded to those units not provided with
National Electrical Code. Abnormal
stainless steel screw plugs provide control, see section P of catalog.
application or use of heaters which
superior rigidity and strength. Heavy Standard temperature ranges are:
results in excessive temperatures
duty jumper straps and terminal can create hazardous conditions
posts assure permanent tightness of which can lead to fire. * Not
connections carrying capacity. 2 and 212" NPT Temp.
intended for use in hazardous
Screw Plug Type RangeF
Long life metal sheath Superior areas.
T1 0-100
grade Incoloy outer sheath provides T2 60-250
the highest practical protection
available against most corrosive
chemical solutions. It resists stress
corrosion, cracking, sulfur attack,
scaling, oxidation, and carburization
at elevated temperatures.

F-24
One Omega Drive | Stamford, CT 06907 | 1-888-TC-OMEGA (1-888-826-6342) | info@omega.com

www.omega.com
UNITED KINGDOM
www. omega.co.uk
Manchester, England
0800-488-488

UNITED STATES FRANCE


www.omega.com www.omega.fr
1-800-TC-OMEGA Guyancourt, France
Stamford, CT. 088-466-342

CANADA CZECH REPUBLIC


www.omega.ca www.omegaeng.cz
Laval(Quebec) Karvin, Czech Republic
1-800-TC-OMEGA 596-311-899

GERMANY BENELUX
www.omega.de www.omega.nl
Deckenpfronn, Germany Amstelveen, NL
0800-8266342 0800-099-33-44

More than 100,000 Products Available!


Temperature Data Acquisition
Calibrators, Connectors, General Test and Measurement Auto-Dialers and Alarm Monitoring Systems,
Instruments, Glass Bulb Thermometers, Handheld Instruments Communication Products and Converters, Data
for Temperature Measurement, Ice Point References, Acquisition and Analysis Software, Data Loggers
Indicating Labels, Crayons, Cements and Lacquers, Infrared Plug-in Cards, Signal Conditioners, USB, RS232, RS485
Temperature Measurement Instruments, Recorders Relative and Parallel Port Data Acquisition Systems, Wireless
Humidity Measurement Instruments, RTD Probes, Elements Transmitters and Receivers
and Assemblies, Temperature & Process Meters, Timers and
Counters, Temperature and Process Controllers and Power
Pressure, Strain and Force
Switching Devices, Thermistor Elements, Probes and
Displacement Transducers, Dynamic Measurement
Assemblies,Thermocouples Thermowells and Head and Well
Force Sensors, Instrumentation for Pressure and Strain
Assemblies, Transmitters, Wire
Measurements, Load Cells, Pressure Gauges, Pressure
Flow and Level Reference Section, Pressure Switches, Pressure Transducers,
Air Velocity Indicators, Doppler Flowmeters, Level Proximity Transducers, Regulators,
Measurement, Magnetic Flowmeters, Mass Flowmeters, Strain Gages, Torque Transducers, Valves
Pitot Tubes, Pumps, Rotameters, Turbine and Paddle Wheel
Flowmeters, Ultrasonic Flowmeters, Valves, Variable Area Heaters
Flowmeters, Vortex Shedding Flowmeters Band Heaters, Cartridge Heaters, Circulation Heaters,
Comfort Heaters, Controllers, Meters and Switching
pH and Conductivity Devices, Flexible Heaters, General Test and Measurement
Conductivity Instrumentation, Dissolved Oxygen Instruments, Heater Hook-up Wire, Heating Cable
Instrumentation, Environmental Instrumentation, pH Systems, Immersion Heaters, Process Air and Duct,
Electrodes and Instruments, Water and Soil Analysis Heaters, Radiant Heaters, Strip Heaters, Tubular Heaters
Instrumentation

click here to go to the omega.com home page