Date 24-07-2013 Alfa Laval Groningen B.V.

Project ref. Bestindo www.alfalaval.com


Version 1.2.0
Cold Room Calculation

General
Room temperature -35.00 C
Temp. difference inside / outside room 71.00 C
Ventilation loss factor
Running time installation 16 hrs/day
Length x Width x Height 3.00 x 2.50 x 2.50 m
Room volume 18.75 m
Insulation material Polyurethane
Thickness 150.00 mm
Floor insulation 150.00 mm
K-value insulation panel 0.14 W/mK
Cooler fans 4500.00 / 12 Watt / Hrs/day
Illumination 15.00 / 8 Watt / Hrs/day
Persons 0/8 nr. / Hrs/day
Other heat sources 0.00 / 0 Watt / Hrs/day
Products Fish sea-fish fat
Storage quantity 2000.00 kg
Stock shift 2000.00 kg
Entering temperature 20.00 C
Cool down/congel. time 12 hr

Heat loads
Transmission losses 389 Watt
Ventilation losses 1139 Watt
Other heat sources 2288 Watt
Cool down/congel. time 14968 Watt
Respiration 0 Watt
Subtotal 18784 Watt

With a running time per day of 16 hrs the total required cooling capacity is 28.2 kW
The specific capacity is 1502.6 W/m