INSTALLATION
IN
Installation P34x/EN IN/I76
CONTENTS
(IN) 15-
1. RECEIPT OF RELAYS 5
2. HANDLING OF ELECTRONIC EQUIPMENT 6
3. STORAGE 7
4. UNPACKING 8
5. P34X RELAY MOUNTING 9
5.1 Rack mounting 9
5.2 Panel mounting 11
FIGURES
IN Figure 30: Generator protection relay (60TE) with biased differential (16 I/P & 14 O/P & CLIO) 47
Figure 31: Generator protection relay (60TE) with biased differential (24 I/P & 14 O/P) 48
Figure 32: Generator protection relay (60TE) with biased differential (16 I/P & 22 O/P) 49
Figure 33: Generator protection relay (60TE) with biased differential (16 I/P & 18 O/P (4HB)) 50
Installation P34x/EN IN/I76
Figure 34: Generator protection relay (60TE) with biased differential (16 I/P & 11 O/P (4HB) & RTDs)
51
Figure 35: Generator protection relay (60TE) with biased differential (16 I/P & 11 O/P (4HB) & CLIO)
52
Figure 36: Generator protection relay (80TE) with biased differential (24 I/P & 24 O/P RTDs & CLIO)
53
Figure 37: Generator protection relay (80TE) with biased differential (24 I/P & 24 O/P & RTDs &CLIO)
54
Figure 38: Generator protection relay (80TE) with biased differential (32 I/P & 24 O/P & RTDs ) 55
Figure 39: Generator protection relay (80TE) with biased differential (24 I/P & 32 O/P & RTDs) 56
Figure 40: Generator protection relay (80TE) with biased differential (32 I/P & 16 O/P & RTD & CLIO)
57
Figure 41: Generator protection relay (80TE) with biased differential (16 I/P & 32 O/P & RTD & CLIO)
58
Figure 42: Generator protection relay (80TE) with biased differential (16 I/P & 24 O/P (8 HB) & RTDs
& CLIO) 59
Figure 43: Generator protection relay (80TE) with biased differential and zero sequence voltage interturn
(24 I/P & 24 O/P & RTDs & CLIO) 60
Figure 44: Generator protection relay (80TE) with biased differential and zero sequence voltage interturn
(24 I/P & 24 O/P & RTDs & CLIO) 61
Figure 45: Generator protection relay (80TE) with biased differential and zero sequence voltage interturn
(32 I/P & 24 O/P & RTDs ) 62
Figure 46: Generator protection relay (80TE) with biased differential and zero sequence voltage interturn
(24 I/P & 32 O/P & RTDs) 63
Figure 47: Generator protection relay (80TE) with biased differential and zero sequence voltage interturn
(32 I/P & 16 O/P & RTDs & CLIO) 64
Figure 48: Generator protection relay (80TE) with biased differential and zero sequence voltage interturn
(16 I/P & 32 O/P & RTDs & CLIO) 65
Figure 49: Generator protection relay (80TE) with biased differential and zero sequence voltage interturn
(24 I/P & 20 O/P (4HB) & RTDs & CLIO) 66
Figure 50: Generator protection relay (80TE) with biased differential and zero sequence voltage interturn
(16 I/P & 24 O/P (8HB) & RTDs & CLIO) 67
Figure 51: Generator Protection Relay (80TE) with 90% & 100% (3rd Harmonic) stator earth fault &
interturn protection (24 I/P & 24 O/P & CLIO & RTD) 68
Figure 52: Generator protection relay (80TE) with 100% stator earth fault protection via terminal earthing
transformer. broken delta with secondary loading resistor (24 I/P & 24 O/P & CLIO & RTD) 69
Figure 53: Generator protection relay (80te) with 100% stator earth fault protection via neutral earthing
transformer with secondary loading resistor (24 I/P & 24 O/P & CLIO & RTD) 70
Figure 54: Generator protection relay (80te) with 100% stator earth fault protection via neutral earthing
transformer with primary loading resistor (24 I/P & 24 O/P & CLIO & RTD) 71
Figure 55: Generator protection relay (80TE) 100% stator earth fault via low frequency injection
configurations 72
IN
Figure 56: Generator protection relay (80TE) with biased differential & 100% stator earth fault
(24 I/P & 24 O/P & CLIO & RTD) 73
Figure 57: Generator protection relay (80TE) with 90% & 100% (3rd Harmonic) stator earth fault
& interturn protection (24 I/P & 32 O/P & RTD) 74
P34x/EN IN/I76 Installation
Figure 58: Generator protection relay (80TE) with 90% & 100% (3rd Harmonic) stator earth fault & interturn
protection (32 I/P & 24 O/P & RTD) 75
Figure 59: Generator protection relay (80TE) with 90% & 100% (3rd Harmonic) stator earth fault & interturn
protection (32 I/P & 16 O/P & CLIO & RTD) 76
Figure 60: Generator protection relay (80TE) with 90% & 100% (3rd Harmonic) stator earth fault & interturn
protection (16 I/P & 32 O/P & CLIO & RTD) 77
Figure 61: Generator protection relay (80TE) with 90% & 100% (3rd Harmonic) stator earth fault & interturn
protection (24 I/P & 20 O/P (4HB) & CLIO & RTD) 78
Figure 62: Generator protection relay (80TE) with 90% & 100% (3rd Harmonic) stator earth fault & interturn
protection (16 I/P & 24 O/P (8HB) & CLIO & RTD) 79
Figure 63: Assembly P341/2 generator protection relay (40TE) (8 I/P & 7 O/P with optional I/P & O/P) 80
Figure 64: Assembly P342 generator protection relay (40TE) (8 I/P & 7 O/P with optional RTD & CLIO) 81
Figure 65: Assembly P342 generator protection relay (60TE) (16 I/P & 16 O/P with optional I/P & O/P) 82
Figure 66: Assembly P342 generator protection relay (60TE) (16 I/P & 8/16 O/P with optional
RTD & CLIO & HB O/P) 83
Figure 67: Assembly P343 generator protection relay (60TE) (16 I/P & 14 O/P with optional I/P & O/P) 84
Figure 68: Assembly P343 generator protection relay (60TE) (16 I/P & 7/14 O/P with optional
RTD & CLIO & HB O/P) 85
Figure 69: Assembly P343/4 generator protection relay (80TE) (16/24 I/P & 16/24 O/P with optional
I/P & O/P) 86
Figure 70: Assembly P343/4 generator protection relay (80TE) (16/24 I/P & 16/24 O/P with optional
RTD & CLIO & HB O/P) 87
Figure 71: Assembly P345 generator protection relay (80TE) (16/24 I/P & 16/24 O/P with optional
I/P & O/P & RTDs) 88
Figure 72: Assembly P345 generator protection relay (80TE) (16/24 I/P & 16/24 O/P with optional
RTDs & CLIO & HB O/P) 89
Figure 73: Assembly P345 generator protection relay (80TE) (16/24 I/P & 16/24 O/P with optional
CLIO & HB O/P) 90
Figure 74: Double ended field winding connection 91
Figure 75: Single ended field winding connection 92
Figure 76: Final assembly drawing - P391 panel mounted 93
Figure 77: Final assembly drawing - P391 rack mounted 94
IN
Installation P34x/EN IN/I76
1. RECEIPT OF RELAYS
Protective relays, although generally of robust construction, require careful treatment prior to
installation on site. On receipt, relays should be examined immediately to ensure no external
damage has been sustained in transit. If damage has been sustained, a claim should be
made to the transport contractor and AREVA T&D should be promptly notified.
Relays that are supplied unmounted and not intended for immediate installation should be
returned to their protective polythene bags and delivery carton. Section 3 gives more
information about the storage of relays.
IN
P34x/EN IN/I76 Installation
IN
Installation P34x/EN IN/I76
3. STORAGE
If relays are not to be installed immediately upon receipt, they should be stored in a place
free from dust and moisture in their original cartons. Where de-humidifier bags have been
included in the packing they should be retained. The action of the de-humidifier crystals will
be impaired if the bag is exposed to ambient conditions and may be restored by gently
heating the bag for about an hour prior to replacing it in the carton.
To prevent battery drain during transportation and storage a battery isolation strip is fitted
during manufacture. With the lower access cover open, presence of the battery isolation strip
can be checked by a red tab protruding from the positive side.
Care should be taken on subsequent unpacking that any dust that has collected on the
carton does not fall inside. In locations of high humidity the carton and packing may become
impregnated with moisture and the de-humidifier crystals will lose their efficiency.
Prior to installation, relays should be stored at a temperature of between 25 to +70C
(-13F to +158F).
IN
P34x/EN IN/I76 Installation
4. UNPACKING
Care must be taken when unpacking and installing the relays so that none of the parts are
damaged and additional components are not accidentally left in the packing or lost. Ensure
that any Users CDROM or technical documentation is NOT discarded - this should
accompany the relay to its destination substation.
Note: With the lower access cover open, the red tab of the battery isolation
strip will be seen protruding from the positive side of the battery
compartment. Do not remove this strip because it prevents battery
drain during transportation and storage and will be removed as part of
the commissioning tests.
Relays must only be handled by skilled persons.
The site should be well lit to facilitate inspection, clean, dry and reasonably free from dust
and excessive vibration. This particularly applies to installations that are being carried out at
the same time as construction work.
IN
Installation P34x/EN IN/I76
P0146ENb
The two horizontal rails of the rack frame have holes drilled at approximately 26mm intervals
and the relays are attached via their mounting flanges using M4 Taptite self-tapping screws
with captive 3mm thick washers (also known as a SEMS unit). These fastenings are
available in packs of 5 (our part number ZA0005 104).
P0147ENb
Note: It is not advised that MiCOM relays are fastened using pop rivets as
this will not allow the relay to be easily removed from the panel in the
future if repair is necessary.
If it is required to mount a relay assembly on a panel complying to BS EN60529 IP52, it will
be necessary to fit a metallic sealing strip between adjoining relays (Part no GN2044 001)
and a sealing ring selected from Table 2 around the complete assembly.
The RTD cables should not be run adjacent to or in the same conduit as other high voltage or
current cables.
A typical cable specification would be:
Each core: 7/0.2mm copper conductors heat resistant PVC insulated
Nominal conductor area: 0.22mm2 per core
Screen: Nickel-plated copper wire braid heat resistant PVC sheathed
The extract below may be useful in defining cable recommendations for the RTDs:
Noise pick up by cables can be categorized in to three types:
Resistive
Capacitive
Inductive
Resistive coupling requires there to be an electrical connection to the noise source. So
assuming that the wire and cable insulation is sound and that the junctions are clean then
this can be dismissed.
Capacitive coupling requires there to be sufficient capacitance for the impedance path to the
noise source to be small enough to allow for significant coupling. This is a function of the
dielectric strength between the signal cable on the noise source and the potential (i.e. power)
of the noise source.
Inductive coupling occurs when the signal cable is adjacent to a cable/wire carrying the noise
or it is exposed to a radiated EMF.
Standard screened cable is normally used to protect against capacitively coupled noise, but
in order for it to be effective the screen must only be bonded to the system ground at one
point, otherwise a current could flow and the noise would be coupled in to the signal wires of
the cable. There are different types of screening available, but basically there are two types:
aluminium foil wrap and tin-copper braid.
Foil screens are good for low to medium frequencies and braid is good for high frequencies.
High-fidelity screen cables provide both types.
Protection against magnetic inductive coupling requires very careful cable routing and
magnetic shielding. The latter can be achieved with steel-armored cable and the use of steel
cable trays. It is important that the armor of the cable is grounded at both ends so that the
EMF of the induced current cancels the field of the noise source and hence shields the
cables conductors from it. (However, the design of the system ground must be considered
and care taken to not bridge two isolated ground systems since this could be hazardous and
defeat the objectives of the original ground design). The cable should be laid in the cable
trays as close as possible to the metal of the tray and under no circumstance should any
power cable be in or near to the tray. (Power cables should only cross the signal cables at
90 degrees and never be adjacent to them).
Clearly, both the capacitive and inductive screens must be contigous from the RTD probes to
the relay terminals.
The best types of cable are those provided by the RTD manufactures. These tend to be
three conductors (a so call "triad") which are screened with foil. Such triad cables are
available in armored forms as well as multi-triad armored forms.
Pin Connection
1 No Connection
2 RxD
3 TxD
4 DTR#
5 Ground
6 No Connection
7 RTS#
8 CTS#
9 No Connection
Connections to the second rear port configured for EIA(RS)232 operation can be made using
a screened multi-core communication cable up to 15m long, or a total capacitance of 2500pF.
The cable should be terminated at the relay end with a 9-way, metal shelled, IN
D-type male plug. The table above details the pin allocations.
For K-bus or IEC60870-5-2 over EIA(RS)485
1 This port is actually compliant to EIA(RS)574; the 9-pin version of EIA(RS)232, see www.tiaonline.org.
P34x/EN IN/I76 Installation
Pin* Connection
4 EIA(RS)485 - 1 (+ ve)
7 EIA(RS)485 - 2 (- ve)
IN
Installation P34x/EN IN/I76
Sealing
23.30 155.40 8 off holes Dia. 3.4 strip
AB BA
177.0
168.00
159.00 (4U)
AB BA
All dimensions in mm
TRIP
ALARM
177.00
157.5
OUT OF
SERVICE
HEALTHY
max.
C = CLEAR
= READ
= ENTER
Side view
206.00 30.00
P1647ENb
IN
P34x/EN IN/I76 Installation
AB A B BA
168.00
159.00 177.0
(4U)
AB B A BA
4.50
62.00 155.40 129.50 483 (19 rack)
408.90
A = Clearance holes
B = Mounting holes
406.90
All dimensions in mm
TRIP
ALARM
177.00
OUT OF
SERVICE
HEALTHY
C = CLEAR
= READ
157.5
= ENTER
max.
SK1 SK2 SK3
413.20
Side view
30.00
P1616ENe
IN
Installation P34x/EN IN/I76
AB A B BA
168.00
159.00 177.0
(4U)
AB B A BA
4.50
62.00 155.40 129.50 483 (19 rack)
408.90
A = Clearance holes
B = Mounting holes
406.90
All dimensions in mm
TRIP
1 6
ALARM
177.00
OUT OF
SERVICE 2 7
HEALTHY
C = CLEAR 3 8
= READ
= ENTER
157.5
4 9
max.
5 10
413.20
Side view
30.00
P1616ENg
IN
P34x/EN IN/I76 Installation
IN
Installation P34x/EN IN/I76
The user shall be familiar with all safety statements listed in section 6.3.5
of the commissioning chapter and the Safety Section/Safety Guide
SFTY/4LM/G11 (or later issue) before undertaking any work on the MiCOM
P391.
Wiring between the DC rotor winding and the MiCOM P391 shall be suitably rated to
withstand at least twice the rotor winding supply voltage to earth. This is to ensure
that the wiring insulation can withstand the inductive Electro Motive Force (EMF)
voltage which will be experienced on disconnection or de-energisation of the DC
rotor winding supply.
Due to the limitations of the ring terminal, the maximum wire size that can be used for any of
the medium terminals is 6.0mm2 using ring terminals that are not pre-insulated (protective
conductor terminal (PCT) only). All MiCOM P391 terminals, except PCT shall be
pre-insulated ring terminals, the maximum wire size that can be used is reduced to 2.63mm2
per ring terminal. If a larger wire size is required, two wires can be used in parallel, each
terminated in a separate pre-insulated ring terminal.
IN
Wiring between the DC rotor winding and the MiCOM P391 shall be suitably rated to
withstand at least twice the rotor winding supply voltage to earth. The wire used for other
P391 connections to the medium duty terminal blocks should have a minimum voltage rating
of 300Vrms.
The dielectric withstand of P391 injection resistor connections (A16, B16, A8, B8) to earth is
5.8kV rms, 1 minute.
P34x/EN IN/I76 Installation
It is recommended that the auxiliary supply wiring should be protected by a high rupture
capacity (HRC) fuse of type NIT or TIA, rated between 2 A and 16 A. Other circuits should
be appropriately fused to protect the wire used.
IN
Installation P34x/EN IN/I76
162
170
IN
IN
Figure 8:
Installation
WIRING ENTRY
254
'A
266
'
WIRING ENTRY
ISOMETRIC VIEW
VIEW ON ARROW 'A'
TERMINAL COVER REMOVED
BEFORE WIRING AND MUST
BE RE-FITTED ON
COMPLETION OF WIRING MOUNTING ARRANGEMENT
MiCOM P342, P343, P344, P345 & P391
2. TERMINAL SCREWS : M4 x 7 BRASS CHEESE HEAD SCREWS WITH LOCK WASHERS PROVIDED.
(PRE PACK ZA0005060 - 1 PACK)
3. TO ACHIEVE ADEQUATE VENTILATION A MINIMUM AIR GAP OF 90mm(2U NOM) BETWEEN THE TOP OF
THE CASE & 45mm(1U NOM) AT THE BOTTOM OF THE CASE IS REQUIRED TO ANY ADJACENT EQUIPMENT.
430
278
IN
P34x/EN IN/I76 Installation
IN
P1727ENb
P2192ena IN
Figure 10: Generator protection relay (40TE) for small generator using VEE connected
VT's (8 I/P & 7 O/P)
P34x/EN IN/I76 Installation
IN
P2193ena
Figure 11: Generator protection relay (40TE) for small generator with sensitive power
(8 I/P & 7 O/P)
Installation P34x/EN IN/I76
IN
P2194ena
Figure 12: Generator protection relay (40TE) for small generator (8 I/P & 7 O/P & RTDs)
P34x/EN IN/I76 Installation
IN
P2195ena
Figure 13: Generator protection relay (40TE) for Small Generator (8 I/P & 7 O/P & RTDs)
Installation P34x/EN IN/I76
IN
P1357ena
Figure 14: Generator protection relay (40TE) for small generator (8 I/P & 7 O/P & CLIO)
P34x/EN IN/I76 Installation
IN
P2196ena
Figure 15: Generator protection relay (40TE) for small generator (8 I/P & 15 O/P)
Installation P34x/EN IN/I76
IN
P2197ena
Figure 16: Generator protection relay (40TE) for small generator (16 I/P & 7 O/P)
P34x/EN IN/I76 Installation
IN
P2198ena
Figure 17: Generator protection relay (40TE) for small generator (12 I/P & 11 O/P)
Installation P34x/EN IN/I76
P2308ENa
IN
Figure 18: Generator protection relay (40TE) for small generator (8 I/P & 11O/P (4 HB))
P34x/EN IN/I76 Installation
IN
P1358ena
Figure 19: Generator protection relay (60TE) for small generator (16 I/P & O/P & RTDs
& CLIO)
Installation P34x/EN IN/I76
IN
P1359ena
Figure 20: Generator protection relay (60TE) for small generator (16 I/P & 16 O/P & RTDs
& CLIO)
P34x/EN IN/I76 Installation
IN
P2201ena
Figure 21: Generator protection relay (60TE) for small generator (24 I/P & 16 O/P & RTDs)
Installation P34x/EN IN/I76
IN
P2202ena
Figure 22: Generator protection relay (60TE) for small generator (16 I/P & 24 O/P & RTDs)
P34x/EN IN/I76 Installation
IN
P2309ENa
Figure 23: Generator protection relay (60TE) for small generator (16 I/P & 20 O/P (4HB))
Installation P34x/EN IN/I76
IN
P2310ENa
Figure 24: Generator protection relay (60TE) for small generator (16 I/P & 12 O/P (4HB)
& RTDs & CLIO)
P34x/EN IN/I76 Installation
IN
P2203ena
Figure 25: Generator protection relay (60TE) for biased differential (16 I/P & 14 O/P & RTDs)
Installation P34x/EN IN/I76
IN
P2204ena
Figure 26: Generator protection relay (60TE) (16 I/P & 14 O/P & RTDs)
P34x/EN IN/I76 Installation
IN
P2205ena
Figure 27: Generator protection relay (60TE) with high impedance differential
(16 I/P & 14 O/P)
Installation P34x/EN IN/I76
IN
P2206ena
Figure 28: Generator protection relay (60TE) with high impedance differential
(16 I/P & 14 O/P)
P34x/EN IN/I76 Installation
IN P2207ena
Figure 29: Generator protection relay with biased differential using VEE connected VTs
and sensitive power (16 I/P & 14 O/P)
Installation P34x/EN IN/I76
IN
P1360ena
IN
P2208ena
Figure 31: Generator protection relay (60TE) with biased differential (24 I/P & 14 O/P)
Installation P34x/EN IN/I76
IN
P2209ena
Figure 32: Generator protection relay (60TE) with biased differential (16 I/P & 22 O/P)
P34x/EN IN/I76 Installation
IN
P2311ENa
Figure 33: Generator protection relay (60TE) with biased differential (16 I/P & 18 O/P (4HB))
Installation P34x/EN IN/I76
IN
P2312ENa
IN
P2313ENa
P1361ena
IN
IN
P1362ena
IN
P2212ena
IN
P2213ena
IN
P1363ena
IN
P1364ena
IN
P2314ENa
IN
P1648ENa
Figure 43: Generator protection relay (80TE) with biased differential and zero sequence
voltage interturn (24 I/P & 24 O/P & RTDs & CLIO)
Installation P34x/EN IN/I76
IN
P1649ENa
Figure 44: Generator protection relay (80TE) with biased differential and zero sequence
voltage interturn (24 I/P & 24 O/P & RTDs & CLIO)
P34x/EN IN/I76 Installation
IN
P1650ENa
Figure 45: Generator protection relay (80TE) with biased differential and zero sequence
voltage interturn (32 I/P & 24 O/P & RTDs )
Installation P34x/EN IN/I76
IN
P1651ENa
Figure 46: Generator protection relay (80TE) with biased differential and zero sequence
voltage interturn (24 I/P & 32 O/P & RTDs)
P34x/EN IN/I76 Installation
IN
P1652ENa
Figure 47: Generator protection relay (80TE) with biased differential and zero sequence
voltage interturn (32 I/P & 16 O/P & RTDs & CLIO)
Installation P34x/EN IN/I76
IN
P1653ENa
Figure 48: Generator protection relay (80TE) with biased differential and zero sequence
voltage interturn (16 I/P & 32 O/P & RTDs & CLIO)
P34x/EN IN/I76 Installation
IN
P2315ENa
Figure 49: Generator protection relay (80TE) with biased differential and zero sequence
voltage interturn (24 I/P & 20 O/P (4HB) & RTDs & CLIO)
Installation P34x/EN IN/I76
IN
P2316ENa
Figure 50: Generator protection relay (80TE) with biased differential and zero sequence
voltage interturn (16 I/P & 24 O/P (8HB) & RTDs & CLIO)
P34x/EN IN/I76 Installation
IN
P2317ENa
Figure 51: Generator Protection Relay (80TE) with 90% & 100% (3rd Harmonic) stator earth
fault & interturn protection (24 I/P & 24 O/P & CLIO & RTD)
Installation P34x/EN IN/I76
P2318ENa
IN
Figure 52: Generator protection relay (80TE) with 100% stator earth fault protection via
terminal earthing transformer. broken delta with secondary loading resistor
(24 I/P & 24 O/P & CLIO & RTD)
P34x/EN IN/I76 Installation
IN P2319ENa
Figure 53: Generator protection relay (80te) with 100% stator earth fault protection via
neutral earthing transformer with secondary loading resistor
(24 I/P & 24 O/P & CLIO & RTD)
Installation P34x/EN IN/I76
IN
P2320ENa
Figure 54: Generator protection relay (80te) with 100% stator earth fault protection via
neutral earthing transformer with primary loading resistor
(24 I/P & 24 O/P & CLIO & RTD)
P34x/EN IN/I76 Installation
P2321ENa
IN
Figure 55: Generator protection relay (80TE) 100% stator earth fault via low frequency
injection configurations
Installation P34x/EN IN/I76
P2322ENa
IN
Figure 56: Generator protection relay (80TE) with biased differential & 100% stator
earth fault (24 I/P & 24 O/P & CLIO & RTD)
P34x/EN IN/I76 Installation
IN P2323ENa
Figure 57: Generator protection relay (80TE) with 90% & 100% (3rd Harmonic) stator earth
fault & interturn protection (24 I/P & 32 O/P & RTD)
Installation P34x/EN IN/I76
IN
P2324ENa
Figure 58: Generator protection relay (80TE) with 90% & 100% (3rd Harmonic) stator earth
fault & interturn protection (32 I/P & 24 O/P & RTD)
P34x/EN IN/I76 Installation
IN
P2325ENa
Figure 59: Generator protection relay (80TE) with 90% & 100% (3rd Harmonic) stator earth
fault & interturn protection (32 I/P & 16 O/P & CLIO & RTD)
Installation P34x/EN IN/I76
IN
P2326ENa
Figure 60: Generator protection relay (80TE) with 90% & 100% (3rd Harmonic) stator earth
fault & interturn protection (16 I/P & 32 O/P & CLIO & RTD)
P34x/EN IN/I76 Installation
IN
P2327ENa
Figure 61: Generator protection relay (80TE) with 90% & 100% (3rd Harmonic) stator earth
fault & interturn protection (24 I/P & 20 O/P (4HB) & CLIO & RTD)
Installation P34x/EN IN/I76
IN
P2328ENa
Figure 62: Generator protection relay (80TE) with 90% & 100% (3rd Harmonic) stator earth
fault & interturn protection (16 I/P & 24 O/P (8HB) & CLIO & RTD)
P34x/EN IN/I76 Installation
IN
P2329ENa
IN
P1367ena
IN
P2345ENa
IN
P2346ENa
IN
P2343ENa
IN
P2344ENa
IN
P2347ENa
IN
P2348ENa
IN
P2349ENa
IN
P2350ENa
IN
P2351ENa
IN
P4195ENa
IN
P4196ENa
IN
Figure 76: Final assembly drawing - P391 panel mounted
P34x/EN IN/I76 Installation