2 Carry out point to point verification and earth loop resistance check.
4 Check charger / inverter cubicles are clean and free from dust and
moisture ingress.
5 Check insulation resistance of anti-condensation heater circuits.
( Min value = 1M )
7 Verify charger / inverter MCB / fuse ratings and relay settings are
correct.
8 Verify batteries are installed, identified and polarity correct to vendor
layout.
9 Verify battery connections are tight, approved grease applied and
shrouds fitted.
10 Verify switchboard feeder cubicle number and labelling is correct.
Remarks
348793682.doc Rev C2
MPN PROJECTS Electrical
Static Commissioning Checksheet E-008B
UPS / Battery System Sheet 3 of 3