1. Feeder panel should be local selection; 1-20 loops should be removed.

2. Both tacho signal should be taken in signal conditioning module. Port


3. Switch should be in cal mode.
4. Total no teeth= 172 .4 nos of radium tape should be applied in equal
distance= 43 teeth, . As radium cross by tacho. It blinks.
5. Speed should be minimum.
6. Mode ILC1-LC2I< 500. LC1= 10000-13000
7. Check nut should be rotated to adjust the load cell.
8. LC1 & LC2 should be properly fitted in groove.
9. Eveling rod should be applied.
10.Self check,9 no press- LC1=?, LC2=?
11.Program press, 1. Enter speed= 300
12.Tare cal- at load disengage, 41 to 49 note it in program
13.Deviation value- 0.5 t0 0.6
14.Apply engage. Self check, 9. LC1-LC2
15.Press span calibration.
16.Enter.
17.Deviation factor should be below 0.5. note down the parameter
18.Switch should be in operation mode. And remove the tacho.