Duct Leakage Testing: Ken Helfers, TSI Inc
Duct Leakage Testing: Ken Helfers, TSI Inc
Conserve energy
10-30% of heated/cooled air lost through ductwork
Leaky supply ducts dont delivery air where needed
Leaky return ducts add load
Higher-pressure ductwork
ASHRAE 90 90.1
1 recommends only testing ductwork rated >3 in H2O
Dont test flex duct
F=CL* P0.65
F = Max Leakage (cfm/100 ft2)
CL = Leakage Class (from table above)
P = Pressure (in H2O)
2011, TSI Incorporated
Prior to Field Testing
Specify
S if Duct
D tPPressure Cl
Classification
ifi ti
F=CL* P0.65
F = Max Leakage (cfm/100 ft2)
CL = Leakage Class (from table above)
P = Pressure (in H2O)
2011, TSI Incorporated
Duct Leakage Equation
F = CL P .65
Test plan
Test
T t reportt form
f
Consider
C Test S
System capabilities:
Ability to Log data and download with Time/Date stamp
vs using liquid-inclined and U-tube manometers
vs.
Contingency planning
(Designer: Put plans in contract drawing/specs)
REMEDIATE!
Re-test
Re test
Re-test failed section only?
gg need to test more sections?
Does section failure trigger
SPECIFY!
2011, TSI Incorporated
Test Procedure
i t ti
instructions
Choose
Ch th
the right
i ht T
Testt E
Equipment
i t
2011, TSI Incorporated
Contacts
Ken Helfers, TSI Inc. Siva Iyer, TSI Inc.
Ken.helfers@tsi.com siva.iyer@tsi.com
502
502-897-0945
897 0945 651
651-765-3721
765 3721
Pt = test pressure
Pt = test pressure
2011, TSI Incorporated
Comparison of SMACNA & EU
L k
Leakage Requirements
R i t