16 Autronica JSchexnayder

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 26

Autronica Fire and Security AS ■ ID: 1 1

Autronica Fire and Security AS

 A leading innovator,
pp
manufacturer and supplier
of fire & gas detection
equipment

 Founded in 1957 in
Trondheim, Norway

 “Protecting life, environment


and property”

Autronica Fire and Security AS ■ ID: 2


Fire & Gas Detection Challenges

 Building Fire Detection System


 95% of Critical Faults caused by electronics faults,
faults human mistakes
mistakes, or manual testing

Autronica Fire and Security AS ■ ID: 3


AutroSafe – Automatic Addressing

 Each detector has a unique ID,


and therefore automatic addressing ID
IDENTITETSKORT
Multi
Sensor
SENSOR

 When powering up, the system will


MULTI
14 05 17
NRR <123 004 567 8<
246 DES 00

automatically find all units’ “IDs”,


register 1
and “remember”... 001199828000346 7
 and simultaneously register 2
each detectors place in the 004199828001125 008199827600125
loop KNUS GLASSET
3
006199828001025
TRYKKBREAK
HER
PRESS HERE

 Built-in Short Circuit Isolators


GLASS

BN- 35
4
BRANNALARM

 100% Operational with Wiring Fault


Tilpasningsenhet
FIRE ALARM

007199828000725
Interface unit

Nr.

No
No.

6
 Specific Location of Fault Provided 5
001199828000025 008199827600126
Autronica Fire and Security AS ■ ID: 4
AutroSafe SelfVerify®

Power supply

All L
Loop U
Units
it SV- Communication-
C i i
control interface
Automatically Tested
Every 24 Hours Smoke detector

Fault warning
Fault signal
ALARM!
Fire Alarm
Fire Alarm Signal
SelfVerify®
stimulator
STOP! Detection
chamber
Operating
p g
Alarm-
Al
signal

Test smoke
Autronica Fire and Security AS ■ ID: 5
Fire & Gas Detection Challenges

 Building Fire Detection System


 95% of Critical Faults caused by electronics faults,
faults human mistakes
mistakes, or manual testing

 Communication Failures – Flame & Gas Detectors


 Between Engineering & Procurement
 Between Engineering & Maintenance/Operations
 Recognizing Need for Revising Procedures

Autronica Fire and Security AS ■ ID: 6


AutroFlame X33AF – Technology
 Multispectrum IR
 Maximum False Alarm Rejection
 Solar Resistance
 Single Detector for Multiple Fuels

 Automatic Optical Integrity (OI) Test


 Built-in lamps test all sensors every 60
seconds
 No external test lamp required

Autronica Fire and Security AS ■ ID: 7


X33AF – Cone of Vision

 N t All Fl
Not Flame D
Detectors
t t “S
“See”” E
Equally
ll

 Coverage Areas are different for each


model & manufacturer

 Smaller coverage areas lead to a


higher quantity of detectors required

Autronica Fire and Security AS ■ ID: 8


AutroPoint HC200 – Technology

 A diffusion-based, infrared combustible gas detector


(point-IR) that provides continuous, fixed monitoring
of flammable hydrocarbon gases from 0 to 100%
Lower Explosive Limit (LEL)

 Methane (default)
(default), ethane
ethane, propane,
propane butane
butane, ethylene
and propylene (100 flammable Hydrocarbon vapours)

 Calibration Not Required!

 21 Years MTBF

Autronica Fire and Security AS ■ ID: 9


AutroPath HC-600 Open Path Gas Detector

 5 – 120 meter Separation


 Redundant Xenon IR lamps
 Same detector model (spares) for
entire range of separation distance

Autronica Fire and Security AS ■ ID: 10


Acoustic Gas Leak Detector

•Stainless Steel

•4-20mA w/ HART

• SIL-2
SIL 2 R
Rated
t d

• Range of 12-20m (at 58dB)

• Analyzes 24 discrete ultrasonic frequency bands

• Data Logging w/ Removable Storage

Autronica Fire and Security AS ■ ID: 11


AutroTox Gas Detectors

 Local Display with Relay, Alarm, and Fault


Outputs Combined with isolated 4-20mA
4 20mA  H2S 0-20 pp
ppm
 H2S 0-50 ppm
 4-20 mA output with HART
 H2S 0-100 ppm
 Nonintrusive Calibration  CL2 0-10 ppm
 Fully Explosion-Proof Housing  NH3 0-100 ppm
 316SS or coated aluminum  NH3 0-500 ppm
 H2 0-1000 ppm
 Easy-to-Set
Easy to Set Alarm Levels
 O2 0-25% by Vol
 Access to Alarm and Fault History  CO 0-100 ppm
 Multiple Conduit Access Points  CO 0-500 ppm
 SO2 0-20
0 20 ppm
 SO2 0-100 ppm
Autronica Fire and Security AS ■ ID: 12
Fire & Gas Detection Challenges

 Building Fire Detection System


 95% of Critical Faults caused by electronics faults,
faults human mistakes
mistakes, or manual testing

 Communication Failures – Flame & Gas Detectors


 Between Engineering & Procurement
 Between Engineering & Maintenance/Operations
 Recognizing Need for Revising Procedures

 Industry Misconceptions
 SIL

Autronica Fire and Security AS ■ ID: 13


What is SIL?

 Safety Integrity Level (SIL) is a measure of safety for a given


protective function.
 Specifically, the extent to which the end user can expect the
protective function to perform, and in the case of a failure, fail
in a safe manner
manner.
 This protective function is known as the Safety Instrumented
Function (SIF).
(SIF)
 A Safety Instrumented System (SIS) is a collection of
components (field devices and logic solver) that execute one or
more SIFs.

Autronica Fire and Security AS ■ ID: 14 14


SIL Misconceptions

 SIL Applies to Individual Devices

 Connecting “SIL
SIL Devices”
Devices Creates a SIL Approved System

 Redundancy is Required to Meet a SIL Rating

Autronica Fire and Security AS ■ ID: 15 15


Misconception: - SIL Applies to Individual Devices

 IEC-61508 states that a SIL number applies to a complete function (SIF), i.e.
the field sensor, the logic solver and the final element. It is therefore incorrect
to refer to any individual item or equipment having a safety integrity level.

 An individual component can be certified for use in a particular SIL application


application,
but such a certificate constitutes only part of the verification effort, since the
target SIL must be verified for the complete SIF.

SIF
Loop driver F&G alarm
Detector Output
module
d l panell

Autronica Fire and Security AS ■ ID: 16


Misconception: – SIL Requires Redundancy

 SIL ratings do not require redundancy.


 SIL Ensures that a safety related system adequately performs the
required safety functions under all stated conditions within a defined
period of time.
 SIL assesses ththe risk
i k reduction
d ti required
i d ffor a ttolerable
l bl llevell off risk.
i k

 Redundancy
y is used to raise the availabilityy of unreliable equipment.
q p

 How likely is it that the function in question will perform its


assigned
i d task
t k when
h needed?
d d?

Autronica Fire and Security AS ■ ID: 17 17


Autronica – The Only Fire Detection System
SIL 2 Approved by TUV
 Autronica is safe and reliable. SelfVerify function tests field devices and
reports
p system
y as if newly
y installed every
y day.
y

 Autronica AutroSafe system’s SIF & SIS have been tested and approved
byy third party
p y TUV - World leader in SIL assessment.
AutroSafe SIF SIL 2 Approved from Input to Output

Loop driver F&G alarm


Sensor Output
module panel

Autronica Fire and Security AS ■ ID: 18 18


Fire & Gas Detection Challenges

 Building Fire Detection System


 95% of Critical Faults caused by electronics faults,
faults human mistakes
mistakes, or manual testing

 Communication Failures – Flame & Gas Detectors


 Between Engineering & Procurement
 Between Engineering & Maintenance/Operations
 Recognizing Need for Revising Procedures

 Industry Misconceptions
 SIL

 Compliance with Different Worldwide Regulations

Autronica Fire and Security AS ■ ID: 19


Autronica – Always a Safe Choice

 Designed and approved according to international standards


g
and regulations
 ISO 9001
 EX certification Approval Certificates Available for Download
 IEC61508 SIL 2

NAN YANG

Autronica Fire and Security AS ■ ID: 20


Fire & Gas Detection Challenges

 Building Fire Detection System


 95% of Critical Faults caused by electronics faults,
faults human mistakes
mistakes, or manual testing

 Communication Failures – Flame & Gas Detectors


 Between Engineering & Procurement
 Between Engineering & Maintenance/Operations
 Recognizing Need for Revising Procedures

 Industry Misconceptions
 SIL

 Compliance with Different Worldwide Regulations


 Communicating with PLC/DCS/ICSS/SIS/insert-your-own-initialism
PLC/DCS/ICSS/SIS/insert your own initialism

Autronica Fire and Security AS ■ ID: 21


AutroSafe – Communication
Safety PLC

Modbus RTU, Modbus TCP, and OPC

{or AutroCom}

AutroSafe – BS-420 / BC-420 panels

A t S f panels
AutroSafe l hhave iintegrated
t t d Modbus
M db converters
t
Autronica Fire and Security AS ■ ID: 22
AutroCom - direct link to DCS vendors
The Serial Port on the Multifunction Connection List can be used for one of these communication
types:
 ABB AC400  Serial – VDR
 ABB AC800 (SIL2)  Serial – ESPA
 Serial - MODBUS Master
 Siemens S7  Serial - MODBUS Slave

 Kongsberg (SIL2) Serial - Autrocom:
 SERIAL
 Emerson Delta V  SERIAL SLIDING WINDOW
 SERIAL SLIDING WINDOW HIGH INTEGRITY
INTEGRITY*
(For example for SIL2 connections)

Two TCP/IP ports on the main board (BSA-400) in different subnet, can be connected to switches with
multiple ports, and can be used for up to six of these communication types:
 TCP - MODBUS Master
 TCP - MODBUS Slave
 TCP - Autrocom:
 TCP/IP
 TCP/IP HIGH INTEGRITY*
(For example for SIL2 connections)

 TCP – Web server with Secure LogOn and Automatically shutdown. For uploading and
downloading software, logs, etc.

Autronica Fire and Security AS ■ ID: 23


Truly Redundant Communication Architecture

Safety PLC/DCS

BS-420
BS 420

Autronica Fire and Security AS ■ ID: 24


AutroSafe IFG – Architecture Overview

Autronica Fire and Security AS ■ ID: 25


Thank You for Your Time

Are There Any Questions

Autronica Fire and Security AS ■ ID: 26 26