Coal-fired power plant project

HP Heaters and bleed system SDD

Southwest Electric Power

Design Institute
SOUTHWEST ELECTRIC POWER DESIGN INSTITUTE

November 2015, Chengdu


1 System Design Range
The system design include:
1 HP Heaters and deflated,
2 Deaerator drainage and deflated.
2 system function and design specification
2.1 Function
2.1.1 Add normal high hydrophobicity is progressively returned to the
deaerator, while three were also set up a high added to the condenser
hydrophobic expansion accidents drains, to ensure that the high water level
can be applied at high hydrophobicity smoothly. Each pipeline has a valve
to adjust the hydrophobicity, plus maintaining a high level is normal.
2. 1.2 oxygen tank overflow discharge pipe to discharge the condenser
during normal operation, when the water quality failed to discharge
periodically blowdown. Deaerator set overflow drain pipe, the latter two by
a combined electric discharge isolation valve to the condenser hydrophobic
expansion. Case of emergency, oxygen tank overflow can be put to periodic
blowdown.
2.2 Design Notes
2.2.1 pipeline design parameters access principles:
1) Heater pipeline design pressure Steam Turbine access doors open
condition extraction pressure of 1.1 times, and not less than 0.1MPa
(g)
2) Heaters access to pipeline design temperature of the steam
extraction piping design pressure corresponding saturation
temperature.
2.2.2 The main drains eventually drawn design parameters, specifications
and materials:
High plus 1 normal / accident drains:
Design parameters: 7.151 MPa (g) & 287
Normal drainage pipe specifications and materials: 1 33 x 8 (20 G) / 194 x
10 (12Cr1MoVG)
Accident Drain Pipe specifications and materials: 1 94 x 11 (20 G) / 219x
11 (12Cr1MoVG)
High plus 2 normal / accident drains:
Design parameters: 4.578 MPa (g) & 2 59
Normal drainage pipe specifications and materials: 1 68 x 7 (CS # 20) / 219
x 8 (12Cr1MoVG)
Accident Drain Pipe specifications and materials: 194x 8 (CS # 20 ) / 219x
8 (12Cr1MoVG)
High plus 3 normal / accident drains:
Design parameters: 2.373 MPa (g) & 2 21
Normal drainage pipe specifications and materials: 1 68 x 7 (CS # 20) /
219x8 (12Cr1MoVG)
Accident Drain Pipe specifications and materials: 194x8 (CS # 20) /
219x8 (12Cr1MoVG)
Deaerator water overflow discharge pipe:
Design parameters: 1.427 MPa (g) & 192.8
Put water piping specifications and materials: 1 59 x 4 (CS # 20)
3 major systems and equipment operating instructions
The system main equipment includes high pressure heater, deaerator,
condenser. Wherein the high pressure feedwater heaters and deaerator see
chapter 3 System description, see condenser condensate system described in
the third chapter.
3. The system runs
3.1.1. Start-up and part load
Before starting the heater, deaerator are all starting the discharge
valve in the open position. After completion of the water side of air-
driven water-close valve on its side.
During startup, the trap levels normally open heater, hydrophobic discharged
under a heater. Due to start-up and low load levels of extraction steam
pressure is low, if the pressure difference between two adjacent heater is
insufficient to overcome the pipeline resistance loss and the static head,
the water level rises within the heater housing, open the trap accident,
hydrophobic row to the condenser.
3 1.2 normal operation
Unit normal operation, the normal drainage valve signal levels of the
normal water level is controlled by the heater, ensure a stable load and
change working conditions under hydrophobic flow. Levels heater continuous
purge valve is open. Heater bleed all system startup purge valve are
closed.
3.1. 3 abnormal operation
A high-pressure heater water level reached a high value, the incident
should open the trap, and the alarm in the control room; if the water level
continues to rise to high value, close the trap on a normal heater, and
turn on a accident heater traps and alarm in the control room; if the water
level continues to rise to high value automatically turns off to the
high-pressure extraction steam electric heater at all levels of isolation
valves and pneumatic check valve, open the trap on the Extraction tube high
pressure heater group splitting, water supply bypassing.
If the deaerator tank water level is high, through the relief valve to
drain the water condenser.
Low levels of water heater, should alarm in the control room.
4 Control and Interlocking
4.1 Control Equipment List
1) No. 1 to No. 2 high plus high plus the normal drainage pneumatic
control valve (1 0L CH 1 1AA1 01)
2) High plus 2 to 3 plus pneumatic high normal drainage valve (1 0L
CH21AA1 01)
3) No. 3 was added to the high normal hydrophobic deaerator pneumatic
control valve (1 0L CH31AA1 01)
4) No. 1 was added to the high condenser air accident hydrophobic
hydrophobic expansion valve (1 0L CH 1 2AA1 0 1 )
5) No. 2 was added to high condenser air accident hydrophobic
hydrophobic expansion valve (1 0L CH22AA1 0 1)
6) No. 3 was added to the high condenser air accident hydrophobic
hydrophobic expansion valve (1 0L CH32AA1 0 1)
7) Deaerator electric drain isolation valve (1 0L AA4 0 AA 0 01 )
8) Deaerator overflow drain to the condenser hydrophobic expansion of
the electric vacuum isolation valve (1 0L AA4 0 AA 002)
9) Deaerator overflow drain to a given electric discharge isolation
valve (1 0L AA4 0 AA 003)
10) Deaerator run electric adjustable exhaust isolation valve (1 0L
AA 42 AA501,)
11) Electric start deaerator exhaust isolation valve (1 0L AA 41
AA501)
4.2 Control and interlock requirements
.2.1 No. 4 to No. 1 High plus 2 plus pneumatic high normal drainage valve (1
0L CH 1 1AA1 01)
A, Overview
The valve is mounted on the No. 1 to No. 2 high plus high plus the normal
drainage pipe for adjusting No. 1 plus normal water level.
B, control and interlock
The valve is controlled by the number 1 plus the high water level
controller. Loss of gas off.
1) Auto Close
When HIGH splitting or No. 2 high added value sophomore level,
automatically shut down.
2) automatic opening
When the No. 2 high add water back to normal, the valve is opened
automatically adjusted.
4 .2.2 No. 2 to No. 3 HIGH HIGH normal hydrophobic pneumatic control valve
(1 0L CH21AA1 01)
A, Overview
The valve is mounted on the No. 2 to No. 3 high plus high plus normal drains
for adjusting No. 2 normal high water added.
B, control and interlock
The valve 2 plus high water level controller by the loss of gas is turned
off.
1) Auto Close
When the high plus splitting or No. 3 sophomore high added value level,
the valve closes automatically.
2) automatic opening
When the No. 3 high pressure heater water level returns to normal, the
valve automatically opens, the water level controller is automatically
tuned.
4 .2.3 No. 3 was added to the high oxygen normally hydrophobic pneumatic
control valve (1 0L CH31AA1 01)
A, Overview
The valve is located on No. 3 was added to the high deaerator normally
drains to adjust the water level high plus No. 3.
B, control and interlock
The valve consists of 3 high pressure heater water level controller.
Loss of gas off.
1) Auto Close
When the high-oxygen water level - high or high solution plus column,
the valve should be closed automatically.
2) automatic opening
When the oxygen water level returned to normal, and three were normal
HIGH put into operation, the door is automatically opened by the water
level controller is automatically tuned.
4 .2.4 1, 2, 3, was added to the high condenser hydrophobic expansion
hydrophobic pneumatic control valve (1 0L CH 1 2AA1 0 1 , 1 0L CH22AA1 0 1, 1
0L CH32AA1 0 1)
A, Overview
The valves are installed in the condenser is added to the high
hydrophobic expansion of road accidents drainage pipe for adjusting the
present high level of added water.
B, control and interlock
The valve heightened by the high water level controller, when the loss
of gas is turned on.
1) automatically open
a) When the high water level plus a high level of the value of the valve
automatically open.
b) When the high water level high junior high plus binary or oxygen water
level - high (for 3 plus high accident hydrophobic valve 1 0L CH32AA1 0 1)
when the valve is automatically opened.
2) Automatic Close
When this level HIGH level returned to normal, (No. 3 for high heater
drain valve 1 0L CH32AA1 0 1 needed oxygen water level is normal), the
recovery is automatically turned off.
High water level between high added value and a sophomore value, the
valves regulate the water level controller for automatic adjustment.
4.2 5 Deaerator electric drain isolation valve (1 0L AA4 0 AA 0 01 )
A, Overview
The valve is mounted on the deaerator drainage pipe, for discharging
the deaerator high - high water level of the water.
B, control and interlock
Deaerator valve is controlled by the high level controller.
1) automatically open
When the oxygen tank water level up to the overflow level, and relief
valve is still fully open deaerator water level drops.
2) automatically close; one of the following conditions is closed
a) oxygen water level back to normal.
b) When the oxygen is being overflow drain, high condenser hot well
water level.
4.2. 6 Deaerator overflow drain to the condenser electric vacuum
isolation valve (1 0L AA4 0 AA 0 0 2)
A, Overview
The valve is mounted on the deaerator to the condenser overflow drain
pipe to discharge the high water level of deaerator water.
B, control and interlock
Oxygen tank valve is controlled by a high water level controller.
1) automatically open
When the oxygen tank water level up to the overflow level.
2) automatically close; one of the following conditions is closed
a) oxygen tank water level back to normal.
b) When the oxygen tank is overflow drain, high condenser hot well water
level.
C) When the oxygen tank is overflow drain, high condenser backpressure.
4.2. 7 Deaerator overflow drain to a given row of electric door (1 0L
AA4 0 AA 003)
A, Overview
The door is mounted on an oxygen tank to overflow drain pipe given row.
B, control and interlock
When the oxygen tank oxygen tank or substandard water quality is high
and the overflow drain the condenser hot well water or condenser back
pressure is high, then open the electric door.
When the above conditions are back to normal, then turn off
automatically.
4.2. 8 Run exhaust deaerator adjustable electric isolating valve (1 0L
AA 42 AA501,)
A, Overview
The valve is mounted on the exhaust pipes run deaerator for continuous
emissions of non-condensable gases oxygen inside.
B, control and interlock
The valve in the control room to manually start, close, can stay in any
position.
4.2. 9 Deaerator exhaust electric start isolating valve (1 0L AA 41
AA501)
A, Overview
The valve is mounted on the exhaust pipe deaerator start for non-
condensable gases oxygen within the startup.
B, control and interlock
The valve in the control room manual opening and closing.
5 associated drawings
F0 5 761S - J 1201 - 01 : HP Heaters and bleed the system flow chart

NOTE: The instructions KKS number to No. 1 unit, for example, to indicate
when the No. 2 unit, simply 10XXXXXX to 20XXXXXX can. J0 is the unit
number 1, 2 public. KKS number listed in the article for reference, the
specific number to the system flow chart prevail.