Motor data:

Name: Feedwater pump


Rated Power: Pn = 1500.0 kW
Rated Voltage: Un = 6.0 kV
Rated Current: In = 175.0 A
Starting Current: IS = 5.00 In 875
Starting time: tS = 10.0 s
Ambient temperature: 40 C 1

Phase CT:
Primary: 200 A
Secondary: 5 A
Relay input current: 5 A

Ring/Cable Type CT:


Primary: 200 A
Secondary: 5 A
Relay input current: 5 A
A in primary.
Thermal overload protection:
p.u. scaling factor of phase currents k= 1,14
Safe stall time: t6x = 21.0 s
Weighting factor: p= 50 %
Prior alarm level: A = 90 %
Restart inhibit level: i = 68 %
Cooling time multiplier: kc = 4
Start-up supervision:
Start-up current: IS> = 5.00 In #VALUE!
Start-up time: tS = 11.00 s
Short-circuit protection:
Start current: I>> = 3.75 In #VALUE!
Operate time: t>> = 0.05 s
Earth-fault protection:
Start current: I0> = 3.0 % In 6
Operate time: t0> = 2.00 s
Unbalance protection:
Start current: I2> = 0.30 In
Time constant: K2 = 7
Undercurrent protection:
Start current: I<= 0.0 % In #VALUE!
Operate time: t<= 0.0 s
Cumulative start-up time counter:
Restart inhibit start count setting: tsi = 21 s
Countdown rate of start-up time counter: ts/t = 10 s/h
A in primary.

A in primary.

A in primary.

A in primary.
Cold condition starts:

Start Current after Running time Stopping


number: start after start time
( In) (min) (min)

1 1 0.18 0
2 1 0.18 10
3 1 0.18 10

U s ed therm al capacity [% ]
100%

90%

80%

#VALUE! 70%
#VALUE! 60%

50%

40%

30%

20%

10%

0%
0 0 0 0
Cold starts
100% 10.00

90% 9.00

80% 8.00

70% 7.00

60% 6.00
I/In

50% 5.00

40% 4.00

30% 3.00

20% 2.00

10% 1.00

0% 0.00
0 0 0 0 0 1 [s] 1
Time 1 1 1 1
Prior load:
Preloading Preloading
Stopping time
current time
( In) (min) (min)

1 100 0

Hot condition starts:

Start Current after Running time Stopping time

U s ed therm al capacity [% ]
number: start after start after start
( In) (min) (min)

1 1 0,19 0
2 1 0,19 0 100%

90%

80%

70%

60%

50%

40%

30%

#VALUE! 20%
#VALUE! 10%

0%
0.00 0.10 0.20 0.30
U s ed therm al capacity [% ]

Hot starts
100% 10.00

90% 9.00

80% 8.00

70% 7.00

60% 6.00

50% 5.00I/In
40% 4.00

30% 3.00

20% 2.00

10% 1.00

0% 0.00
0.00 0.10 0.20 0.30 0.40 0.50 [s]0.60
Time 0.70 0.80 0.90 1.00
Prior load:
Preloading
Preloading time
current
( In) (min)

1 100 6000 s

Cycle
Load current: Running time:
number:
( In)

U s ed therm al c apac ity [% ]


(min)

1 1 1 60 s
2 0 s
3 0 s
4 0 s
100%
5 0 s
6 0 s 90%

7 0 s 80%
8 0 s
70%
9 0 s
60%
10 0 s
11 0 s 50%
12 0 s 40%
13 0 s
30%
14 0 s
15 0 s 20%

10%
NOTE! The program does not calculate cycles 0%
correctly if load current is below 0,12 x In. 0 0 0 0
U s ed therm al c apac ity [% ]

Cycles
100% 10.00

90% 9.00

80% 8.00

70% 7.00
I/In

60% 6.00

50% 5.00

40% 4.00

30% 3.00

20% 2.00

10% 1.00

0% 0.00
0 0 0 0 0 1 [s] 1
Time 1 1 1 1
Project name: Protection device:
Type here REM 610
Customer reference:
Type here
Title:
Setting proposal for Motor Protection
A BB
Motor: Prepared by: Sheet:
400 LKB 6/12/2003 Type name here 1/5
Checked by: Revision:
6/12/2003 Type name here A

MOTOR DATA: Rated power PnM = 1500.0 kW


Rated voltage UnM = 6.0 kV
Rated current InM = 175.0 A
Starting current Is = 5.00 InM
Starting time ts = 10.0 s
Ambient temperature Tamb = 40.00 C

PHASE CURRENT CT DATA: CT primary = 200 A


CT secondary = 5A
relay input = 5A

NEUTRAL CURRENT CT DATA: CT primary = 200 A


CT secondary = 5A
relay input = 5A
RELAY SETTINGS:

Thermal overload protection: Setting range:


p.u. scaling factor (0,52,5) k= 1,14
Safe stall time (2,0...120 s) t6x = 21.0 s
Weighting factor (20...100%) p= 50 %
Prior alarm level (50...100%) a = 90 %
Restart inhibit level (20...80%) i = 68 %
Cooling time constant (1...64 H) kc = 4
Start-up supervision:
Start current (1,0...10 IN) Is> = 5.00 In
Start-up time (0,3...80 s) ts> = 11.00 s
Short-circuit protection:
Start current (0,5...20 IN or ) I>> = 3.75 In
Operate time (0,05...30 s) t>> = 0.05 s
Earth-fault protection:
Start current (1,0...100% IN) I0> = 3.00 % In
Operate time (0,05300 s) t0> = 2.00 s
Unbalance protection:
Start current (0,10,5 x In) I2> = 0.30 x In
Time constant (5100) K2 = 7.0
Undercurrent protection:
Start current (3080% x In) I< = not in use % x In
Operate time (2600 s) t< = not in use s
Cumulative start time counter:
Restart inhibiting
Start count setting (5500 s) tsi = 21.0 s
Countdown rate of
start-up time counter (2250 s/h) ts/t = 10.0 s/h

Remarks:
Project name: Protection device:
Type here REM 610
Customer reference:
Type here
Title:
Setting proposal for Motor Protection
A BB
Motor: Prepared: Sheet:
400 LKB 6/12/2003 Type name here 2/5
Checked: Revision:
6/12/2003 Type name here A

Switch Function Setting Checksum


SGF3/1 Short-circuit protection inhibited or in use
1 = short-circuit protection inhibited (setting displayed "---"), 0 = short-circuit protection in use 0 1= 0
SGF3/2 Under current protection inhibited or in use
1 = under current protection inhibited (setting displayed "---"), 0 = under current protection in use 1 x2= 2
SGF3/3 Earth-fault protection inhibited or in use
1 = earth-fault protection inhibited (setting displayed "---") , 0 = earth-fault protection in use 0 4= 0
SGF3/4 Unbalance protection inhibited or in use
1 = unbalance protection inhibited (setting displayed "---"), 0 = unbalance protection in use 0 8= 0
SGF3/5 Phase reversal protection inhibited or in use
1 = phase reversal not in use, 0 = phase reversal in use 1 x 16 = 16
SGF3/6 Stall protection based on the thermal stress supervision, I s2 ts or a definite time overcurrent
function, Is & ts. 0 = thermal stress monitoring, 1 = definite time overcurrent 0 32 = 0
SGF3/7 Start criteria for stage I s2 x ts
0 = stage is active only during motor start-up, 1 = stage starts when current exceeds I s > 0 x 64 = 0
SGF3/8 Setting of short-circuit protection doubled during a motor start-up
0 = no doubling, 1 = doubling feature active 1 128 = 128

= 146
SGF4/1 Inhibition of stage Io > when one or several phase currents
SGF4/2 exceed the motor full load current as follows:

SGF4/2 = 0 SGF4/2 = 1
SGF4/1 = 0 no inhibit inhibit at 4 times FLC SGF4/1 = 0 x1= 0
SGF4/1 = 1 inhibit at 6 times FLC inhibit at 8 times FLC SGF4/2 = 0 2= 0
SGF4/3 Selection of ambient temperature
0 = set ambient temperature, 1 = ambient temperature from RTD6 0 x4= 0
( If the RTD card has not been installed, the set ambient temperature will be used )

= 0

Remarks:

Unbalance Protection
10.00
I2 (x IN)

1.00

0.10
0.10 1.00 10.00 100.00 1000.00 10000.00
Operate time (s)

Remarks:
Project name: Protection device:
Type here REM 610
Customer reference:
Type here
Title:
Setting proposal for Motor Protection
A BB
Motor: Prepared by: Sheet:
400 LKB 6/12/2003 Type name here 3/5
Checked by: Revision:
6/12/2003 Type name here A

Operation Characteristics

Relay trip curve: cold


Relay trip curve: hot
Start-up supervision
Feedwater pump
Column J
Relay trip curve: hot
Relay trip curve: cold
Start-up supervision
Feedwater pump
Column J

10000

1000

100
Time [s]

10

0.1

0.01
1 10
I/In

Remarks:
Project name: Protection device:
Type here REM 610
Customer reference:
Type here
Title:
Setting proposal for Motor Protection
A BB
Motor: Prepared by: Sheet:
400 LKB 6/12/2003 Type name here 4/5
Checked by: Revision:
6/12/2003 Type name here A

Us ed thermal c apac ity [% ]

Cold starts
100% 10.00

90% 9.00

80% 8.00

70% 7.00

I/In
60% 6.00

50% 5.00

40% 4.00

30% 3.00

20% 2.00

10% 1.00

0% 0.00
0 0 0 0 0 1 1 1 1 1 1
Time [s]

Remarks:
Us ed thermal c apac ity [% ]

Prior load
100% 10.00

90% 9.00

80% 8.00

70% 7.00

I/In
60% 6.00

50% 5.00

40% 4.00

30% 3.00

20% 2.00

10% 1.00

0% 0.00
0 0 0 0 0 1 1 1 1 1 1
Time [s]

Remarks:
Us ed thermal c apac ity [% ]

100% Hot starts 10.00

90% 9.00

80% 8.00

70% 7.00
I/In

60% 6.00

50% 5.00

40% 4.00

30% 3.00

20% 2.00

10% 1.00

0% 0.00
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00
Time [s]

Remarks:
Project name: Protection device:
Type here REM 610
Customer reference:
Type here
Title:
Setting proposal for Motor Protection
A BB
Motor: Prepared by: Sheet:
400 LKB 6/12/2003 Type name here 5/5
Checked by: Revision:
6/12/2003 Type name here A

Swithes RTD Sensors Setting range Setting


SGF Checksum, SGF 1 = 127 Alarm value Ta1> 0200 C
Checksum, SGF 2 = 255 Operate time ta1> 1100 s
Checksum, SGF 3 = 146 Trip value Tp1> 0200 C
Checksum, SGF 4 = 0 Operate time tp1> 1100 s
Checksum, SGF 5 = 255
Alarm value Ta2> 0200 C
Trip value Tp2> 1100 s
SGB Checksum, SGB 1 = 8191 Operate time Tp2> 0200 C
Checksum, SGB 2 = 8191 Operate time tp2> 1100 s
Checksum, SGB 3 = 8191
Checksum, SGB 4 = 8191 Alarm Value Ta3> 0200 C
Checksum, SGB 5 = 8191 Operate time ta3> 1100 s
Trip value Tp3> 0200 C
SGR Operate time tp3> 1100 s
Checksum, SGR 1 = 524287
Checksum, SGR 2 = 524287 Alarm Value Ta4> 0200 C
Checksum, SGR 3 = 524287 Operate time ta4> 1100 s
Checksum, SGR 4 = 524287 Trip value Tp4> 0200 C
Checksum, SGR 5 = 524287 Operate time tp4> 1100 s

SGL Alarm Value Ta5> 0200 C


Checksum, SGL 1 = 1048575 Operate time ta5> 1100 s
Checksum, SGL 2 = 1048575 Trip value Tp5> 0200 C
Checksum, SGL 3 = 1048575 Operate time tp5> 1100 s
Checksum, SGL 4 = 1048575
Checksum, SGL 5 = 1048575 Alarm Value Ta6> 0200 C
Checksum, SGL 6 = 1048575 Operate time ta6> 1100 s
Checksum, SGL 7 = 1048575 Trip value Tp6> 0200 C
Checksum, SGL 8 = 1048575 Operate time tp6> 1100 s

Thermistors Trip value Thp1> 0.130 k


Trip value Thp2> 0.130 k

Operate time of CBFP 0.160 s

Remarks:
A BB
A BB
A BB
A BB
A BB
Operation Characteristics
Relay trip curve: cold
Relay trip curve: hot
Start-up supervision
Feedwater pump
Column J
Empty
Empty
Empty
Empty
Empty
10000

1000

100
Time [s]

10

0.1

0.01
1 10
I/In
Cold condition starts

100.00%
Used Thermal Capacity [%]

90.00%

80.00%

70.00%

60.00%

50.00%

40.00%

30.00%

20.00%

10.00%

0.00%
0 0 0 0 0 1 1 1 1 1 1
Time [sec]
Prior Load
Used Thermal Capacity [%]

100.00%

90.00%

80.00%

70.00%

60.00%

50.00%

40.00%

30.00%

20.00%

10.00%

0.00%
0 0 0 0 0 1 1 1 1 1 1
Time [sec]
Hot condition starts
Used Thermal Capacity [%]

100.00%

90.00%

80.00%

70.00%

60.00%

50.00%

40.00%

30.00%

20.00%

10.00%

0.00%
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00
Time [sec]
Cycles
Used Thermal Capacity [%]

100.00%

90.00%

80.00%

70.00%

60.00%

50.00%

40.00%

30.00%

20.00%

10.00%

0.00%
0 0 0 0 0 1 1 1 1 1 1
Time [sec]