REFERENCES/STANDADS

OBRAS DE SALIDA - TDF - SCC -CODE -DESCRIPTION

DE TABLERO DE SERVICIOS T-310


FROM MAIN BOARD ALTERN CURRENT DISTRIBUTION BOARD OBRA SUPERFICIAL LAS LAJAS DIAGRAMA
OUTPUT FOREBAY -TDF - SCC
AUXILIARES-ENTRADA FOREBAY OF AUXILIARY SERVICES-INTAKE FOREBAY 630-SC-PLA-107
SURFACE WORK LAS LAJAS DIAGRAM UNILINEAL
400/230 CA (T-210) 400/230 AC (T-210) LOW VOLTAGE FOREBAY OUTLET
DIAGRAMA UNIFILAR DE SERVICIOS AUXILIARES
6310-EL-PLA-7011) 6310-EL-PLA-7021 CORRIENTE CONTINUA
DIRECT CURRENT ANCILLARY SERVICES SINGLE LINE
DIAGRAM

T-310

NOTAS - NOTES

1. EL CONTRATISTA FABRICARA Y PROBARA LOS


TABLEROS COMPLETOS,ESTOS DEBEN SER A PRUEBA DE POLVO,
CHORRO DE AGUA Y NIEVE TIPO IP65 CONFORME A LA NORMA DIN
40050 O NEMA 4.
2. EL CONEXIONADO INTERIOR DE CADA TABLERO SER EN
CABLE THHN CON UNA MINIMA DE 14 AWG Y
INTERRUPTOR QUE LO PROTEGE.
3. TODOS LOS CONDICTORES LLEVAR
MEDIANTE MARCAS ADHESIVAS Y SE POR MEDIO DE

/ SYMBOLS 4. TODOS LOS INTERRUPTORES DE LOS TABLEROS


TERMOMAGNETICA DE LOS CALIBRES INDICADOS Y
CON

CAPACIDADES DE RUPTURA DE 15 KA, PARA 400(V),


NORMAS IEC 157-1 (P1) 6 UL 489.
5. LOS CONTACTORES QUE EL CONTRATISTA
CARGA DE 15 KW CON BOBINA DE 24 DC PARA LOS CALIBRES INDICADOS, PARA
CHARGE OF 15 KW SERVICIOS AC-3.
6. EL GABINETE SE DE TAL FORMA QUE LOS EQUIPOS
TENGAN UNA RECOMENDADA POR EL
FABRICANTE.PARA PERMITIR UNA ADECUADA Y
1 DE 2 CERRADO
7. TODOS LOS EQUIPOS DE COMANDO Y SE
CON TAPA CUBRE EQUIPOS Y TODAS LAS BARRAS
1 OF 2 CLOSED EXPUESTAS DEBEN SER PROTEGIDAS CONTRA CONTACTOS
AUTOMATIC SWITCHING ACCIDENTALES, DE ACRILICO CON UNA DE
PELIGRO.
8.
9. SE CONSIDERAR ESPACIO NECESARIO PARA BORNES DE

PROTECCION DE MINIMA TENSION


10. (NA) NORMALMENTE ABIERTO
UNDER VOLTAGE PROTECTION 11. (NC) NORMALMENTE CERRADO

1. BOARDS WILLBE DESIGN,BUIT AND TASTED BY THE


CONTRACTOR,AND SHALL BE DUSPROOF,WATERPROOF AND
SNOWPROOF.BOARDS MUST BE IP66 TYPE ACCORDING TO DIN
VOLTIMETRIC SELECTOR 40050 OR NEMA 4 STANDARD.
2. INSIDE BOARD CONEXION SHALL BE WITH A MINIMUM 14AWG WIRE
THHN TYPE,AND WITH PROTECTION SWITCH.
3. WIRES SHALL BE IDENTIFIED WITH ADHESIVE MARKS,AND WIRING
THROUGH PVC WIREWAYS.
4. CIRCUITS BREAKERS SHALL HAVE THERMOMAGNETIC
POINT PROTECTION TEST PROTECTION FOR SPECIFIED GAUGES,AND 16 KA BREAKING
CAPACITY FOR 400 (V), ACCORDING TO STANDARDS IEC 157-1 (P1)
6 UL 489.
5. CONTACTOR COIL SHALL BE 24 DC FOR SPECIFIED GAUGES, FOR
AC.3 SERVICES.
TIERRA/ POINT INDICATION TEST 6. CABINET DIMENSIONS
RECOMMENDATIONS TO ALLOW
SHALL FOLLOW MAKERS
GOOD OPERATION AND
VENTILATION UNDER LOCAL CLIMATE.
GROUND (N) 7. CONTROL AND SIGNALING EQUIPMENT SHALL BE INSTALLED WITH
LIDS.ALL EXPOSED BARS SHALL BE COVERED WITH ACRYLIC TO
THERMAL AND MAGNETIC PROTECTION PREVENT ACCIDENTS,AND MARKED "DANGER ".
8. THE BOARD MUST HAVE AN INTERNAL HEATER.
9. IT MUST CONSIDER ENOUGH SPACE FOR THE PLC SIGNAL
TERMINALS.
VOLTIMETRO 10. NORMALLY OPEN (NO)
11. NORMALLY CLOSED (NC)
VOLTMETER

MOTOR
MOTOR

SELECTOR REVISIONES- REVISIONS


SELECTOR SWITCH

/
GROUND TRANSFORMADOR DE CORRIENTE
CURRENT TRANSFORMER

MEDIDOR MULTIFUNCIONAL
MULTIFUNCTIONAL METER

LOW VOLTAGE CABLE


A00 15-03-17 SZE MGM MOJ FUP
FIRST EMISSION
FECHA
REV PROY REV REV APR APR
DATE DESCRIPTION

THREE-PHASE TRANSFORMER
630-COM-023 OUTLET

TRIANGLE STAR CONNECTION


RADIATOR GATE
EMERGENCY GATE
ELECTRIC WINCHE

ELECTRIC WINCHE

CHARGE CAMERA

COMMUNICATION
POWER OUTLET

ALIMENTADOR OBRAS FEEDER WORK

ALTO MAIPO
TECLE MOTOR

SWITCH FLOW
AVAILABLE 1

AVAILABLE 2

AVAILABLE 3

AVAILABLE 4
GEARMOTOR

EXTRACTOR
630-MOT-024

630-MOT-024

630-MOT-024

AUXILIARY
MOTOR # 1

ICER OF

SERVICES
CHARGER
LIGHTING

LIGHTING
BATTERY

HEATING

HEATING

CABINET

CAMERA
CON MANDO MOTORIZADO Y MANUAL,
CON MECANISMO DE DISPARO LIBRE,

AIR
CON
630-COM-023 SALIDA
WINCHE ELECTRICO

CAMARA DE CARGA

DISPARO REMOTO, UN CONTACTO

CALEFACCION DE

CAUDALIMETROS
DE COMPUERTAS
MOTOREDUCTOR

DESHIELADORES

AUXILIAR DE CIERRE Y OTRO DE


EMERGENCIA 61

COMUNICACION

EXTRACTOR DE
CARGADOR DE

APERTURA. -AREA
CALEFACCION

TABLEROS DE
DISPONIBLE 1

DISPONIBLE 2

DISPONIBLE 3

DISPONIBLE 4
RADIADORES
COMPUERTA

ALUMBRADO

SISTEMA LAS LAJAS


630-MOT-024

630-MOT-024

630-MOT-024

CAMARA DE
6300
AUXILIARES
ENCHUFES

SERVICIOS
MOTOR # 1

MOTOR # 2

BATERIAS

TRIPOLAR CONNECTION DEVICE, WITH


OBRAS SUPERFICIALES AUCAYES
MOTORIZED AND MANUAL CONTROL, WITH
FREE TRIGGER MECHANISM, THERMAL
SURFACE WORKS AUCAYES

AIRE
OVERLOAD, MAXIMUM CURRENT, MANUAL
DIAGRAMA UNIFILAR DE SERVICIOS AUXILIARES CA Y CC
TRIGGER WITH
AC & DC AUXILIARY POWER SUPPLY SINGLE LINE DIAGRAM
RETAINER, REMOTE TRIGGER, AN
AUXILIARY CLOSURE CONTACT AND SISTEMA DE CORRIENTE ALTERNA - OBRA DE SALIDA
OTHER OPENING. AC POWER SUPPLY - FOREBAY OUTLET
(UNIFILAR REPRESENTATION) ESCALA-SCALE: NOMBRE-NAME FIRMA-SIGNATURE FECHA-DATE
PROY. F.MUNOZ 15-03-2017
INDICADAS REV.S. E.SULLCA 15-03-2017
AS SPECIFIED REV.M.S P.MALDONADO 15-03-2017
LIDER J.MORENO 15-03-2017
APR. P.FURRER 15-03-2017
-DRAWING NUMBER: REV.-REV.

6310-EL-PLA-7021 A00