www.hilti-me.com Profis Anchor 2.6.

4
Company: Page: 1
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 4/4/2017
E-Mail:

Specifier's comments:

1 Input data
Anchor type and diameter: HVZ M16x105
Effective embedment depth: hef = 105 mm, hnom = 125 mm
Material: 8.8
Evaluation Service Report: ETA 03/0032
Issued I Valid: 6/4/2013 | 6/4/2018
Proof: Design method ETAG (No. 001 Annex C/2010)
Stand-off installation: eb = 0 mm (no stand-off); t = 16 mm
Anchor plate: ; E = 210000.00 N/mm2; fyk = 275.00 N/mm2; gMs = 1.100
lx x ly x t = 210 mm x 210 mm x 16 mm; (Recommended plate thickness: calculated (13 mm))
Profile: Square hollow; (L x W x T) = 100 mm x 100 mm x 5 mm
Base material: cracked concrete, C35/45, fcc = 45.00 N/mm2; h = 500 mm, Temp. short/long: 30/40 C
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: reinforcement spacing < 150 mm (any ) or < 100 mm ( <= 10 mm)
with longitudinal edge reinforcement d >= 12

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.6.4
Company: Page: 2
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 4/4/2017
E-Mail:

2 Load case/Resulting anchor forces y


Load case: Design loads
3 4

Anchor reactions [kN]


Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 15.000 7.500 0.000 7.500
2 15.000 7.500 0.000 7.500 x
Tension
3 15.000 7.500 0.000 7.500
4 15.000 7.500 0.000 7.500
max. concrete compressive strain: - []
max. concrete compressive stress: - [N/mm2]
resulting tension force in (x/y)=(0/0): 60.000 [kN]
resulting compression force in (x/y)=(0/0): 0.000 [kN] 1 2

3 Tension load (ETAG, Annex C, Section 5.2.2)


Load [kN] Capacity [kN] Utilization bN [%] Status
Steel Strength* 15.000 60.000 25 OK
Pullout Strength* N/A N/A N/A N/A
Concrete Breakout Strength** 60.000 75.495 80 OK
Splitting failure** N/A N/A N/A N/A
* anchor having the highest loading **anchor group (anchors in tension)

3.1 Steel Strength


NRk,s [kN] gM,s NRd,s [kN] NSd [kN]
90.000 1.500 60.000 15.000

3.2 Concrete Breakout Strength


Ac,N [mm2] A0c,N [mm2] ccr,N [mm] scr,N [mm]
216225 99225 158 315
ec1,N [mm] yec1,N ec2,N [mm] yec2,N ys,N yre,N k1
0 1.000 0 1.000 1.000 1.000 7.200
N0Rk,c [kN] gM,c NRd,c [kN] NSd [kN]
51.966 1.500 75.495 60.000

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.6.4
Company: Page: 3
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 4/4/2017
E-Mail:

4 Shear load (ETAG, Annex C, Section 5.2.3)


Load [kN] Capacity [kN] Utilization bV [%] Status
Steel Strength (without lever arm)* 7.500 40.800 19 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 30.000 150.989 20 OK
Concrete edge failure in direction y+** 30.000 531.859 6 OK
* anchor having the highest loading **anchor group (relevant anchors)

4.1 Steel Strength (without lever arm)


VRk,s [kN] gM,s VRd,s [kN] VSd [kN]
51.000 1.250 40.800 7.500

4.2 Pryout Strength


Ac,N [mm2] A0c,N [mm2] ccr,N [mm] scr,N [mm] k-factor
216225 99225 158 315 2.000
ec1,V [mm] yec1,N ec2,V [mm] yec2,N ys,N yre,N
0 1.000 0 1.000 1.000 1.000
N0Rk,c [kN] gM,c,p VRd,c1 [kN] VSd [kN]
51.966 1.500 150.989 30.000

4.3 Concrete edge failure in direction y+


lf [mm] dnom [mm] k1 a b
105 18.0 1.700 0.013 0.031
c1 [mm] c'1 [mm] Ac,V [mm2] A0c,V [mm2]
9925 6617 5500000 197011250

ys,V yh,V ya,V ec,V [mm] yec,V yre,V


0.728 4.455 1.000 0 1.000 1.200
V0Rk,c [kN] gM,c VRd,c [kN] VSd [kN]
7342.556 1.500 531.859 30.000

5 Combined tension and shear loads (ETAG, Annex C, Section 5.2.4)


bN bV a Utilization bN,V [%] Status
0.795 0.199 1.500 80 OK
a a
bN + bV 1

6 Displacements (highest loaded anchor)


Short term loading:
NSk = 11.111 [kN] dN = 0.136 [mm]
VSk = 11.111 [kN] dV = 0.929 [mm]
dNV = 0.938 [mm]
Long term loading:
NSk = 11.111 [kN] dN = 0.452 [mm]
VSk = 11.111 [kN] dV = 1.393 [mm]
dNV = 1.464 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.6.4
Company: Page: 4
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 4/4/2017
E-Mail:

7 Warnings
Load re-distributions on the anchors due to elastic deformations of the anchor plate are not considered. The anchor plate is assumed to be
sufficiently stiff, in order not to be deformed when subjected to the loading!

Input data and results must be checked for agreement with the
existing conditions and for plausibility!
Checking the transfer of loads into the base material is required in accordance with ETAG 001, Annex C(2010)Section 7! The software
considers that the grout is installed under the anchor plate without creating air voids and before application of the loads.
The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 4.1 of ETAG 001, Annex C! For larger
diameters of the clearance hole see Chapter 1.1. of ETAG 001, Annex C!
The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.6.4
Company: Page: 5
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 4/4/2017
E-Mail:

8 Installation data
Anchor plate, steel: ; E = 210000.00 N/mm2; fyk = 275.00 N/mm2 Anchor type and diameter: HVZ M16x105
Profile: Square hollow; 100 x 100 x 5 mm Installation torque: 0.090 kNm
Hole diameter in the fixture: df = 18 mm Hole diameter in the base material: 18 mm
Plate thickness (input): 16 mm Hole depth in the base material: 125 mm
Recommended plate thickness: calculated (13 mm) Minimum thickness of the base material: 160 mm
Drilling method: Hammer drilled
Cleaning: Manual cleaning of the drilled hole according to instructions for use is required.

8.1 Recommended accessories

Drilling Cleaning Setting


Suitable Rotary Hammer Manual blow-out pump HVA square drive shafts
Properly sized drill bit Torque wrench
y

105 105

30
3 4

105
150

x
105

1 2
30

30 150 30

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y
1 -75 -75 9925 1075 925 10075
2 75 -75 10075 925 925 10075
3 -75 75 9925 1075 1075 9925
4 75 75 10075 925 1075 9925

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.6.4
Company: Page: 6
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 4/4/2017
E-Mail:

9 Remarks; Your Cooperation Duties


Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted
prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the
data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be
put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly
with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an
aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or
suitability for a specific application.
You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

You might also like