Professional Documents
Culture Documents
Seismic Qualification: Acceleration
Seismic Qualification: Acceleration
Seismic Qualification
Acceleration
Method of Analysis
A numerical analysis involving the Finite-Element-Method will be carried out. Choosen calculation
method is the Static-Coefficient-Analysis according to IEC 62271-207, 6.3.4, which leads, compared to
other methods, to a notably conservative nature of the end results, by regarding maximum seismic
response from response spectrum and an additional static coefficient kst=1.5.
Vertical avd=kstav=1.13
Loadcases
In static calculations seismic loads are added to permanent loads only. Other exceptional loads
(e.g. short-circuit forces,switching forces) and loads which frequently happen (e.g. wind) shall not be
considered at the same time. Thus following loadcombinations will be used together with earthquake:
- Dead Load + Loads by thermal expansion + Static Conductor Tension + Earthquake Load in X
+/- Earthquake Load in Z
- Dead Load + Loads by thermal expansion + Static Conductor Tension + Earthquake Load in Y
+/- Earthquake Load in Z
with X and Y as horizontal directions and Z as the vertical one.