Triant A Fill Ou 2017

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 13

Construction and Building Materials 133 (2017) 113

Contents lists available at ScienceDirect

Construction and Building Materials


journal homepage: www.elsevier.com/locate/conbuildmat

An innovative structural and energy retrofitting system for URM walls


using textile reinforced mortars combined with thermal insulation:
Mechanical and fire behavior
Thanasis C. Triantafillou , Kyriakos Karlos, Kalliopi Kefalou, Eirini Argyropoulou
Univ. of Patras, Dept. of Civil Engrg., Univ. of Patras, Patras GR-26504, Greece

h i g h l i g h t s

 An innovative system for both structural and energy retrofitting of masonry walls is proposed.
 The new system involves the combination of textile reinforced mortar (TRM) and thermal insulation.
 In terms of strength and deformation capacity, the proposed system is better than the use of TRM alone.

a r t i c l e i n f o a b s t r a c t

Article history: The application of a new system, which combines textile reinforced mortars (TRM) and thermal insulat-
Received 1 November 2016 ing materials as a means of both structural (including seismic) and energy retrofitting of masonry walls is
Received in revised form 9 December 2016 experimentally investigated in this study. Medium scale tests were carried out on 17 masonry walls sub-
Accepted 10 December 2016
jected to out-of-plane bending. Several parameters were investigated, including the use of fire-resistant
(cement-based) versus polymer-based insulating material, one sided versus two-sided insulation and/or
TRM jacketing, placement of the TRM outside the insulation or in a sandwich form (over and under the
Keywords:
insulation) and the displacement amplitude of the loading cycles. From the results obtained in this study
Energy retrofitting
Fire
the authors believe that TRM jacketing may be combined effectively with thermal insulation, which can
Masonry be fire-resistant too.
Out-of-plane bending 2016 Elsevier Ltd. All rights reserved.
Seismic retrofitting
Textile reinforced mortar
Thermal insulation

1. Introduction and background by current seismic design standards, and in non-seismic areas,
e.g. due to change of usage and/or the introduction of more strin-
Masonry wall construction is one of the oldest construction gent design requirements.
types found worldwide. Masonry walls have been proven to be Numerous techniques have been developed aiming at increas-
prone to failure during high or moderate intensity earthquakes ing the strength and/or deformation capacity of masonry walls,
or high wind pressure, hence they represent a significant hazard including the use of metallic or polymer-based grid reinforced sur-
to life safety. Moreover, structural decay due to ageing or cumula- face coatings, shotcrete overlays, internal or external prestressing
tive seismic-induced damage poses a direct threat to the preserva- with steel ties, externally bonded or near-surface mounted fiber
tion and safeguarding of masonry structures that comprise an reinforced polymers (FRP) and textile reinforced mortar (TRM)
important part of many countries cultural heritage. Thereby, there jacketing. TRM-based solutions for masonry structures are becom-
is an urgent need for upgrading existing masonry structures, both ing increasingly promising, as they combine the favorable proper-
in seismic areas, where structures designed according to old seis- ties offered by FRP systems (e.g. high strength and stiffness to
mic codes have to meet upgraded performance levels demanded weight ratio, high deformation capacity, corrosion resistance, ease
and speed of application and minimal change in the geometry)
while addressing most of the problems associated with the use
Corresponding author. of organic resins, namely: poor behavior at elevated temperatures,
E-mail addresses: ttriant@upatras.gr (T.C. Triantafillou), karloskyriakos@gmail.
incompatibility with substrates, combustibility, high costs of
com (K. Karlos), kalliopi.kefalou@gmail.com (K. Kefalou), eirini.argyr@gmail.com
(E. Argyropoulou). epoxies, lack of breathability, potential hazards for the workers,

http://dx.doi.org/10.1016/j.conbuildmat.2016.12.032
0950-0618/ 2016 Elsevier Ltd. All rights reserved.
2 T.C. Triantafillou et al. / Construction and Building Materials 133 (2017) 113

Nomenclature

K stiffness T temperature; time


P
max maximum load in the push direction d
u displacement at failure in the push direction
P
max maximum load in the pull direction d
u displacement at failure in the pull direction

difficulty to conduct post-earthquake assessment behind FRP jack- Textile reinforced mortar (TRM) jacketing has minimal, if any,
ets, reversibility requirements, etc. thermal insulation capacity, while external or internal insulation
The TRM system, also known as TRC (textile reinforced con- has no load bearing capacity. In this paper the authors propose,
crete) or FRCM (fabric reinforced cementitious matrix), comprises for the first time, the combination of the two systems into a single
an open weaved fabric made of long woven, knitted or even unwo- one, which will provide both structural (including seismic) and
ven fiber rovings (e.g. glass, basalt, carbon, steel) in at least two energy retrofitting. In this new system, illustrated in Fig. 1, the
(typically orthogonal) directions, and an inorganic mortar matrix TRM is combined with the insulating material as a single unit,
[1]. The density, that is the quantity of the spacing of rovings in which may be either in the form of a prefabricated board or con-
each direction can be controlled independently, thus affecting structed in situ. Depending on the loading, the aesthetics and the
the mechanical characteristics of the open weaved fabric and the constructability requirements, the system may be placed either
degree of penetration of the mortar matrix through the woven on both sides of existing masonry walls (preferably, if subjected
mesh. to out-of-plane cyclic loading) or on one side. The TRM may be
TRM systems were used by [2,3] as a means of increasing the placed outside the insulating material, inside, that is between the
strength of tuff masonry wallettes tested in diagonal compression, insulation and the masonry wall, or on both faces (outside and
by [4,5] in the form of confining jackets for small scale rectangular inside) of the insulation. All the above are investigated experimen-
column-type masonry specimens tested in uniaxial compression tally in the present study for the case of masonry walls subjected to
and by [6,7] as a means of seismic retrofitting of unreinforced out-of-plane cyclic loading. The study includes fire testing of some
masonry walls subjected to in-plane or out-of-plane loading. Addi- of the masonry walls prior to mechanical testing.
tional studies focused on bond testing and behavior [811], in-
plane loading of walls [12], out-of-plane loading of walls [13,14],
strengthening of arches [15] and seismic retrofitting of infill 2. Experimental program
masonry walls [16,17].
In addition to structural (including seismic) retrofitting, given 2.1. Scope and method
the high energy consumption associated to old buildings and their
significant environmental impact, there is a strong need for effec- The main objective of the experimental program was to provide
tive solutions for the building envelope energy retrofitting. an understanding on the effectiveness of externally applied TRM
Towards this goal, a wide range of solutions has been proposed, combined with thermal insulation as both structural and energy
with external and internal insulations becoming increasingly pop- retrofitting material for masonry walls subjected to out-of-plane
ular, due to high energy savings, the quick and easy application and cyclic loading. The investigation was carried out on two series of
the low cost, e.g. [18,19]. Various types of thermal insulation medium-scale, single-wythe, fired clay brick wallettes comprising
boards are currently used in external and internal insulation, running bond courses. The masonry wall in all specimens mea-
mostly made by expanded polystyrene (sintered or extruded), sured (approximately) 1500 mm in height, 400 mm in width and
expanded polyurethane and mineral wool. The finishing typically 85 mm in thickness. The specimens were subjected to cyclic out-
involves continuous and applied during placing mineral or poly- of-plane bending, such that the plane of failure would form per-
meric renders and coatings, e.g. [20,21], although some kinds of pendicular to the bed joints (e.g. as in typical vertically supported
discontinuous tile finishing (applied on site instead of the render) walls loaded out-of-plane). Series A specimens were insulated
has recently been proposed, e.g. [22]. using expanded polystyrene with a density equal to 29 kg/m3
and a thermal conductivity coefficient equal to kp = 0.029 W/m K.
Series B specimens were insulated using a fire-resistant insulation
material made of foamed cement with a density equal to 115 kg/
m3 and a thermal conductivity coefficient equal to kc = 0.045 W/
m K; specimens in this series were subjected to fire testing prior
to mechanical testing. Note that in this study the objective was
to prove the concept of structural alongside energy retrofitting,
hence the details regarding the energy performance of retrofitted
versus unretrofitted walls is out of scope of this paper.
All specimens were constructed in the laboratory by an experi-
enced mason using perforated bricks (185  85  60 mm), with
the perforations running parallel to the units length. For all spec-
imens, the first row of bricks was laid on a 10 mm thick horizontal
layer of mortar and all joints (bed and head) were approximately
10 mm thick.
Whereas all specimens received the same amount of structural
retrofitting (four layers of textile), the investigation considered the
following key parameters: cement-based versus polymer-based
(not fire-resistant) insulating material; one sided versus two sided
Fig. 1. Schematic view of proposed structural and energy retrofitting system on one insulation; one sided versus two sided TRM jacketing; placement
side of the masonry wall. of the TRM jackets outside the insulation, between the insulation
T.C. Triantafillou et al. / Construction and Building Materials 133 (2017) 113 3

and the masonry or both outside the insulation and between the the TRM and the masonry (Fig. 2g); (ii) one specimen (F_i2M2i)
insulation and the masonry; thickness of the fire-resistant insulat- retrofitted on both sides with TRM containing two layers of textile
ing material; and the displacement amplitude of the loading cycles. and one layer of fire-resistant insulating material on both sides,
outside the TRM (Fig. 2h); (iii) one specimen (F_i2iMi2i) retrofitted
on both sides with two layers of fire resistant insulating material
2.2. Test specimens and materials
and TRM containing two layers of textile between the two insulat-
ing layers (Fig. 2i); (iv) one specimen (F_2Mi2) with one layer of
All specimens were constructed using ridge-faced, 6-hole, hori-
fire-resistant insulating material on one side (interior) and TRM
zontally perforated clay bricks, supplied by a local manufacturer,
jackets with two layers of textile on the outside (Fig. 2j); and (v)
and a general-purpose masonry cement mortar. One specimen
one specimen (F_2M2i_th) retrofitted on both sides with TRM con-
was used as control (M), without TRM or insulation (Fig. 2a). Series
taining two layers of textile and one thicker layer (hence the letters
A included six different designs: (i) specimens 2M2 and 2M2s ret-
th at the end of the specimens notation) of fire-resistant insulat-
rofitted on both sides with TRM containing two layers of textile
ing material on one side (interior) (Fig. 2k).
and no insulation (Fig. 2b); (ii) specimens 2iMi2 and 2iMi2s retro-
A total of 17 tests were performed. The notation of specimens in
fitted on both sides with TRM containing two layers of textile and
Series A comprises a series of numbers and letters. The numbers (1
one layer of insulating material on both sides, between the TRM
or 2) indicate the number of layers in the textile, i stands for
and the masonry (Fig. 2c); (iii) specimens 1i1M1i1 and 1i1M1i1s
insulation and M stands for masonry. Moreover, the sequence
retrofitted on both sides with TRM containing one layer of textile,
of numbers and letters represents the sequence of the different
one layer of insulating material and a second TRM jacket with one
materials in each specimen. For instance, 2M2 = two-layered TRM
layer of textile, such that the TRM forms the faces of a sandwich
masonry two-layered TRM, 2iMi2 = two-layered TRM insula-
system with the insulation as the core material (Fig. 2d); (iv) spec-
tion masonry insulation two-layered TRM, 2iiM2 = two-
imens 2ii2M and 2ii2Ms retrofitted on one side with a sandwich
layered TRM - two layers of insulation masonry two-layered
system comprising TRM faces with two layers of textile and a core
TRM etc. The symbol s at the end of the specimens notation
with two layers of insulation material (Fig. 2e); (v) specimens
denotes small displacement amplitude (1 mm). The notation of
2iiM2 and 2iiM2s with two layers of insulation material on one
specimens in Series B follows the same logic; the letter F at the
side and TRM jackets with two layers of textile on the outside
beginning denotes fire, as all specimens in this series were tested
(Fig. 2f); and (vi) specimen 2iMi2_na as in (ii) above (Fig. 2c), but
in fire prior to cyclic loading. The control specimen is denoted as M
with retrofitting materials non-anchored (hence the letters
(masonry only).
na at the end of the specimens notation), i.e. not extending all
The mean compressive strength of the masonry units in direc-
the way to the end of the walls, so that they were not clamped
tions parallel and perpendicular to the perforations was derived
between the end supports and the masonry. All specimens in Series
from three compressive tests in each case. The bearing surfaces
A, except the ones in design (vi), that is the one with non-
of the individual brick specimens were capped using a self-
anchored retrofitting, were tested in pairs, corresponding to two
leveling, rapid hardening cement mortar. The average values
different displacement amplitudes (1 mm and 2 mm) of the load-
obtained were 12.9 MPa and 8.8 MPa for directions parallel and
ing cycles.
perpendicular to the perforations, respectively.
Series B included five different designs, subjected to fire testing
The cement:lime:sand proportions in the mortar used to bind
prior to mechanical testing: (i) one specimen (F_2iMi2) retrofitted
the bricks were roughly 1:0.5:4.5, by volume. The mortar strength
on both sides with TRM containing two layers of textile and one
was obtained through flexural and compression testing according
layer of fire-resistant insulating material on both sides, between
to [23], using a servohydraulic MTS testing machine. Flexural test-
ing was carried out on 40  40  160 mm hardened mortar prisms,
at an age of 28 days. The prisms were: (i) prepared in steel moulds
with three identical compartments; (ii) cured in the laboratory
until testing, in conditions identical to those for the wall speci-
mens; and (iii) subjected to three-point bending, at a span of
100 mm, with a constant loading rate equal to 5 N/s. The peak load
was recorded and used for the calculation of flexural strength.
Compression testing was carried out on each of the fractured parts
of the prisms used in flexural testing, by means of two 40  40 mm
bearing steel platens placed on top and bottom of each specimen
part, which was carefully aligned so that the load was applied to
the whole width of the faces in contact with the platens. The flex-
ural and compressive strengths obtained from this procedure were
2.2 MPa and 8.3 MPa, respectively (mean values of all prisms
tested).
For the specimens receiving externally bonded strengthening, a
commercial textile with equal quantity of polymer-coated glass
fiber rovings in two orthogonal directions was used (Fig. 3a). The
choice of this type of textile was made due to availability in the
laboratory as well as to account for the possible adverse effect of
the polymer coating on the fire resistance of the system. Each fiber
roving was 3 mm wide and the clear spacing between rovings was
7 mm. The weight of the textile was 300 g/m2 and the nominal
thickness of each layer (based on the equivalent smeared distribu-
tion of fibers) was 0.06 mm. The guaranteed tensile strength of the
Fig. 2. (a) Control specimen; (bf) Series A specimens; and (gk) Series B glass fibers (as well as of the textile, when the nominal thickness is
specimens. used) in each direction, as taken from data sheets of the producer,
4 T.C. Triantafillou et al. / Construction and Building Materials 133 (2017) 113

Fig. 3. (a) Photograph of bi-directional textile used in this study; (b) geometry of TRM coupons tested in tension (dimensions in mm).

was equal to 1400 MPa. The elastic modulus of glass fibers was All textile layers were applied as usual, that is each specimen
74 GPa. was first ground at points where mortar was protruding from the
For the matrix of the TRM a commercial inorganic dry binder brickwork face and brushed clean, then dust and any loose parti-
was used, consisting of cement and polymers at a ratio of approx- cles were removed with high air pressure and, finally, a standard
imately 15:1, by weight. The binder to water ratio was 4:1, by wet lay-up procedure was followed to bond the textile on the
weight, resulting in plastic consistency and good workability with walls, covering the entire surface. The procedure involved the
a retention period of approximately half an hour in ambient tem- application of mortar on the dampened wall surface and the subse-
perature (20 C). The binders flexural and compressive strengths quent bonding of the textile by hand and roller pressure. The mor-
(4.5 MPa and 12 MPa, respectively) were obtained from a proce- tar was also applied in between layers of the textile, on top of the
dure identical to the one described for the general-purpose last textile layer, in between the masonry and the insulating mate-
masonry mortar, using a triplet of mortar prisms taken on the rial, in between layers of the insulating material and in between
day of the strengthening execution. the insulating material and the textile. Hence, the mortar served
The tensile properties of TRM were obtained by testing two as the matrix of the TRM as well as the binding agent of the insu-
pairs of specimens (one pair with a single layer of textile and a sec- lating material.
ond one with two layers) with the geometry shown in Fig. 3b, The insulating material was pre-cut in plates with length and
according to the test setup illustrated in Fig. 4. The average values width equal to the wall surface. The thickness of each layer of
of properties from two tests on TRM coupons with one layer of tex- the insulating material was 20 mm in all cases, except in specimen
tile were as follows: maximum stress 7.56 MPa, ultimate strain F_2M2i_th, which received a much heavier insulating material,
0.8%. The corresponding values for TRM coupons with two layers with a thickness equal to 70 mm, to improve the fire behavior.
of textile were 4.98 MPa and 1.3%. Note that stresses were calcu- Note that given the (smaller than full) scale of the masonry walls,
lated on the basis of the nominal thickness of TRM, taken equal which have a thickness of 85 mm, 20 mm of thermal insulation is a
to 4 mm and 8 mm for one layer and two layers of the textile, reasonable value. In any case, the detailed study of the energy per-
respectively. The reduced (by approximately 34%) capacity of cou- formance of the specimens tested is out of scope of this study.
pons with two layers in comparison to the ones with one layer is Application of the mortar was made in approximately 2 mm
attributed to the non-uniform stressing of the fibers. thick layers with a smooth metal trowel. The textile was pressed
slightly into the mortar, which protruded through all the perfora-
tions between fiber rovings. Of crucial importance in this method
was the application of each mortar layer while the previous one
was still in a fresh state. Curing of the mortar was achieved in room
conditions. Typical photographs of the application method of tex-
tiles and insulating materials on wall specimens are shown in
Fig. 5.
The mean compressive strength of the walls in directions
parallel to the bed joints was measured from three compressive
tests in each case, conducted on small wall assemblages (two
bricks long by six bricks high), measuring 410  85  390 mm
(length  width  height). These masonry prisms were
constructed using the same bricks, mortar and bond type (that is
running bond) as for the rest of the specimens used in the experi-
mental program. It should be noted that all types of wall specimens
were constructed and tested during the same time spans. The sur-
faces of these specimens in contact with the compression platens
were capped using a normal strength cement mortar, in order to
achieve a better load transfer. The compression tests were carried
Fig. 4. Uniaxial tension testing of TRM coupons. out in displacement control mode at a constant loading rate equal
T.C. Triantafillou et al. / Construction and Building Materials 133 (2017) 113 5

Fig. 5. Application of the textile reinforcement and the insulation material: (a) Application of mortar on masonry wall; (b) application of textile; (c) impregnation of textile
with mortar; (d) application of insulation material; (e) application of mortar on top of insulation material; (f) typical cross section of masonry wall.

to 0.1 mm/s, using a 4000 kN loading capacity testing machine. at mid-span (that is along the load application line). The load
Loads were measured from a load cell and displacements were was applied using a vertically positioned 500 kN MTS actuator.
obtained using external linear variable differential transducers At least one week prior to testing six 80 mm wide and 5 mm thick
(LVDTs) with a stroke of 5 mm. The LVDTs were mounted at bands of high strength mortar had been cast on the specimens
mid-height, at a gauge length of approximately 140 mm. The mean faces along all bearing lines (three per side), to compensate for
values of the compressive strength, secant modulus of elasticity (at any surface unevenness and to ensure uniformity of load transfer.
maximum stress) and ultimate strain derived from compressive Displacements were measured at mid-span using an external
loading parallel to the bed joints were 11.30 MPa, 2.61 GPa and rectilinear displacement transducer (of 25 mm stroke capacity)
0.43%, respectively. mounted on one side of the specimen. Data from the load cell
and the displacement transducers (the actuators and the external
2.3. Mechanical tests set-up, instrumentation and procedure one) were recorded using a fully computerized data acquisition
system. The resulting load mid-span displacement and load
All strengthened specimens were subjected to cyclic out-of- piston displacement loops were generated by the system in real
plane loading using a stiff steel frame. The walls were laid horizon- time.
tal (with the bonded surfaces facing upwards and downwards) and All strengthened specimens were tested by applying the load in
were loaded in three-point bending (Fig. 6) at a span of 1.30 m. a quasi-static cyclic pattern of controlled displacements at a rate of
Two pairs of steel hinges were placed at each support (along the 0.1 mm/s. The loading sequence consisted of cycles at a series of
specimens width, at top and bottom) and a third one was placed progressively increasing displacement amplitudes in both direc-
tions (push and pull). The displacement amplitude increment
was either 2 mm or 1 mm, as described above, and a single loading
cycle was applied for each amplitude level. The test was run in a
fully computerized manner and was completed (manually termi-
nated by returning the piston to zero position) when the ultimate
capacity of the wall was reached and a considerable load reduction
was evidenced in either direction (push or pull). The control spec-
imen (M) was tested under monotonically applied loading, in a dis-
placement control mode and at the same rate as for strengthened
specimens.

2.4. Fire tests set-up, instrumentation and procedure

All specimens in Series B were subjected to one-sided fire test-


ing for 90 min inside a 3  3  1.2 m furnace (Fig. 7) according to
[24], so that the mean temperature T (in C) inside the furnace
developed over time t (in min) according to the following
equation:
T 345log10 8t 1 20 1
Fig. 6. Experimental setup for mechanical testing.
6 T.C. Triantafillou et al. / Construction and Building Materials 133 (2017) 113

870 C in specimens F_2iMi2 and F_2Mi2, 340 C in specimens


F_i2M2i and F_i2iMi2i, and 90 C in specimen F_2M2i_th.
Fire resulted in full or partial damage of the TRM on the exposed
face of each wall, depending on the protection provided by the
insulating material. In specimens F_2iMi2 and F_2Mi2, with the
insulation between the TRM and the masonry, the TRM was fully
destroyed (Fig. 8a). In fact specimen F_2Mi2 was so severely dam-
aged that it fractured during handling and transport at the end of
the fire test. In specimens F_i2M2i and F_i2iMi2i, with a 20 mm
thick fire insulation material on top of the TRM, the insulating
material developed cracks (Fig. 8b) and the TRM was partially
damaged. Finally, in specimen F_2M2i_th, with the 70 mm thick
insulating material, damage in the TRM was minimal, if any.
Following fire testing, the specimens were left to cool; a couple
of days later they were subjected to mechanical testing.

3. Results and discussion


Fig. 7. Furnace used for fire testing of walls.

The results are discussed on the basis of the load versus out-of-
While the mean temperature in the furnace reached 1006 C, plane displacement response. Peak load values in the push and pull
temperatures in the TRM on the exposed (to fire) face of each wall directions, P 
max and Pmax , mid-span displacements at failure, du and
were measured through the use of thermocouples as follows: 
du (defined as the point of the load versus mid-span displacement

Fig. 8. (a) Severe damage of TRM after fire testing; (b) cracking of fire-resistant insulating material.

Table 1
Summary of test results.

Specimen notation Peak load (kN) Mid-span displacement Cumulative dissipated Failure mode (failure direction)
at failure (mm)a energy (kN mm) at cycle
Push Pull Push Pull 4 (8b) 7 (14b)
Series A
M 3.42 0.72 Flexural crack
2M2 9.28 9.28 13.78 15.69 154.29 421.19 FRc (both)
2iMi2 11.47 12.45 33.68 22.44 95.77 283.47 Dc (push), FR (pull)
2iMi2_na 10.50 10.25 >28.23 27.48 80.23 221.12 D (pull)
1i1M1i1 12.70 12.21 19.66 20.17 104.80 326.91 FR (both)
2ii2M 20.26 3.66 25.97 24.20 75.06 250.09 FR (push), MCc (pull)
2iiM2 13.92 15.14 17.14 24.70 146.71 470.77 FR (push), D (pull)
2M2s 8.06 9.28 12.31 14.15 208.39 626.35 FR (both)
2iMi2s 12.97 12.17 23.49 23.49 144.79 461.72 FR (both)
1i1M1i1s 10.01 10.01 16.30 15.12 114.48 419.46 FR (both)
2ii2Ms 20.26 3.66 29.64 1.00 121.86 402.59 FR (push)
2iiM2s 11.96 13.18 17.26 18.91 194.51 657.37 FR (push), D (pull)
Series B
F_2iMi2 5.37 2.44 8.57 5.80 66.52 140.66 D (push), MC (pull)
F_i2M2i 10.25 5.62 15.60 2.81 140.89 381.81 FR (both)
F_i2iMi2i 6.01 2.93 15.63 0.80 71.58 185.35 D (push), MC (pull)
F_2Mi2 Fractured during transport
F_2M2i_th 10.74 9.52 15.90 17.70 159.21 447.77 FR (both)
a
Corresponding to sudden load reduction, or to displacement at 80% of the peak load in case of gradual post-peak load reduction.
b
For specimens tested at small displacement amplitude (1 mm).
c
FR = fiber rupture, D = debonding, MC = masonry cracking.
T.C. Triantafillou et al. / Construction and Building Materials 133 (2017) 113 7

envelope curve where either sudden load reduction was detected of a single crack at the brick head joint interfaces closest to the
or a 20% reduction in load was noted in specimens with gradual loading line (mid-span). Visual inspection revealed that the crack
post-peak load reduction), cumulative energy dissipation capacity caused fracture of two bricks and propagated stepwise through
and observed failure modes are given in Table 1, for all specimens. one of the bed joints (in the longitudinal direction). All other (ret-
rofitted) specimens failed at higher loads (see Table 1), as
3.1. Series A mechanical testing only described next.
The load versus mid-span displacement hysteresis loops for
The control specimen (M) of Series A failed under monotonic all retrofitted specimens in Series A are given in Fig. 9; envel-
loading at a maximum load of 3.42 kN, following the formation ope curves are shown in Fig. 10. Specimens 2M2 and 2M2s

Fig. 9. Load versus mid-span displacement hysteresis loops for specimens in Series A.
8 T.C. Triantafillou et al. / Construction and Building Materials 133 (2017) 113

Fig. 9 (continued)

failed due to gradual tensile rupture of the TRM jacket both wall through the insulation and then caused sudden rupture
in the push and in the pull direction (Fig. 9a and b), following of the fibers (Fig. 11c). Failure in specimen 2iMi2_na (Fig. 9e)
the formation of a single crack at mid-span of the masonry was due to debonding, which was caused by the less favor-
wall (Fig. 11a). Specimens 2iMi2 and 2iMi2s (Fig. 9c and d) able anchorage conditions of the retrofitting system (Fig. 11d);
failed in a similar way, except for specimen 2iMi2 in the this fact highlights the importance of anchorage. Specimens
push direction, which failed due to debonding at the interface 1i1M1i1 and 1i1M1i1s (Fig. 9f and g) failed due to rupture
between the masonry and the insulation (Fig. 11b). In these of the fibers, first in the outer faces, due to the higher lever
specimens the middle crack propagated from the masonry arm, and then in the inner ones. As expected, specimens
T.C. Triantafillou et al. / Construction and Building Materials 133 (2017) 113 9

Fig. 10. Envelope curves for specimens in Series A: (a) 2 mm displacement increment; (b) 1 mm displacement increment.

Fig. 11. (a) Fiber rupture at mid-span; (b) debonding at the interface between the masonry and the insulation; (c) flexural cracking through the insulating material; (d)
debonding, as a result of not favorable anchorage conditions; and (e) debonding at the interface between the two insulation layers and between the masonry and the first
insulation layer.

2ii2M and 2ii2Ms (Fig. 9h and i) performed well only in the between the two insulation layers and between the masonry
push direction, because the retrofitting system was one- and the first insulation layer in the pull direction (Fig. 11e).
sided, that is all four layers of the textile were placed on Overall, it is concluded that the new retrofitting system is
the same (tension) side (Fig. 2e); failure in this direction extremely effective. In terms of strength and deformation capac-
occurred due to fiber rupture in the outer face. In the pull ity, the combined use of textile reinforcement with insulation
direction these specimens displayed low strength, as if they material is better than the use of TRM alone. TRM jacketing
were without strengthening, due to the lack of reinforcement without insulation (specimen 2M2) increased the strength by
in the tension zone. Finally, in specimens 2iiM2 and 2iiM2s approximately 170% [(9.283.42 kN)/3.42 kN = 1.71], whereas
(Fig. 9j and k) failure was due to rupture of the fibers in this increase varied from 200% [(10.253.42)/3.42 = 1.99] to
the push direction and due to debonding at the interface 340% [(15.143.42)/3.42 = 3.43] when the (double sided) textile
10 T.C. Triantafillou et al. / Construction and Building Materials 133 (2017) 113

reinforcement was combined with insulation layers, due to the Finally, the comparison of the stiffness versus loading cycles,
increased lever arm of the tension reinforcement. The respective shown also in Fig. 12b and d, confirms the similar behavior of
numbers for specimens type s (small displacement amplitude nearly all specimens, except, of course, for the case of specimens
increment) are 135% [(8.063.42)/3.42 = 1.36], 190% [(10.01 with one-sided TRM and one-sided insulation (2ii2M, 2ii2Ms),
3.42)/3.42 = 1.93] and 285% [(13.183.42)/3.42 = 2.85]. As, which are much stiffer in the push direction and much more com-
expected, jackets with unfavorable bond conditions (specimen pliant in the pull, due to the unsymmetrical positioning of the
2iMi2_na) were less effective; they increased the strength by jacket.
at least 200%, whereas the strength increase in specimen
2iMi2, with favorable bond conditions, was at least 235% 3.2. Series B mechanical testing after fire testing
[(11.473.42)/3.42 = 2.35].
In terms of deformation capacity, as expressed by the mid-span The load versus mid-span displacement hysteresis loops for all
displacement at failure, TRM jacketing combined with insulation retrofitted specimens in Series B are given in Fig. 13; envelope
was always much more effective than the TRM system alone, by curves are shown in Fig. 14.
up to approximately 140145%. Specimen F_2iMi2 (Fig. 13a) displayed poor behavior in the
A comparison of the results for specimens loaded with a small pull direction, because the TRM jacket mobilized in tension in
displacement amplitude increment (1 mm) with the ones for the this direction had already failed during fire testing. Failure in
case of a larger increment (2 mm) shows no systematic effect of this direction occurred due to masonry (flexural) cracking. In
this increment on the response. the push direction failure was due to debonding at the inter-
By comparison of the cumulative dissipated energy given in face between the masonry and the insulation. Specimen
Fig. 12a and c and Table 1 (computed by summing up the area F_i2M2i failed due to tensile rupture of the TRM jacket both
enclosed within the load versus piston displacement curves), it is in the push and in the pull direction, following the formation
concluded that, in general, the energy dissipation capacity of the of a single crack at mid-span of the wall. Partial damage of
combined TRM insulation systems is lower than that of the TRM- the TRM jacket on the fire-exposed face of the wall resulted
alone system, except for the case of one-sided insulation and in reduced capacity when this jacket was subjected to tension,
two-sided TRM (specimens 2iiM2, 2iiM2s), which gives similar that is in the pull direction. Failure in specimen F_i2iMi2i in
values. the push direction was due to debonding at the interface

Fig. 12. (a) Cumulative energy and (b) stiffness versus loading cycles for specimens in Series A, 2 mm displacement increment. (c) Cumulative energy and (d) stiffness versus
loading cycles for specimens in Series A, 1 mm displacement increment.
T.C. Triantafillou et al. / Construction and Building Materials 133 (2017) 113 11

Fig. 13. Load versus mid-span displacement hysteresis loops for specimens in Series B.

in this direction) during fire testing. Finally, specimen


F_2M2i_th failed due to tensile rupture of the TRM jacket at
high loads both in the push and in the pull direction, following
the formation of a single crack at mid-span.
Overall, it is concluded that if the TRM is protected by a
fire-resistant insulating material of proper thickness, the new
retrofitting system is extremely effective after the event of
fire. The effectiveness depends on the thickness of the insula-
tion: 70 mm of a cement-based insulating material provided
full protection (specimen F_2M2_th), whereas 20 mm of the
same material was 40% [(9.525.62)/9.52 = 0.41] less effective,
as concluded by comparing the response of specimens
F_2M2I_th and F_i2M2i. On the other hand, the lack of fire
insulation outside the TRM (specimens F_2iMi2, F_2Mi2) yields
poor behavior.
In terms of deformation capacity, as expressed by the mid-span
displacement at failure, TRM jacketing combined with proper fire
insulation (specimen F_2iMi2) was slightly more effective than
the TRM system alone (specimen 2M2), by approximately 13
15%. A similar conclusion holds for the energy dissipation capacity
Fig. 14. Envelope curves for specimens in Series B.
(Fig. 15a and Table 1), with the increase being only marginally
higher.
Finally, the comparison of the stiffness versus loading cycles,
between the insulating material and the masonry. In the push shown in Fig. 15b, confirms the best performance for the case of
direction the capacity of the specimen was reduced proper fire protection and the poor performance if the TRM jacket
substantially, due to damage of the TRM (subjected to tension is exposed to fire.
12 T.C. Triantafillou et al. / Construction and Building Materials 133 (2017) 113

Fig. 15. (a) Cumulative energy and (b) stiffness versus loading cycles for specimens in Series B.

4. Conclusions [3] A. Prota, G. Marcari, G. Fabbrocino, G. Manfredi, C. Aldea, Experimental in plane


behaviour of tuff masonry strengthened with cementitious matrix-grid
composites, J. Compos. Constr. 10 (3) (2006) 223233.
The present study presents an innovative system for both struc- [4] T. Krevaikas, Strengthening of unreinforced masonry structures with advanced
tural (including seismic) and energy retrofitting of masonry walls, composites, Ph.D. Dissertation, Dept. of Civil Engineering, University of Patras,
Greece, 2005 (in Greek).
involving the combination of textile reinforced mortar (TRM) and [5] A. Nurchi, M. Valdes, Strengthening of stone masonry columns by means of
thermal insulating materials. The system was tested on brick cement-based composite wrapping, in: Proceedings of 3rd International
masonry wallettes subjected to out-of-plane cyclic bending. Some Conference on Composites in Construction, Lyon, France, 2005, pp. 11891196.
[6] C.G. Papanicolaou, T.C. Triantafillou, K. Karlos, M. Papathanasiou, Textile
of the wallettes were subjected to fire testing prior to mechanical
reinforced mortar (TRM) versus FRP as strengthening material of URM walls:
testing, to assess the effectiveness of the new system under realis- in-plane cyclic loading, Mater. Struct. 40 (10) (2007) 10811097.
tic fire conditions. [7] C.G. Papanicolaou, T.C. Triantafillou, M. Papathanasiou, K. Karlos, Textile
Overall, it is concluded that the new retrofitting system not only reinforced mortar (TRM) versus FRP as strengthening material of URM walls:
out-of-plane cyclic loading, Mater. Struct. 41 (1) (2008) 143157.
improves the thermal performance of masonry walls but also is [8] A. DAmbrisi, L. Feo, F. Focacci, Experimental and analytical investigation on
extremely effective as a means of structural retrofitting. In terms bond between carbon-FRCM materials and masonry, Composites: Part B 46
of strength and deformation capacity of walls not subjected to fire, (2013) 1520.
[9] G. De Felice, S. De Santis, L. Garmendia, B. Ghiassi, P. Larrinaga, P.B. Lourenco,
the combined use of textile reinforcement with insulation material D.V. Oliveira, F. Paolacci, C.G. Papanicolaou, Mortar-based systems for
is better than the use of TRM alone. In case of masonry walls sub- externally bonded strengthening of masonry, Mater. Struct. 47 (2014) 2021
jected to fire prior to mechanical loading, the new system is quite 2037.
[10] V. Alecci, M. De Stefano, R. Luciano, L. Rovero, G. Stipo, Experimental
effective provided that the TRM is placed under the fire-resistant investigation on bond behaviour of cement-matrix composites for
insulating material. In this case, the effectiveness of the retrofitting strengthening masonry structures, J. Compos. Constr. 20 (1) (2016) 04015041.
increases with the thickness of the fire insulation. [11] P.D. Askouni, C.G. Papanicolaou, Experimental investigation of bond
between TRM overlay and masonry, in: Proceedings of 10th International
From the results obtained in this study the authors believe that
Conference on Structural Analysis of Historical Constructions (SAHC2016),
TRM jacketing may be combined effectively with thermal insula- 2016.
tion, which can be fire-resistant too. The proposed system provided [12] F. Parisi, G.P. Lignola, N. Augenti, A. Prota, G. Manfredi, Nonlinear behaviour of
a masonry subassemblage before and after strengthening with inorganic
an extremely promising solution for combined structural and
matrix-grid composites, J. Compos. Constr. 15 (5) (2011) 821832.
energy retrofitting of masonry subjected to out-of-plane bending. [13] M. Harajli, H. ElKhatib, J. Tomas San-Jose, Static and cyclic out-of-plane
Further investigation is needed to enhance the experimental data- response of masonry walls strengthened using textile-mortar system, J. Mater.
base (part of this work is under way) and to optimize the proposed Civ. Eng. 22 (11) (2010) 11711180.
[14] S. Babaeidarabad, F. De Caso, A. Nanni, Out-of-plane behavior of URM walls
solution. strengthened with fabric-reinforced cementitious matrix composite, J.
Compos. Constr. 18 (4) (2014) 04013057.
[15] L. Garmendia, J.T. San-Jose, P. Larrinaga, Rehabilitation of masonry arches with
Acknowledgements compatible advanced composite material, Constr. Build. Mater. 25 (2011)
43744385.
[16] L. Koutas, T.C. Triantafillou, S.N. Bousias, Analytical modeling of masonry
The authors wish to thank Ms A. Petropoulou for her assistance infilled RC frames retrofitted with textile reinforced mortar, J. Compos. Constr.
in the experimental program. The work reported in this paper was 19 (5) (2015). 04014082.
partially funded by the European Commission, through the FP7 ITN [17] L. Koutas, S.N. Bousias, T.C. Triantafillou, Seismic strengthening of masonry
infilled RC frames with TRM: experimental study, J. Compos. Constr. 19 (2)
project ENDURE.
(2015). 04014048.
[18] M. Bomberg, J. Lstiburek, F. Nabhan, Long-term, hydrothermal performance of
exterior insulation and finish systems (EIFS), J. Build. Phys. 20 (3) (1997) 223
References 248.
[19] D. Anastaselos, E. Giama, A.M. Papadopoulos, An assessment tool for the
[1] T.C. Triantafillou, C.G. Papanicolaou, P. Zissimopoulos, T. Laourdekis, Concrete energy, economic and environmental evaluation of thermal insulation
confinement with textile reinforced mortar (TRM) jackets, ACI Struct. J. 103 (1) solutions, Energy Build. 41 (11) (2009) 11651171.
(2006) 2837. [20] Y. Huang, J.L. Niu, T.M. Chung, Study on performance of energy-efficient
[2] C. Faella, E. Martinelli, E. Nigro, S. Paciello, Tuff masonry walls strengthened retrofitting measures on commercial building external walls in cooling-
with a new kind of C-FRP sheet: experimental tests and analysis, in: dominant cities, Appl. Energy 103 (2013) 97108.
Proceedings of 13th World Conference on Earthquake Engineering, paper no. [21] D.I. Kolaitis, E. Malliotakis, D.A. Kontogeorgos, I. Mandilaras, D.I. Katsourinis,
923, 2004. M.A. Founti, Comparative assessment of internal and external thermal
T.C. Triantafillou et al. / Construction and Building Materials 133 (2017) 113 13

insulation systems for energy efficient retrofitting of residential buildings, [23] EN 1015-11, Methods of test for mortar for masonry Part 11: determination
Energy Build. 64 (2013) 123131. of flexural and compressive strength of hardened mortar, European
[22] B.P. Jelle, Traditional, state-of-the-art and future thermal building insulation Committee for Standardization, Brussels, 1993.
materials and solutions properties, requirements and possibilities, Energy [24] EN 1363-1, Fire resistance tests Part 1: general requirements, European
Build. 43 (2011) 25492563. Committee for Standardization, Brussels, 1999.

You might also like