Download as pdf or txt
Download as pdf or txt
You are on page 1of 9

DOC.

NUMBER REV

TECHNICAL DATA - APPENDIX B2


MCR02041 02

JOB CUSTOMER

JCB162895
P.O. IMAGRO CONSTRUCTION SRL
TPD-FPO-NAC-E-015-2016
PROJECT DESCRIPTION

NEW ASSIUT COMBINED CYCLE ADD-ON


SITE

-
PARTS NUMBER

Rev. Date Description Checked Approved


01 19-11-2016 FIRST ISSUE M.Freschi P.Conti
02 09-01-2017 AS PER COMMENTS M.Freschi P.Conti

This document is of the exclusive property of the BORRI company.


1 - 09
It is strictly forbidden partial or total re production unless previously authorized
Specification 10083A-9-3PS-ED00-00001
Appendix B2

APPENDIX B2

TECHNICAL DATA SYSTEM NO. 2

DC AND UNINTERRUPTABLE POWER SUPPLY SYSTEM


(Specification 10083A-3PS-ED00-00001)

B. GENERAL
Supplier shall furnish the following data and shall guarantee that the performance of
the equipment will be at least as good as stated.
Supplier agrees that in the event of a conflict between the requirements of the
technical specifications and the Technical Data included herein, the requirements of
the technical specifications shall govern.
This summary represents minimum data provided by Supplier for each item of
equipment
Supplier shall furnish detailed description, specifications and lists of all features to
be furnished.

Supplier shall furnish List of maintenance tools included

1.0 BATTERIES

1.1 EQUIPMENT / INSTALLATION INFORMATION

1.1.1 Type

a. Manufacturer FIAMM
b. Battery Type VENTED L.A.
c. Model No. 1XLM3000

1.1.2 Weight

a. Battery, including electrolyte, kg 222 (each)

b. Battery rack, complete, kg 7240 & 3630

1.1.3 Overall dimensions


3450x920x1600
a. Battery rack, L x W x H, mm 3450x920x600
TWO TIERS
b. Configuration (e.g., two-tier, back to back, etc.) ONE TIE

1.1.4 Working space and clearance (If Required)

a. Front, mm 1000

b. Back, mm 0

c. Right, mm 1000

d. Left, mm 1000

B2-1
Rev. 0
PGESCo Confidential PGESCo 2016. All rights reserved.
Specification 10083A-9-3PS-ED00-00001
Appendix B2

1.1.5 Civil works interfaces

a. Loading
7240
Self weight 3630

Installation loads (if any specified) N.A.


Operating loads (if any specific required) N.A.

b. Floor penetrations/openings

Dimensions, (W x L), mm N.A.

Number N.A.

c. Anchorage requirement

Anchor bolts (type, size, number) EXPANTION,M12,40

Others N.A.

d. Embedded items

Mounting skid (type, dimensions) N.A.

Others N.A.
1.1.6 Onsite Storage

a. State recommendations for short-term onsite storage (6


months or less) or provide storage procedures WE WILL
b. State recommendations for long-term onsite storage (over 6 PROCEDURE
months) or provide storage procedures

1.2 DESIGN DATA (Include complete catalog information)

1.2.1 One-minute rating of battery on which contract is based, A 1142A


Ten -hour rating at 25 C as per IEC 60896 on which contract is
1.2.2
based, Ah 315

1.2.3 Maximum short circuit current of battery, A 20400

1.2.4 Internal resistance of cell at 25 C, ohm 0.100


Internal resistance of complete battery, including intercell
1.2.5 0.100
connectors, at 25C and full charge, ohm

1.2.6 Recommended charging rates at 25 C

a. Floating minimum, V, A 2.24V/C 315A


b. Boosting maximum, V, A 2.30V/C 315A

c. Equalizing maximum, V, A 2.60V/C 315A

1.2.7 Final volts per cell at end of 2 hours 1.85

B2-2
Rev. 0
PGESCo Confidential PGESCo 2016. All rights reserved.
Specification 10083A-9-3PS-ED00-00001
Appendix B2

1.2.8 Number of cells 59


1.2.9 Type of terminal seal used MIO

1.2.10 Cell container material SAN

1.2.11 Volume of liquid per cell, liters 52.6


Minimum temperature at which the batteries will meet the duty
1.2.12
cycle requirement, C 20
Maximum hydrogen evolution charging at equalizing Voltage, 40
1.2.13 3
C, m /hr 40
Maximum and normal heat generated to room by battery, watts
1.2.14
(during charging and discharging) 2899

1.2.15 Battery Room minimum required ventilation rate N.A.

1.2.16 Maximum storage period without float charge, months 60

1.2.17 Life time of battery, years 20

2.0 BATTERY MONITORING SYSTEM (BMS)

2.1 EQUIPMENT / INSTALLATION INFORMATION

2.1.1 Type

a. Manufacturer GENEREX
b. Model No BACS
2.1.2 Weight, kg 50

2.1.3 Dimensions, W x D x H, mm 400X510X210

2.2 DESIGN DATA (Include complete catalog information)

2.2.1 Number of strings 2


2.2.2 Number of cell channels 59

2.2.3 Measurement Range:

a. Cell Voltage (V) 1.25-3.2

b. Cell Resistance () 20-6000


c. String Voltage (V) 125

d. Discharge Current (A) 1500

e. Float Current (A) 315

2.2.4 Operating Temperature range (C) 0-60

2.2.5 Local / Remote alarm notification AS PER DATA SHEET

B2-3
Rev. 0
PGESCo Confidential PGESCo 2016. All rights reserved.
Specification 10083A-9-3PS-ED00-00001
Appendix B2

2.2.6 Digital input/ output permit monitoring AS PER DATA SHEET

2.2.7 Data Storage capacity (MB) AS PER DATA SHEET

2.2.8 Enclosure degree of protection (IP) 31

2.2.9 Human Machine Interface(HMI):

f. Manufacturer BACS

a. Model number (include catalog information) TOUCH PANEL PC

b. Processor Model INTEL ATOM N2600

c. Memory (MB) 2048MB DDR3

d. Password for security (Yes/No) NO

2.2.10 Total DC load consumption, kW N.A.


2.2.11 Total AC load consumption, kW 0.5
3.0 BATTERY CHARGERS

3.1 EQUIPMENT / INSTALLATION INFORMATION

3.1.1 Type

a. Manufacturer BORRI

b. Model No RTB.2
3.1.2 Weight

a. Each battery charger, kg (net/shipping) 1000

b. Heaviest piece to be shipped as a unit, kg 1000

3.1.3 Overall dimensions

a. Each battery charger, W x D x H, mm 2400X1000X2200

b. Largest piece to be shipped as a unit, W x D x H, mm 1800X1000X2200

3.1.4 Cable entry TOP

3.1.5 Working space and clearance (If Required)

a. Front, mm

b. Back, mm 100

c. Right, mm

d. Left, mm

B2-4
Rev. 0
PGESCo Confidential PGESCo 2016. All rights reserved.
Specification 10083A-9-3PS-ED00-00001
Appendix B2

3.1.6 Civil works interfaces

a. Loading

Self weight 1000


Installation loads (if any specified) N.A.

Operating loads (if any specific required) N.A.

b. Floor penetrations/openings

Dimensions, (W x L), mm N.A.

Number N.A.

c. Anchorage requirement

Anchor bolts (type, size, number) EXPANTION,M12,16

Others N.A.

d. Embedded items

Mounting skid (type, dimensions) N.A.

Others N.A.
Onsite Storage
3.1.7
a. State recommendations for short-term onsite storage (6
months or less) or provide storage procedures WE WILL PROVIDE
b. State recommendations for long-term onsite storage (over 6 PROCEDURE
months) or provide storage procedures

3.2 DESIGN DATA (Include complete catalog information)


Maximum and normal output current, at nominal DC voltage, for
3.2.1
each battery charger, A 811
3.2.2 DC nominal voltage, output (V) 125
3.2.3 Equalizing voltage (V) N.A.
3.2.4 Boosting voltage (V)
153.4
3.2.5 Conversion efficiency, each battery charger at rated output 92%

3.2.6 Nominal AC voltage input (V) 400VAC


3.2.7 Power factor, each battery charger at rated output and
nominal AC voltage input 0.8
3.2.8 Maximum AC withstand transient input voltage for 10
microseconds 460VAC
AC input Current Distortion Limits(Percent of Maximum Demand
3.2.9
Current )

B2-5
Rev. 0
PGESCo Confidential PGESCo 2016. All rights reserved.
Specification 10083A-9-3PS-ED00-00001
Appendix B2

a. Odd % 5.9%
b. Even harmonics (% of odd harmonics) 1.2%
c. Total Demand Distortion % <6% WITH THD FILTER
Maximum DC withstand transient input voltage for 10
3.2.10 TBA
microseconds

3.2.11 Maximum charger output voltage and current, V/A 160V/1141A


Regulation and ripple, maximum within load ranges given in table
3.2.12 below
(Note: Values entered are to be applicable to all chargers unless
otherwise noted.)

Regulation Ripple
a. No-load to full load output with input
voltage constant, percent 0.5% / 1%
b. 10 percent load to full load output with input
voltage constant, percent 0.5% / 1%
c. No-load to full load output, percent with
input voltage 10 percent 0.5% / 1%
d. 10 percent load to full load with input
voltage 10 percent, percent 0.5% / 1%

3.2.13 Time after ac power restoration to full dc output restoration 5S


WE WILL PROVIDE
3.2.14 Maintenance schedule for component replacement PROCEDURE

3.2.15 Audible noise level, dB @ 1 m <70


3.2.16 Heat generated to room at full load, watts 15.2KW
3.2.17 Enclosure Degree of Protection (IP) 31

3.2.18 Total DC load consumption, kW 167.5

3.2.19 Total AC load consumption, kW 337

4.0 DC SWITCHBOARDS

4.1 EQUIPMENT / INSTALLATION INFORMATION

4.1.1 Type

a. Manufacturer BORRI

b. Model No. DCDB

4.1.2 Weight

a. Each switchboard, kg (net/shipping) 600

B2-6
Rev. 0
PGESCo Confidential PGESCo 2016. All rights reserved.
Specification 10083A-9-3PS-ED00-00001
Appendix B2

b. Heaviest shipping section, kg (net/shipping) 600

4.1.3 Dimensions

a. Each switchboard, (W x D x H), mm 1000X1000X2200

b. Largest shipping section,(W x D x H), mm 1000X1000X2200

4.1.4 Cable entry

4.1.5 Working space and clearance (If Required)

a. Front, mm

b. Back, mm 100

c. Right, mm

d. Left, mm

4.1.6 Civil works interfaces

a. Loading

Self weight 500


Installation loads (if any specified) N.A.

Operating loads (if any specific required) N.A.

b. Floor penetrations/openings

Dimensions, (W x L), mm N.A.

Number N.A.

c. Anchorage requirement

Anchor bolts (type, size, number) EXPANTION,M12,4

Others N.A.

d. Embedded items

Mounting skid (type, dimensions) N.A.

Others N.A.

4.1.7 Onsite Storage


a. State recommendations for short-term onsite storage (6
months or less) or provide storage procedures WE WILL SEND
b. State recommendations for long-term onsite storage (over 6 PROCEDURE
months) or provide storage procedures

B2-7
Rev. 0
PGESCo Confidential PGESCo 2016. All rights reserved.
Specification 10083A-9-3PS-ED00-00001
Appendix B2

4.2 DESIGN DATA (Include complete catalog information)

4.2.1 Bus size, dc amps 1200


4.2.2 Maximum short-circuit rating, dc amps 47

4.2.3 Bus material SILVERED COPPER

4.2.4 Fuse ratings, V dc/amps; max. interrupting, dc amps N.A.


4.2.5 Switch ratings, V dc/amps ACB 1600A 125VDC 50KA
Have all dc short-circuit withstand/interrupting ratings been
4.2.6
validated by test? NO
4.2.7 Heat generated to room at full load, watts NEGLIGIBLE
4.2.8 Enclosure Degree of Protection (IP) 31
4.2.9 Circuit Breaker

Manufacturer Model

-250A 630
AC A DC SCHNEIDER / NSX3205 MAGN. ONLY
-1600A
300DC
A DC
ABB /
E2N16
-250A AC SCHNEIDER NSX3205 MAGN. ONLY

B2-8
Rev. 0
PGESCo Confidential PGESCo 2016. All rights reserved.

You might also like