Professional Documents
Culture Documents
Grease Trap
Grease Trap
CHAPTER 9
Wastewater Grease and Sand/Oil Interceptor Standards
These standards should be read in conjunction with the (FOG) Fats, Oil and Grease
Policies and Procedures Manual available on Colorado Springs Utilities Internet site
under www.csu.org - Environment Wastewater Industrial Pretreatment and
the current version of the International Plumbing Code approved by Pikes Peak Regional
Building Department.
Paragraph Title
Number
9.01 General
9.02 Definition (Fats, Oil and Grease Policies and Procedures Manual)
9.03 Approval.
9.04 Design
9.05 Location
9.06 Maintenance
9.07 Sizing Requirements. Includes Calculation Sheet for Recommended Grease
Interceptor Sizing
9.08 Variances (Given only with the approval of the Colorado Springs Utilities)
9.09 Sand/Oil Interceptor
Car Wash Checklist for both Recycled and Wash Only car washes
9.10 Lint Interceptor for Laundromats
9.11 Swimming Pool (Indoors and outdoors)
9.12 Abandoned Interceptors and traps
9.13 Typical Abbreviations
In general under these standards, a Grease Interceptor is required for New Food Service
Establishments or when there is a significant construction/reconstruction or a substantial
change in use.
If a grease interceptor is required, all drains from the kitchen, food preparation, and
dishwashing areas shall be connected to the grease interceptor to ensure proper grease
handling/removal. Fixtures to be connected to a grease interceptor include, but are not
limited to, scullery sinks, pot and pan sinks, mop sinks, dishwashing and sanitizing
machines, soup kettles, hand sinks and floor drains located in areas where grease-
containing materials may exist. All designated kitchen waste shall enter the grease
interceptor through the inlet pipe only. No grey water from toilets, urinals or similar
fixtures shall enter through the grease interceptor.
Garbage disposals (garbage grinders) are strongly discouraged because they are not
efficient. Food particles are not ground small enough and particles carry over to the
grease interceptor, taking up interceptor capacity and providing a vehicle for grease
carry-over into the wastewater service line and wastewater mainline. If installed, garbage
disposals are required to be connected to an approved grease interceptor. Garbage
disposals cannot discharge to a grease trap or directly to the POTW.
Grease traps are approved for installation by Springs Utilities only through the variance
process and under very limited conditions because of their minimal holding capacities,
poor grease and oil separation capability and difficulty of cleaning. Grease traps will
only be considered on a case-by-case basis for locations that do no cooking on site, do
not serve catered food (pre-packaged food may be acceptable), do not have a dishwasher
or garbage disposal, and with the contingency that if conditions change (such as change
in menu, the installation of additional kitchen fixtures or improper maintenance to the
trap), a grease interceptor may be required. See Section 9.08 (Variances) in this chapter.
In the event of unique conditions, Springs Utilities may exercise its discretion to
determine which FOG removal device is required to be installed.
9.02 Definitions. (From the Fats, Oil and Grease (FOG) Policies and Procedures Manual)
a.) Best Management Practices (BMPs): Schedules of activities, prohibitions of
practices, maintenance procedures, and other management practices to prevent or
reduce the pollution of waters of the State. Best Management Practices include
procedures and practices that reduce the discharge of Fats, Oil and Grease (FOG) to
the building drain and to the Wastewater System. A list of BMPs are available in the
FOG Manual on the Springs Utilities website located at www.csu.org. All food
service establishments are required to develop and follow BMPs suitable for their
location.
b.) Collection Line: That portion of the Wastewater Treatment System, which collects
and transmits Wastewater from Users to the Wastewater treatment plant, excluding
Service Lines.
c.) Colorado Discharge Permit System (CDPS) permit: Means: Colorado Discharge
Permit System Permits No. CO-0026735 and No. CO00046850, issued by the State to
the City of Colorado Springs/Springs Utilities.
e.) Emulsifying Additives: Defined as any grease trap or grease interceptor additive
that suspends fat, oil and grease in solution. The fat, oil and grease gets carried
through the trap or interceptor to the wastewater collection system.
f.) Existing Food Service Establishment: Any Food Service Establishment, which is
not a New Food Service Establishment.
g.) Fat, Oil and Grease (FOG): A semi-solid, viscous liquid organic polar compound
derived from animal and/or plant sources that contain multiple carbon chain
triglyceride molecules. These substances are detectable and measurable using
h.) Food Preparation: Preparing food such that any wastewater from the activity has
the potential to cause harm or interference in the wastewater collection system.
i.) Food Service Establishment: Any facility engaged in preparing and/or serving food
for consumption by the public either on or off premises, such as but not limited to:
restaurants, commercial kitchens, cafeterias, nightclubs, coffee shops, delicatessens,
meat cutting-preparations, bakeries, bagel shops, grocery stores, caterers, hotels,
schools, churches, hospitals, correctional facilities, day cares and nursing care
institutions.
j.) Grease Interceptor: A tank that serves one or more fixtures and is remotely located.
Such Grease Interceptors include, but are not limited to tanks that capture Wastewater
from dishwashing and sanitizing machines, soup kettles, garbage grinders, pot and
pan sinks, mop sinks and hand sinks and floor drains in areas where grease containing
materials may exist. A Grease Interceptor is typically an outside, underground, multi-
compartment tank that reduces the amount of FOG in Wastewater prior to discharging
into the Wastewater Treatment System. (Reference Section 9.07) Springs Utilities
requires that the minimum capacity of the interceptor be no less than 325 gallons for a
facility without a dishwasher and 1000 gallons for a facility with a dishwasher.
Under-sizing the grease interceptor will increase maintenance costs and reduce its
efficiency. (Reference Section 9.07)
k.) Grease Trap: A device designed to retain grease from one to a maximum of four
fixtures per International Plumbing Code. A Grease Trap is not appropriate for use
on heated water (e.g. dishwasher) or in-line to a waste disposal unit (e.g., garbage
disposal and garbage grinders). A Grease Trap is a small, indoor device. Springs
Utilities requires that the capacity of the trap be no less than two hundred twenty
(220) pounds grease retention. Internal Grease Traps are not approved by Springs
Utilities for installation in Food Service Establishments that prepare food on site, or
serve catered food and have a dishwasher or a garbage disposal.
l.) Industrial User: A source of discharge, which introduces pollutants into the Publicly
Owned Treatment Works from any non-domestic source.
m.) Industrial Waste: Any liquid, solid or gaseous waste or form of energy or
combination thereof resulting from any process or operational procedures of an
Industrial User. Industrial Waste includes wastes generated from cleaning and
maintaining equipment and facilities used for the relevant process or operation.
p.) New Food Service Establishment: (1) Any Food Service Establishment for which a
contract for Significant Construction/Reconstruction, or for tenant finish in a pre-
existing building, was entered into after the Effective Date of this standard. (2) Any
food service establishment for which a Substantial Change in Use occurs.
Prior to using any non-emulsifying additive, a Material Safety Data Sheet (MSDS) is
required to be submitted to Springs Utilities-Industrial Pretreatment. The use of this
product may or may not be authorized by Springs Utilities.
r.) Publicly Owned Treatment Works (POTW): Any devices, facilities, structures,
equipment or works owned by the City or used by Springs Utilities for the purpose of
the transmission, storage, treatment, recycling and reclamation of Industrial and
Domestic Wastes, or necessary to recycle or reuse water at the most economical cost
over the estimated life of the system, including intercepting sewers, outfall sewers,
Collection Lines, pumping, power and other equipment, and their appurtenances and
excluding Service Lines.
s.) Sand/Oil Interceptor: Whenever the discharge of a fixture or drain may contain oil
(or solids and semi-solids heavier than water) that would be harmful to the drainage
system or cause a stoppage within the system, the discharge shall be through a
sand/oil interceptor. Sand/Oil interceptors are required whenever Springs Utilities
deems it necessary to protect its Wastewater Collection System.
t.) Service Line: The wastewater collector line extending from the wastewater disposal
facilities of the premises up to and including the connection to the Collection Line.
v.) Substantial Change in Use: a change in cuisine, food preparation, menu items,
seating capacity or similar operation which have the possibility of causing harm to, or
interference with, the wastewater collection or treatment system.
w.) User: Any person, firm, corporation, government or other entity that discharges,
causes or permits the discharge of Wastewater into the POTW.
x.) Wastewater: The liquid and water-carried Industrial or Domestic Wastes and
pollutants from dwellings, commercial buildings, industrial facilities and institutions,
including hauled liquid waste and any groundwater, surface water and storm water
that may be present, whether treated or untreated.
Except where otherwise specifically permitted, no wastes other than those requiring
separation shall be discharged into any interceptor. Two sets of plans, including
complete kitchen mechanical and plumbing sections shall be submitted to Springs
Utilities as part of the Utility Service Plan for approval prior to construction. Such plans
shall include the calculation of the size, type, location of the interceptor and out-fall
location to the main line for each interceptor. (Per City Code 12.5.803 Pretreatment
Facilities - Submission of Plans).
9.04 Design. All interceptors for grease and heavy solids shall be so designed and located as
to be readily accessible for inspection and cleaning and shall have a water seal of not less
than six (6) inches. Interceptor shall be constructed in accordance with the current version
of ASTM C 1227 and the design standards contained herein, and shall be approved by the
Springs Utilities, and shall have a minimum of two (2) compartments with fittings
designed for grease retention. There shall be a minimum of two ring and covers to
provide access for cleaning and inspection of all fixtures and compartments of the
interceptor. (Recommendation: A larger diameter manhole ring and cover maybe used to
access the outer and middle interceptor rings, if the middle plug is removed for clearing
purposes on the larger interceptors, at the request of the Developer and approved by the
Engineer) A minimum of one (1) access per ten (10) feet of interceptor length, additional
access shall be required for each additional ten (10) feet in length. The interceptor shall
be located within fifty (50) feet of the last appliance connected to the grease line within
the building. Manhole covers shall be gas-tight in construction, having a minimum
opening dimension of twenty-four (24) inches.
In traffic areas, the interceptor shall be designed to have adequate reinforcement and
cover (including piping), meeting HS-20 traffic loading specifications. Grease Interceptor
in traffic areas requires a concrete driving surface over piping with structural backfill
around piping.
Interceptor shall be designed so that they shall not become air bound if a closed cover is
used. The tank and the discharge line shall each be vented, and the vents shall not be tied
together less than forty-two (42) inches above the tank lid elevation. Reference:
Wastewater Construction Drawing C 2-4, Typical Restaurant Grease Interceptor.
Drawing details of outlet/drainage design (including size) is to be shown on the approved
construction or service plans. (Per City Code 12.5.803 Pretreatment Facilities;
Submission of Plans, City Code 12.5.407 Service Lines; Separate for each building;
Exceptions)
- Grease interceptors are required for any facility engaged in preparing and/or serving
food for consumption by the public. This includes but is not limited to restaurants,
grocery stores, cafeterias, schools, churches, coffee shops and any other business that
is engaged in preparing and/or serving food. Sand-Oil Interceptors are required for
any business which stores, repairs or services motor vehicles (including washing
activities).
- Grease or Sand/Oil interceptors shall not be installed in drive-through driveway
locations.
- Interceptors will be approved by Springs Utilities
- Interceptor must be drawn to scale and be shown on the Utility Services Plan.
- Only grease or oily wastes will be routed through these interceptors.
- Under sink grease traps will not be accepted in lieu of exterior grease interceptors.
- For shell only construction, provisions must be made for the installation of an
interceptor to serve any future tenant finish projects where food products may be
used.
Developers of shopping centers/strip buildings are required to install two dedicated sanitary
sewer lines. Stub outs shall be provided to direct the kitchen waste of future food service
facilities through the grease line into a common outside grease interceptor, then return the
effluent from the grease interceptor back into the building sanitary sewer through the grey water
line, as illustrated below. Property owners are responsible for ensuring common grease
interceptors are adequately maintained.
A sample trap shall be provided on the outlet side of each grease interceptor, before
the down stream clean-out and vent (Reference: Wastewater Construction Drawing C 2-
4 Typical Restaurant Grease Interceptor). The sample trap shall be a tee connection,
located within two (2) feet of the wall, on the outlet (downstream) pipe side. The tee shall
be extended to the surface (for inspection purposes) with a 4-inch pipe and a clean out
adapter used to cap the pipe. In areas where traffic may exist, a valve box configuration
shall be used to protect the inspection pipe.
(b) 24-Inch Diameter Manhole Rings and (Solid or Bolted) Cover reference Chapter 5
- Manholes
1. General. All twenty four (24) inch manhole ring and covers shall be manufactured
to meet HS-20 traffic load conditions and have a minimum inside ring clearance of
22-1/8 inches.
2. The manhole lid shall be drilled with a one-half inch (1/2) hole six (6) inches off
center to the right of the word WASTEWATER, with a rubber plug inserted into
the drilled hole to prevent infiltration. All ring and covers shall be cast iron,
Depending on the location of the manhole, the Springs Utilities will require Self-
Sealing lids in traffic areas or Self-Sealing bolt down lids in off-road (i.e. landscape
area) areas. All off-road locations require the cast iron ring to be secured to the
grease/sand-oil interceptor with securing bolts.
9.05 Location. All interceptors shall be readily accessible for inspection, servicing, and
maintaining and be in proper working condition (Planting restrictions are for trees only
unless specifically noted, no landscaping shall be permitted within fifteen (15) foot radius
clear from the center of manhole access location, also provide a sixteen (16) foot wide
access route to manholes in landscape areas. (Reference: Springs Utilities Site Design
Guidelines-Facilities Requirements, located on City of Colorado Springs web site)). The
use of ladders or the removal of bulky equipment such as dumpsters in order to inspect or
service interceptors shall constitute a violation of accessibility. Where feasible, all
interceptors shall be located outside of the facility served. Interceptor may not be installed
in any part of a building where food is handled. Location of all interceptors shall be
approved by Springs Utilities, and shall be shown on the approved service utility plan
connected to the outfall line.
9.06 Maintenance. The owner and/or lessee shall be jointly and severally responsible for efficient
cleaning and maintenance of the grease trap or interceptor. Both the inside grease trap and
outside interceptor are required to be completely cleaned when oil/grease and solids occupy
25 % of the holding capacity. Grease traps and interceptors are required to be inspected
monthly. Maintenance records shall be kept on site for at least three (3) years. Industrial
Pretreatment or other authorized personnel may perform unannounced inspections to verify
compliance. (Per City Code 12.5.804: Pretreatment Facilities; Operations) See the FOG
Manual for maintenance procedures located at the Colorado Springs Utilities website at
www.csu.org Environment Wastewater Industrial Pretreatment.
The designer shall size the grease interceptor using the spreadsheet shown at the end of
section 9.08 and the restaurant types as described in section 9.07(a).
(a) The following descriptions are to be used in helping to determine the recommended
size of a grease interceptor for food preparation and/or food serving facilities. To
determine the grease interceptor size, consideration must be given to the fat content of
the food prepared, number of kitchen drainage fixtures, seating capacity, customer
turnover rate, previous problems with the service line or main, compliance history of
the food establishment, eat-in or carryout, number of employees, hours of operation,
frequency of kitchen use, size of the kitchen, number and type of cooking appliances,
etc. The food service categories as described herein function only as a guide. Every
food establishment may not fit clearly within one category; therefore, it may be
necessary to combine characteristics and expected size ranges from more than one
category to determine the grease interceptor size.
High Volume:
Facilities often preparing three meals per day or having continuous food prep
(cooking) throughout much of the day. These facilities may prepare large
amounts of food for distribution to other locations. Examples may include full
service dine-in restaurants, buffets, hotels, large senior living facilities, hospitals,
food courts, grocery stores, caterers, etc. They typically have large or multiple
kitchens with a wide range in plumbing fixtures. These facilities frequently have
at least one large dishwasher with a large pre-wash sink and garbage disposal.
Additionally, there will likely be 2 and/or 3-compartment sinks, vegetable
preparation sinks, mop sinks, hand sinks, etc. Food items can be served on
disposable or washable dishware.
Facilities often cooking two meals per day, such as lunch and dinner with
washable eating utensils. They usually have a 50 150 person seating capacity.
Examples may include small senior living facilities, steak houses, gourmet burger
establishments, dine-in pizza places, seafood or ethnic restaurants high in fat
content. They typically have medium to large kitchens with a medium to large
dishwasher, 2 and/or 3-compartment sink, pre-wash sink with garbage disposal,
vegetable preparation sink, mop sink, hand sinks, etc.
Facilities often opening early and closing late that cook or fry a large variety of
food items throughout the day such as burgers, chicken, tacos, fries, etc. high in
fat content. These foods are all served on disposable paper products. They
typically have medium to small kitchens with a 3-compartment sink, vegetable
preparation sink, mop sink and hand sinks. A small countertop dishwasher may
be installed, but usually a pre-wash sink or garbage disposal is not present.
Facilities having few employees and/or limited hours of operation and meals
served. To a limited degree, foods may be prepared and cooked from scratch on
site, but more often foods are prepared and cooked elsewhere and delivered here
to be preheated. Most foods are served with washable eating utensils. These
facilities have a seating capacity of between 25 and 50. The kitchens are medium
to small with a wide range in plumbing fixtures. Potential plumbing fixtures
include a single, 2 or 3-compartment sink, small dishwasher, pre-wash sink with
or without garbage disposal, vegetable preparation sink, hand sinks, and mop
sink. Food service establishments in this category may be independent, family-
owned operations out of the main traffic flow, or some small schools.
Larger coffee houses will likely fall into this category. Although normally there
is minimal food preparation, a considerable amount of oil and grease is generated
from milk products disposed of down the drain.
Facilities having few employees and/or limited hours of operation and food
served. The foods are pre-packaged and may be heated using limited means prior
to consumption. All food is served on disposable paper products. These facilities
are prohibited from having garbage disposals. Under-the-counter dishwashers
will be considered on a case-by-case basis. Examples such as a convenience
store, small coffee shop, hot dog or ice cream stand, may fit this category.
(b) The minimum acceptable volume of a grease interceptor shall be not less than three
hundred and twenty-five (325) gallons. (With a dishwasher - 1000 gallons minimum
size.)
(c) A copy of the kitchen mechanical or plumbing plan, showing the number of fixtures
i.e. 3-comp sink, dishwasher, hand sink, floor drains, etc., is required to be submitted
Location:
a. Sand/Oil Interceptor shall be so installed and connected that they shall be at all times
accessible for inspection and cleaning of the intercepted waste.
e. Location of all Sand/Oil Interceptor and its outfall location shall be shown on the
approved construction or utility service plans.
f. Each sand/oil interceptor shall serve only one business establishment. Multiple
business connections to a single sand/oil interceptor are not permitted unless
approved by Springs Utilities in writing.
Springs Utilities requires that the minimum size of a sand/oil interceptor shall be five
hundred (500) gallons of total liquid capacity, meeting HS-20 traffic loading
specifications.
The maximum individual interceptor size shall be two thousand five hundred (2500) gallons, a
series of interceptors maybe necessary for larger sand/oil interceptor capacities greater than two
thousand five hundred (2500) gallons, based on cleaning and maintenance requirements.
Design criteria for sizing sand/oil interceptors are based on the following and with the
approval of Springs Utilities. Typical approved sizes of sand/oil interceptors are 500, 1000,
1500, 2500 gallon capacity (Traffic rated) or 500, 1000, 1500, 2250 (Non-traffic rated)
(check with local suppliers for correct sizing and specifications). (Reference: Wastewater
Construction drawing C 2-7 Typical Sand and Oil Interceptor for Automotive
Application.) In the event a sand/oil interceptor is installed that was not previously approved
by Springs Utilities, the User may be required to remove the device and install equipment
that conforms to the current Wastewater Line Extension and Service Standards.
Car Wash:
This includes but not limited to: manual, auto and recycled car wash facilities. (Reference
text later in this Chapter for car wash facilities)
Maximum wash floor area of 1500 sq. ft = 500 gallon interceptor
Wash floor area of 1501 to 3000 sq. ft = 1000 gallon interceptor
Floor area greater than 3,000 sq. ft, sizing with approval of Springs Utilities
Clean-outs shall be installed in the drainage piping inlet and outlet side of each sand/oil
interceptor. In areas where traffic may exist, the trap shall be designed to have adequate
reinforcement and cover (including piping), meeting HS-20 traffic loading specifications. If
piping is metal, corrosion protection shall be shown on the service plan per these
specifications. (Reference: Wastewater Construction drawing C 2-7 Typical Sand and Oil
Interceptor for Automotive Application.)
All on-site recycled water piping shall be manufactured and installed in accordance with the
International Plumbing Code and all governing codes, rules and regulations set down by
Regional Building Department and the City of Colorado Springs. All piping shall be
continuously and permanently marked with the manufacturers name or trademark, nominal
size and schedule or class indicating the pressure rating. There shall be no connection
between recycled water systems and the potable water system without the necessary
backflow connection device. (Per City Code 12.4.12 - Cross Connection Control).
Recycled water systems shall be completely separate from the potable water system; there
shall be no connection between recycled water systems and the potable water system without
the required backflow connection device. (Per City Code 12.4.12 - Cross Connection
Control). External area drains or catch basins exposed to the environment shall be connected
to the storm drainage system, only internal drains (covered) are permitted to connect to the
Springs Utilities sanitary sewer system.
a. Provide a copy of the mechanical plans for review in conjunction with the proposed car
wash utility plans.
b. Provide a detail of the internal trench drain needs to capture initial sand/mud (if
required).
c. Provide a detail/cross section of the reclaim/storage tanks and sand/oil interceptor on the
utility service plan or on the attached Plumbing/Mechanical plan submitted to
Development Services.
d. Provide a detail of the by-pass (plug valve) valves and the backwater valve (call out-
model and make on plans) per Springs Utilities Wastewater Line Extension and Service
Standards.
e. Show location of by-pass valves (if any) and Backwater valve (per Wastewater
Construction detail C 2-5) on the utility service plans. [A variance maybe given for the
manhole, with the approval of the Springs Utilities for manholes that are two to (2-3)
three feet deep, by using a plastic meter pit fitted with a standard manhole lid].
f. Recycle water lines shall be a minimum of five (5) to six (6) feet deep per Springs
Utilities Water Line Extension and Service Standards or wrapped in heat tape under a
concrete pad to prevent freezing.
g. Show clean outs every one hundred (100 ft) feet (if required) per Springs Utilities
Wastewater Line Extension and Service Standards.
h. Install Sand/Oil interceptors upstream of the first reclaim/storage tanks, per Wastewater
Construction drawing schematic in the Wastewater Line Extension and Service
Standards.
i. The outfall line from the facility to the main line shall be a minimum of six (6) inch
diameter @ 1.04% grade.
j. Sign off by Plumbing/Mechanical Engineer maybe required for the Recycled/Reclaimed
schematic on the Utility Service plan.
l. A (S.O.P.) Standard Operating Procedure manual should be sent to Infrastructure
Records, for Springs Utilities Inspection purposes only and future maintenance.
In traffic areas, the trap shall be designed to have adequate reinforcement and cover
(including piping), meeting HS-20 traffic loading specifications. Lint traps in traffic areas
require a concrete driving surface over piping with structural backfill around piping.
Maintenance. The lint interceptor should be cleaned (or pumped out) routinely to
prevent the escape of appreciable quantities of grease. Cleaning should be performed
when the interceptor is at 75% of lint/silt retention. The frequency of cleaning at any
given installation will vary depending on use. Pumping frequencies for Laundromats
usually range from once a month, to once every six months.
Sizing Criteria for Lint Interceptors. The lint interceptor is generally sized according
to the International Plumbing Code. The different variables include; number of washing
machines, wastewater flow rate, wastewater detention time, and storage factor and
detention time.
Note: Springs Utilities is not responsible for sizing lint interceptors for
Laundromats.
9.11 Swimming Pools (Indoors and outdoors).
All swimming pools shall discharge into a sanitary sewer line. The minimum size for a
swimming pool discharge trap shall be calculated based on a restricted discharge of water
of one hundred (100) gallons per minute entering the sanitary sewer line (without
discharging into the grease trap if a kitchen facility is part of the proposed structure). A
detail drawing of the proposed outlet/drainage design shall be shown on the approved
construction or service plans, also show the location/connection to sanitary sewer line.
The minimum size for a swimming pool discharge trap shall be calculated
based on a restricted discharge of water of one hundred (100) gallons per
minute entering the sanitary sewer line.