Perhitungan Cooling Load - by IND
Perhitungan Cooling Load - by IND
SPACE NAME :
SIZE (ft X ft): X = 0 (sq ft)
INTERNAL HEAT
People 8 People X 0.9 X 255
Power HP or KW X 0
Light 445.284 Watts X 3.4 X 0.96 X 1.125
Appliance Etc.
Additional Heat Gain
Sub total
Storage Sq m 0
Sub total
Safety Factor 5 %
Sub Total
Safety Factor 5 %
Sub Total
% Return Duct % Return Duct % Dehum &
Heat Gain + Leak. Gain + % HP Pump + Piupe Loss
0 3 0 4
BTU/HOUR
0.00
0.00
0.00
0.00
482.91
0.00
0.00
0.00
0.00
0.00
0.00
0.00
198.33
0.00
836.70
0.00
0.00
0.00
0.00
0.00
0.00
1927.80
0.00
1635.08
0.00
0.00
5080.82
0.00
5080.82
254.04
5334.86
0.00
99.79
5434.65
0.00
1852.20
0.00
0.00
0.00
0.00
1852.20
92.61
1944.81
194.48
0.00
2139.29
7573.94
898.13
0.00
8472.07
upe Loss
593.04
TR
ESTIMATED FOR LOCAL TIME PEAK LOAD LOCAL TIME
SUN TIME SUN TIME
HOURS OF OPERATION
CONDITION DB WB % RH DP GR/LB
OUTDOOR (OA) 86 82.4
ROOM (RM) 75 60
DIFFRENCE 11
OUTDOOR AIR
VENTILA- 8.4 People X 10 CFM/Person = 84.00
TION 37.8 Sq m 0 CFM/Sq Ft = 0.00
CFM Ventilation = 84.00
75 F) = 79.131489269 TEDB F
50 ) 52.913148927 TLDB F
Tabel 45 :
Bank room Meeting ro Office
CFM/perso 10 50 30
CFM/sq ft 0 1.25 0.25