Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

COMPACT, RICH-FEATURED, HOT

SWAPPABLE, ALL-IN-ONE
CONTROLLER
The Smartpack S covers all control and
monitoring needs of small to medium telecom
and industrial dc power systems. Status and
configuration is fully available through the
display locally, or through the Ethernet plug
both remote or locally.

Designed for the Flatpack S system platform,


the Smartpack S finds its way into many space
restricted application. Used in the 1U high,
265mm deep power racks, Smartpack S offers
comprehensive monitoring and control of a 2-
3kW system occupying less than 6 liters.

SMARTPACK S CONTROLLER
FOR 12VDC, 24VDC, 48 VDC & 60 VDC SYSTEMS
Doc 242100.410.DS3 v4

APPLICATIONS KEY FEATURES


TELECOM MOBILE / WIRELESS GRAPHICAL 2.2 TFT HIGH
RADIO BASE STATIONS/ CELL CONTRAST, HIGH RESOLUTION
SITES COLOR DISPLAY FOR EASY
NAVIGATION IN USER MENU
LTE / 4G / WIMAX
DISTRIBUTED ANTENNA ETHERNET FOR REMOTE OR LOCAL
1U 50A SYSTEM
SYSTEMS MONITORING AND CONTROL VIA
WEB BROWSER
BROADBAND
SNMP PROTOCOL WITH TRAP, SET
TELECOM FIXED AND GET ON ETHERNET. EMAIL OF
FIBER OPTICS / FTTX TRAP ALARMS
MICROWAVE 6 PROGRAMMABLE RELAY OUTPUTS
CABLE 1U 100A SYSTEM 6 PROGRAMMABLE MULTI-PURPOSE
BROADBAND INPUTS (DIGITAL INPUTS OR
ANALOG SIGNALS).
OFFSHORE AND PROCESS INDUSTRY COMPREHENSIVE LOGGING
SAFETY AND AUTOMATION AUTOMATIC BATTERY MONITORING
SYSTEMS (SAS) AND TEST
BATTERY QUALITY INDICATION
RAILWAY INFRASTRUCTURE (BASED ON TEST RESULTS)
CONTROL & PROTECTION
SIGNALING 3U SYSTEM BULK OUTPUT

Eltek Grterudveien 8, PB 2340 Strms, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek 2015 www.eltek.com
SMARTPACK S CONTROLLER
FOR 12VDC, 24VDC, 48 VDC & 60 VDC SYSTEMS
TECHNICAL SPECIFICATIONS
Model Smartpack S
Part number 242100.410

INPUT DATA
Voltage (nominal) 10 - 75 VDC
Power Consumption, max - no relays energized 3,1W (display sleep)
max - all relays energized 5,5W (display on)
SYSTEM CONNECTIONS - SYSTEM
MONITORS
Voltage sense, system voltage support 12 VDC, 24VDC, 48VDC & 60VDC
Current sense, shunt support 0 - 20mV and 0 - 60mV
Battery fuse monitoring Auxiliary switch NO/NC, Pull up/down
Load fuse monitoring Auxiliary switch NO/NC, Diode Matrix Pull up/down
Ground fault detection Simple bridge circuit detection

SYSTEM CONNECTIONS - LVD CONTROL


Battery disconnect 1 (latched or non-latched supported)
Load disconnect 1 (latched or non-latched supported)

INPUTS AND OUTPUTS


Digital configurations, Inputs #1-6 Auxiliary switch: NO/NC
Analog configurations, Inputs #1-4 Analog Voltage[0 - 10V]
4-20mA current measurement (through external 470k resistor)
Temperature (for NTC probe)
Analog configurations, Inputs #5-6 Analog Voltage[0-75V]
Symmetry measurement
Output configurations, Outputs #1-6 6x RelayDry/Form C
(alarms) Configurable Normally Open/Closed
[Max capacity 75V/2A/60W]

USER INTERFACE
Local 2.2 TFT 65k Colour display
QVGA resolution
4 keys

Ethernet port 10/100 BASE-T


HP Auto MDI/MDI-X
IP protocols: HTTP / SSL, SNMP v3, MODBUS TCP and pComm UDP (PowerSuite)

Serial port RS-232 and RS-485 on RJ11 connector


Serial protocols: MODBUS RTU, Modem Call-Back/SMS reporting (PSTN or GSM), COMLI,
CSCP and pComm (PowerSuite)

GENERAL SPECIFICATIONS
Dimensions (WxHxD) 72.2 x 43.0 x 220.7mm (2.8 x 1.7 x 8.7)
Temperature Range Operating -20 to +65C (-40 to 149F)

DESIGN STANDARDS
Electrical safety UL 60950-1-3rd edition, EN 60950-1-3rd edition
EMC ETSI EN 300 386 V.1.4.1
EN 61000-6-1 / -2 / -3 / -4
FCC Part 15 Subpart 109

Marine*) DNV- OS-D202, Ch.2 Sev.4 (DNV 2.4), Temperature Cl. B, Humidity Cl. B, Vibration Cl. A and
EMC Class B
Environment ETSI EN 300 019: 2-1 (Class 1.2), 2-2 (Class 2.3) & 2-3 (Class 3.2)
ROHS compliant
*) As part of CA0603.000 Flatpack S 3U Marine system

Doc 242100.410.DS3 v4 Specifications are subject to change without notice

Eltek Grterudveien 8, PB 2340 Strms, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek 2015 www.eltek.com