Rooftop VAV System PDF

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

engineers newsletter

volume 354 providing insights for todays hvac system designer

setpoint (Figure 1). In this case, only


energy-saving control strategies for cooling and heating are shut off; the

Rooftop VAV Systems supply fan continues to operate and


the outdoor-air damper remains open
to continue ventilating the building.

Rooftop variable-air-volume (VAV) between actual zone temperature and The optimal stop strategy also reduces
systems are used to provide comfort in occupied setpoint. It compares this the number of system operating hours,
a wide range of building types and difference with the historical saving energy by allowing indoor
climates. This system consists of a performance of how quickly the zone temperatures to drift early.
packaged rooftop air conditioner that has been able to warm up or cool
serves several individually-controlled down.
zones. Each zone has a VAV terminal
Figure 1. Optimal start and optimal stop
unit that is controlled by a temperature
sensor in the zone.
system occupied hours
system
This EN discusses HVAC system on off
control strategies that can be used to
save energy in rooftop VAV systems. optimal optimal
start stop
occupied
Optimal Start/Stop. In some setpoint
zone temperature
buildings, a simple time clock or time- temperature
of-day schedule is used to start and allows 2F drift
stop the HVAC system. During hours unoccupied below setpoint
when the building is expected to be setpoint
unoccupied, the system is shut off and temperature starts system as
late as possible
the temperature is allowed to drift
away from the occupied setpoint. The
mid 6 AM noon 6 PM mid
time at which the system starts again
in the morning is typically set to ensure
that the indoor temperature reaches Fan-Pressure Optimization. As
the desired occupied setpoint prior to The optimal start strategy reduces the
cooling loads change, the VAV
occupancy on either the coldest or number of system operating hours and
terminals modulate to vary airflow
warmest morning of the year. As a saves energy by avoiding the need to
supplied to the zones. This causes the
result, for most days, the system starts maintain the indoor temperature at
pressure inside the supply ductwork to
much earlier than needed. In turn, this occupied setpoint even though the
change. In many systems, a pressure
increases the number of operating building is unoccupied.
sensor is located approximately two-
hours and system energy use. thirds of the distance down the main
A related strategy is optimal stop. As
mentioned earlier, at the end of the supply duct. The rooftop unit varies the
An alternative approach is a strategy capacity of the supply fan to maintain
called optimal start. This strategy occupied period, the system is shut off
and the temperature is allowed to drift the static pressure in this location at a
utilizes a building automation system constant setpoint. With this approach,
(BAS) to determine the length of time away from occupied setpoint.
However, the building occupants may however, the system usually generates
required to bring each zone from more static pressure at part load than
current temperature to the occupied not mind if the indoor temperature
drifts just a few degrees before they necessary.
setpoint temperature. The system
waits as long as possible before leave for the day.
When communicating controllers are
starting, so that the temperature in used on the VAV terminals, it is
Optimal stop uses the BAS to
each zone reaches occupied setpoint possible to optimize this static-
determine how early heating and
just in time for occupancy (Figure 1). pressure control function to minimize
cooling can be shut off for each zone,
This optimal starting time is duct pressure, and save fan energy.
so that the indoor temperature drifts
determined using the difference Each VAV unit controller knows the
only a few degrees from occupied

2006 American Standard All rights reserved 1


Figure 2. Fan-pressure optimization it to be installed inside the rooftop
unit and tested at the factory. In this
location, it can also serve as the duct
static
pressure
high-pressure sensor, protecting the
sensor ductwork from damage in the event
of a fire damper closing.
supply P
fan

Supply-Air-Temperature Reset . In a
VAV system, it is tempting to raise the
supply-air (SA) temperature at part-load
conditions to save compressor and/or
VAV terminals
reheat energy. Increasing the supply-
air temperature reduces compressor
energy because it allows the
communicating BAS
compressor to operate at a warmer
suction temperature. The
corresponding higher suction pressure
current position of its air-modulation Lower sound levels. The supply fan reduces the compressor lift, reducing
damper. The BAS continually polls does not generate as much static the power required.
these individual controllers, looking for pressure and will typically generate
the VAV terminal with the most-open less noise. In addition, with lower In addition, supply-air-temperature
damper (Figure 2). The setpoint for the pressures in the supply duct, the reset makes an airside economizer
supply fan is then reset to provide just dampers in the VAV terminals will be more beneficial. When the outdoor air
enough pressure so that at least one more open, resulting in less is cooler than the SA temperature
damper is nearly wide open. This regenerated noise. setpoint, the compressors are shut off,
results in the supply fan generating and the outdoor- and return-air
only enough static pressure to push Reduced risk of fan surge. By dampers modulate to deliver the
the required quantity of air through this allowing the fan to operate at a lower desired supply-air temperature. A
"critical" VAV terminal unit. pressure when delivering reduced warmer SA temperature setpoint
airflow, the fan operating point is allows the compressors to be shut off
This control strategy, sometimes called kept further away from the surge sooner and increases the number of
fan-pressure optimization, has several region (Figure 3). hours when the economizer is able to
benefits: provide all the necessary cooling.
Flexibility of sensor location. Since
Reduced supply fan energy use. At this strategy uses the position of For zones with very low cooling loads,
part-load conditions, the supply fan VAV dampers to reset the pressure when the supply airflow has been
is able to operate at a lower static setpoint, the static-pressure sensor reduced to the minimum setting of the
pressure and consume less energy can be located anywhere in the VAV terminal, raising the supply-air
(Figure 3). supply duct. It can even be located temperature also decreases the use of
at the discharge of the fan, allowing reheat at the zone level.
Figure 3. Benefits of fan-pressure optimization
However, because the supply air is
warmer, zones that require cooling will
need more air to satisfy the cooling
load. This increases supply fan energy.

surge Finally, in non-arid climates, warmer


supply air means less dehumidification
static pressure

at the coil and higher humidity levels in


the zones. If dehumidification is a
concern, use caution when
10

implementing this strategy.


00

duct static
rp

pressure control
m
90
0

Supply-air-temperature reset should be


rp
m

s
ving 80
ener
gy s
a
fan-pressure 0 implemented so that it minimizes
rp
ntial m
pote optimization overall system energy use. This
requires considering the trade-off
between compressor, reheat, and fan
airflow

2 Trane Engineers Newsletter volume 354 providing insights for todays HVAC system designer
energy, as well as the impact on space Table 1. Supply-air-temperature reset
humidity levels. Table 1 contains some
general guidance to determine when Conditions that favor using
supply-air-temperature reset Comments
this strategy might provide the most
Mild climates that have many hours when In this type of climate, the economizer-
benefit. outdoor dry-bulb temperature is below 60F related benefits typically outweigh the
impact on increased supply fan energy.
These competing issues are often best
Systems with VAV terminals that have Higher minimum airflow settings increase
balanced by first reducing supply minimum airflow settings higher than the likelihood that reheat will be needed
airflow, taking advantage of the 30% of design airflow to avoid overcooling the zones.
significant energy savings from
Efficient air distribution system design Low pressure losses result in less of a
unloading the fan. Once fan airflow has fan energy penalty for the higher airflows
been reduced, raise the supply-air that result from raising SA temperature.
temperature to minimize reheat energy Systems with interior zones that have The variable loads might allow these zones
and enhance the benefit of the airside varying cooling loads to still be satisfied with a warmer supply-air
temperature.
economizer. While one could dream up
numerous control schemes, the
Conditions that reduce the potential
simplest approach is probably most to save energy with supply-air- Comments
common. Figure 4 shows an example temperature reset
of a supply-air-temperature reset Hot climates that have relatively few hours In this type of climate, the economizer-related
when the outdoor dry-bulb temperature is benefits are minimal.
strategy based on the changing below 60F
outdoor dry-bulb temperature. Systems with efficient part-load fan Using a VFD on the supply fan, and/or the
modulation fan-pressure optimization control strategy,
When the outdoor temperature is may make it more advantageous to reduce
warmer than 70F, no reset takes place supply airflow to save fan energy, rather than
increase airflow and save compressor energy.
and the SA temperature setpoint
Inefficient air distribution system design High pressure losses result in a significant fan
remains at the design value of 55F. energy penalty for the higher airflow that
When it is this warm outside, the accompanies a warmer supply-air temperature.
outdoor air provides little or no cooling Systems that serve some zones that have These zones will require near-design airflow
benefit for economizing. The cooling nearly-constant cooling loads during all occupied hours, limiting the ability to
raise supply-air temperature. Investigate using a
load in most zones is likely high separate system to serve these zones.
enough that reheat is not required to
Source: California Energy Commission, Advanced Variable Air Volume System Design Guide, 2003.
prevent overcooling. In addition, the
colder (and drier) supply air allows the and it is likely that some zone-level When considering using supply-air-
system to provide sufficiently dry air to reheat can be avoided. temperature reset in a rooftop VAV
the zones, improving part-load
system:
dehumidification. Finally, when the outdoor temperature
is colder than 60F, no further reset First analyze the system to determine
Figure 4. Supply-air-temperature reset occurs, and the SA temperature if the savings in compressor and
based on OA temperature setpoint remains at 60F. Limiting the reheat energy will outweigh the
amount of reset to 60F allows the increase in fan energy.
system to satisfy the cooling loads in
SA temperature setpoint, F

61

60 interior zones without needing to If higher space humidity levels are a


59 substantially oversize VAV terminals concern, consider either disabling
58 and ductwork. reset when it is humid outside, or
57 providing one or more humidity
56
Alternatively, some systems reset the sensors to override the reset function
55
SA temperature setpoint based on the whenever humidity in the zone
temperature in the "critical" zone. This exceeds some maximum limit.
50 55 60 65 70 75 80
is the zone that is most nearly at risk of
outdoor dry-bulb temperature, F
overcooling, which would require For interior zones with near-constant
When the outdoor temperature is activating local reheat. A building cooling loads during occupied
between 60F and 70F, the SA automation system (BAS) monitors the periods, calculate design airflows for
temperature setpoint is reset at a 2-to- temperature in all zones, finding the those zones based on the warmer,
1 ratio. That is, for every 2F change in critical zone that is closest to heating reset supply-air temperature (60F in
outdoor temperature, the setpoint is setpoint. The rooftop unit then resets the example from Figure 4). While
reset 1F. In this range, supply-air- the SA temperature setpoint to prevent this may require larger VAV terminals
temperature reset enhances the this critical zone from needing to and ductwork, it allows the use of
benefit provided by the economizer activate reheat. supply-air-temperature reset during

providing insights for todays HVAC system designer Trane Engineers Newsletter volume 354 3
cooler weather, while still providing Figure 5. Demand-controlled ventilation at the zone level
the necessary cooling to those
weather-independent, interior communicating BAS
zones.
TOD
Design the air distribution system lounge rest mech storage office
for low pressure losses and use the room room
fan-pressure optimization strategy
to minimize the fan energy penalty CO2 OCC
that accompanies a warmer SA
temperature. vestibule corridor

Ventilation Optimization . In a
typical VAV system, the rooftop unit

elevators
delivers fresh outdoor air to several, OCC CO2
individually-controlled zones. Demand-
reception area office conference room computer room
controlled ventilation (DCV) involves
resetting intake airflow in response to
variations in zone population. While
commonly implemented using carbon occupant is present. When requirement based on anticipated
dioxide (CO2) sensors, occupancy unoccupied, the controller lowers the population.
sensors, or time-of-day (TOD) ventilation requirement for the zone.
schedules can also be used. Occupancy sensors are relatively These various zone-level DCV
inexpensive, do not need to be strategies can be used to reset the
Ventilation reset involves resetting calibrated, and are already used in ventilation requirement for their
intake airflow based on variations in many zones to control the lights. respective zones for any given hour.
system ventilation efficiency. This zone-level control is then tied
Finally, zones that are sparsely together using ventilation reset at the
One approach to optimizing ventilation occupied or have predictable system level (Figure 6).
in a multiple-zone VAV system is to occupancy patterns may be best
combine the various DCV strategies at controlled using a time-of-day In addition to resetting the zone
the zone level (using each where it schedule. This schedule can either ventilation requirement, the controller
best fits) with ventilation reset at the indicate when the zone will normally on each VAV terminal continuously
system level. be occupied vs. unoccupied, or can be monitors primary airflow being
used to vary the zone ventilation delivered to the zone. The BAS
With this strategy, CO2 sensors are
installed only in those zones that are Unoccupied Humidity Control periods, so delivering this cold air will
densely occupied and experience result in overcooling. Reheat coils in the
A VAV system typically dehumidifies VAV terminals, and possibly a boiler and
widely varying patterns of occupancy. effectively over a wide range of operating hot water pumps, will need to be
For the example building in Figure 5, conditions because it continues to deliver activated.
CO2 sensors are installed only in the cold, dry air at part-load conditions. As
conference room and the lounge. long as supply-air-temperature reset is An energy-saving alternative is to equip
used with caution, and reheat is available the rooftop unit with hot gas reheat. When
These zones are the best candidates
for those VAV terminals that have high after-hours dehumidification is needed,
for CO2 sensors, and provide "the minimum airflow settings or experience the rooftop unit turns on and diverts hot
biggest bang for the buck." These very low cooling loads, a VAV system will refrigerant vapor leaving the compressor
sensors reset the ventilation typically provide supply air at a dew point through a refrigerant-to-air heat
requirement for their respective zones that's low enough to prevent elevated exchanger that is located in the airstream,
indoor humidity levels during occupied following the evaporator coil. Sensible
based on measured CO2. periods. heat is transferred from the hot refrigerant
to reheat the dehumidified air leaving the
However, zones that are less densely However, controlling humidity levels isn't evaporator.
occupied or have a population that only a priority when the building is
varies only a little (such as private occupied. When indoor humidity rises too This strategy uses heat recovered from
high during unoccupied times, one option the refrigeration circuit to reheat centrally,
offices, open plan office spaces, or
is to turn on the rooftop unit and and saves energy by avoiding the use of
many classrooms) are probably better dehumidify recirculated air to 55F or so. new energy to reheat remotely at the VAV
suited for occupancy sensors. In Figure However, there is typically very little terminals.
5, each of the private offices has an sensible load in the zones during these
occupancy sensor to indicate when the

4 Trane Engineers Newsletter volume 354 providing insights for todays HVAC system designer
Figure 6. Ventilation reset at the system level
strategies in an office building that has
a typical rooftop VAV system. The
optimized system uses the optimal
rooftop unit with controls start, supply-air-temperature reset, and
OA Reset outdoor airflow (Vot) ventilation optimization strategies
discussed in this EN. In addition, the
SA RA supply fan is controlled based on fan-
pressure optimization, rather than on a
constant setpoint in the ductwork.

The optimized rooftop VAV system


reduced the HVAC energy use by about
30% for the building in both Atlanta
CO2 OCC CO2 OCC and Los Angeles, and by 33% in
communicating BAS DDC/VAV terminals
Minneapolis.
New OA setpoint (Vot) Required ventilation (Voz)
Actual primary airflow (Vpz)
There is a real potential to save energy
in rooftop VAV systems through
periodically gathers this data from all ventilation airflow (cfm) in every zone optimized system control strategies.
VAV terminals and solves the for every hour. This savings reduces operating costs
ventilation reset equations (prescribed for the building owner and can help in
by ASHRAE Standard 62) to determine Uses system-level ventilation reset achieving points toward LEED
how much outdoor air must be brought equations that are explicitly defined in certification.
in at the rooftop unit to satisfy all zones an industry-wide standard. Using Article by John Murphy, applications
served. Finally, the BAS sends this equations from ASHRAE 62 improves engineer,Trane. You can find this and previous
the "defend-ability" of the control issues of the Engineers Newsletter at
outdoor airflow setpoint to the rooftop www.trane.com/engineersnewsletter. To
unit which modulates a flow-measuring strategy. comment, e-mail comfort@trane.com.
outdoor-air damper to maintain this
new setpoint. Summary. The impact of any energy-
saving strategy on the operating cost
In a DDC/VAV system, this strategy is of a specific building depends on
fairly easy to implement because the climate, building usage, and utility
necessary real-time information is costs. Building analysis tools (like
already available digitally. Combining TRACE 700) can be used to analyze
DCV at the zone level with ventilation these strategies and convert energy
reset at the system level has the savings to operating cost dollars that
following benefits: can be used to make financial
decisions.
Assures that each zone is properly
ventilated without requiring a CO2 Figure 7 shows the potential energy
sensor in every zone. CO2 sensors savings of using these various
are used only in those zones in which
Figure 7. Energy-saving potential of optimized control
they will bring the most benefit. This
minimizes installed cost and avoids 100

the periodic calibration and cleaning


required to assure proper sensor 80
HVAC energy consumption, % of base

operation. For the other zones,


occupancy sensors and time-of-day
60
schedules are used to reduce
ventilation.
40
Enables documentation of actual
ventilation system performance. The 20
VAV controllers communicate the
ventilation airflow for every zone to
the BAS, even for those zones that do 0
not have a CO2 sensor. The BAS can Atlanta Los Angeles Minneapolis

be used to generate reports showing base system optimized system controls

providing insights for todays HVAC system designer Trane Engineers Newsletter volume 354 5
Trane
A business of American Standard Companies
www.trane.com

For more information, contact your local Trane


office or e-mail us at comfort@trane.com

Trane believes the facts and suggestions presented here to be accurate. However, final design and
application decisions are your responsibility. Trane disclaims any responsibility for actions taken on
the material presented.

6 Trane Engineers Newsletter volume 354 ADM-APN022-EN (October 2006)

You might also like