Material Specifications:
A. All galvanized ductwork is fabricated by using ASTM A90, A568, A653, and A924
commercial grade lock forming G-90/G-60 materials.
B. All material and gauges fabricated per code and customer request.
C. Options of stainless steel, aluminum, galvaneal and other materials are available
upon request.
Ductwork Specifications:
A. Full Section (wrap around): One piece joint section with one button lock or
Pittsburgh lock longitudinal seam and end treatment required for joining
connectors.
B. Half Section: Two-piece joint section with two button lock or Pittsburgh lock
longitudinal seams and end treatment required for joining connectors.
C. Four Piece Section: Four-piece joint section with four button lock or Pittsburgh
longitudinal seams and end treatment required for joining connectors.
D. All duct is beaded on 12 centers, with first bead 6 from end for extra strength.
Cross breaking is available upon request.
E. All duct is available in any length requested. Standard lengths are 5 (59).
F. All slips and drives, nuts, bolts, gaskets, and reinforcements are included on duct
and fitting quotes.
G. All duct and fittings are available lined or unlined.
H. All rectangular duct is shipped unassembled (KD), unless otherwise requested.
I. All rectangular fittings are shipped assembled, unless otherwise requested
The installing contractor should select the duct system consistent with the static
pressure class, applicable sealing requirements, materials involved, duct support
intervals, and other provisions for proper assembly of ductwork. The precise type, size,
material, and fasteners used in joint assemblies are in several instances left open to the
judgment of the contractor; consult SMACNA HVAC Duct Construction Standards
Manual, Uniform Mechanical Code, and/or job code requirements.
USED FOR
MED PRESSURE DUCT
USED FOR
LOW PRESSURE DUCT
- FOR MED PRESSURE DUCT
- FOR LOW PRESSURE DUCT
- FOR LOW PRESSURE DUCT
- USED BY MED PRESSURE DUCT
SILVER SHEET ENTERPRISES INC.
Sheet Metal * Ductwork * Rectangular * Spiral * Oval * Supply
General: Provide static pressure, quantity, type, size and connection for fittings and ductwork. All
double wall sizes are inside dimension.
Construction: Double wall rectangular duct and fittings to be fabricated in accordance with 2005
SMACNA "HVAC Duct Construction Standards, Metal and Flexible. Conform to the requirement in the
referenced standards for metal thickness, conduits and tie rod applications and joint types. External
reinforcement is to be field installed and coordinated with duct hangers
Metal: Galvanized Steel of ASTM Standard A653 (formally A527) and 2005 SMACNA Standards.
Fittings: Bead duct sizes that are 14" and larger, (cross-break on request), longitudinal seam shall be
pittsburgh lock. Fabricate elbows, transitions, offsets, mitered elbows (turning vanes are available by
request) and 90 branch connections in accordance with SMACNA 2005 standards.
Ductwork: Bead duct sizes that are 14" and larger, (cross- break on request), longitudinal seam shall be
pittsburgh lock. Standard TDC ductwork length is 56". Standard Slip and Drive ductwork length is 591/2.
Connections: Double wall ductwork and fittings are TDC flange connection.(Slips/Drives and other
connections available on request).
Inner Liner: Ductwork & Fittings: Perforated 3/32" holes on 3/16" stager centers with 22% open
area. Ductwork that is up to or equal to 30" in width will be fabricated with 24 gauge perforated
inner material, any ductwork larger than or equal to 31" in width will be fabricated using 22 gauge
perforated inner material. Solid galvanized inner liner is available by request.
Insulation: 1" thick liner, unless specified otherwise. Liner to be secured with adhesive and mechanical
fasteners per SMACNA.